Specifications
SC-WGWNA-A, SC-WGWNA-B Configuration Manual 
Document No. ISTZ10006 March 1, 2010 
13
7  ABOUT PACinfo_128.csv (WGWconfig_128.csv) FILE 
7.0 How to switch to one SUPERLINK System 
  In case that an outdoor unit of combination systems is used, more than 65 indoor units might 
be connected to one SUPERLINK system. 
    In this case, the WEB Gateway is used in one SUPERLINK system. 
    Access to the following URL from the browser of the PC. 
  URL : http://192.168.0.110/128/
    If the IP Address of the WEB Gateway was changed, enter the IP Address instead. 
    Push “Switch Mode” button, then a screen shown below is displayed and the WEB Gateway will 
reboot automatically. 
    About 3 minutes later, access following URL and set the initial configuration. 
  URL : http://192.168.0.110/en/
    If the IP Address of the WEB Gateway was changed, enter the IP Address instead. 