Specifications
SC-WGWNA-A, SC-WGWNA-B Configuration Manual
Document No. ISTZ10006 March 1, 2010
6
6.1.1 SL System Number
The two (2) SL system numbers (SL Sys No.) for the WEB Gateway are written as S1 and S2.
6.1.2 SL Address
The SL Address of an indoor unit is written as U00∼U63.
SL system number and SL Address are shown in ascending order. For Prev. SL, use U00∼U47.
6.1.3 Accounting Type (SC-WGWNA-B only)
Choose from the following the accounting method for the indoor unit.
Type Accounting Method
MULTI1 Accounting according to the amount of refrigerant flow.
Applicable to KX and LX Series
MULTI2 Accounting according to the thermo ON/OFF.
Applicable to KX and LX Series
RUN/STOP Accounting according to the unit operating time.
Applicable to Multi-indoor unit PAC,Single PAC and PAC for
equipments (with I/F).
6.1.4 Capacity (SC-WGWNA-B only)
Choose the nominal capacity (Cooling capacity) of the indoor unit.
6.1.5 Air-con Cell Number
The WEB Gateway performs monitoring and control by the cell number.
The cell numbers C00∼C95 are assigned to the indoor units specified by the SL system
number and SL Address. Attach a cell number to the indoor unit connected to the SUPERLINK.
It is not necessary to attach a cell number to indoor units that are not connected.
Cell number C00∼C95 can be freely assigned to the indoor units. Assign cell numbers to the
desired display order in the monitoring screen.
Moreover, a cell number can set up the indoor unit remote control group. When two or more
indoor units are specified as a remote control group, attach the same cell number to these indoor
units to define the group. There is no restriction on the number of the indoor units that form a
group. In case of groups, only the indoor unit having the smallest SL system number or SL
address (SL system number being the priority) will be assigned the “Air-con Cell Name” and
“Description” explained in the following clause.
6.1.6 Air-con Cell Name
Assign an understandable name to a particular cell number. The length of the character string
can be up to 16 characters.
6.1.7 Description
A description more detailed than the cell name can be assigned to a cell number. The length of
the character string can be up to 64 characters. Leave it blank in case recording a detailed
description is not necessary.