Specifications

SC-WGWNA-A, SC-WGWNA-B Configuration Manual
Document No. ISTZ10006 March 1, 2010
4
z Connections
Connect with the used network. When the PC is connected to a WEB Gateway in a Local
Area Network (LAN), disable the use of a proxy server.
z Advanced
It is recommended to use the default IE settings for each item ofAdvanced .
4 INITIAL SETTING OF WEB GATEWAY
4.1 Initial Setting of WEB Gateway Ethernet
4.1.1 Initial setting of the IP Address
As for the WEB Gateway, the IP address and the subnet mask, the factory settings are as
follows.
IP Address 192.168.0.110
Subnet mask 255.255.255.0
4.2 How to change the IP Address of the WEB Gateway
Log in to the WEB Gateway using “Administrator User” then from Configuration Menu,
open theCommunication/Buzzer Configurationscreen. On this screen, the IP Address and
Subnet mask are specified, and only when required, the Default Gateway is specified.
Information entered into each field should be in "XXX.XXX.XXX.XXX" format.
Attention:
IP address 0.*.*.*, 127.*.*.*, 224.*.*.* to 255.*.*.*
can't be used due to reservations.
Don't input "0" at the front of each octet.
Ex: Correct:192.168.1.110 Incorrect:192.168.001
.110
Don't input more than a four-digit number for each octet.
Ex: Correct:192.8.100.110 Incorrect:192.8.0100
.110
Subnet mask must contain only binary bit"1" from left side.
Ex: Correct:255.255.255.0 Incorrect:192
.255.255.0
4.3 SUPERLINK Setting
It is necessary to change from Prev. SL using the SL switch (SUPERLINK SELECTION) on
the right side of the unit. (Switching is possible only when the power is OFF.)
For SL2N and SL3N, change is required for the setup deprived of the right of instruction of
Remocon control Lock/Unlock.
5 PASSWORD FAILURE
5.1 Troubleshooting
5.1.1 Trouble regarding the IP Address
Push the reset SW (located inside of the hole with a diameter of about 2mm) in the center on
the right side of the unit using a clip or wire. Pushing for 10 seconds or more and then
releasing it will result in a reboot and the IP address will return to the initial value. Please
check that the red LED blinks for about 30 seconds at this time.