Technical data

13
Pac k ag ed Ai r Con d i tion e rs
High Efficiency
FDU71/100/125/140V
Return air option
RC-E3
(Option)
Wired remote control
Outline drawing (Unit:mm)
FDU71V
FDU100,125,140V
Height
297mm
The FDU71 noise level is only 37dB on low fan. Weight is only 40kg
and height 297mm. In addition a 600mm drain pump is mounted in all
models. The indoor unit is concealed in the ceiling making it the ideal
choice for homes and commercial premises.
Quiet, Lightweight and Compact
RCN-KIT3-E
RCH-E3
(Option)
operational data
Model FDU71VNV FDU100VNV FDU125VNV FDU140VNV
Rated Capacity Cool/Heat kW 7.1/8.0 10.0/11.2 12.5/14.0 14.0/16.0
Power Input Cool/Heat kW/h 2.08/2.21 2.88/2.99 4.04/3.79 4.95/4.43
EER/COP Cool/Heat 3.41/3.62 3.47/3.75 3.09/3.69 2.83/3.61
Current Cool/Heat (MAX) Amp 5 (17) 5 (25) 5 (27) 5 (28)
Sound Pressure Level Hi/Lo Fan dB(A) 41/37 42/37 43/38
Airflow Cool Hi/Lo Fan l/s 417/333 566/450 700/558
Static Pressure Pa standard 50 MAX 130
indoor
Dimensions (hxwxd) mm 297x850x650 350x1370x650
Dimensions (hxw) Return & Supply Air mm 244x848 297x1368
Weight kg 40 63
Remote Wired RC-E3, RCH-E3 Wireless RCN-KIT3-E
outdoor
Power Source 1 Phase 220-240V 50Hz
Dimensions (hxwxd) mm 750x880x(88)x340 845x970x370
Weight kg 60 74
Sound Pressure Level dB(A) 48 49 50 51
Sound Power Level (AS/NZS1217.4) dB(A) 62 63 64 65
Compressor Rotary
Refrigerant R410A kg 2.95 3.8
Refrigerant Piping mm ø 9.52/15.88