Specifications

SC-WGWNA-A, SC-WGWNA-B Configuration Manual
Document No. ISTZ10006 March 1, 2010
11
Table A.1 Example of SC-WGWNA-A Cell Configuration and SL Address
SL
Outdoor Unit
Type
Outdoor
Unit
Address
Indoor Unit
Type
Room
Name
Remocon
Group
Indoor
Unit
Address
Air-con
Cell No.
Air-con
Cell Name
FDUM45KXE6 ○ U00
FDUM56KXE6 ↑ U01
FDC155KXEN6 00
FDUM56KXE6
Room 01
U02
C00 Room 01
FDC100VN - FDT100V Room 02 U03 * C01 Room 02
FDC125VN - FDT125V Room 03 U04 * C02 Room 03
FDUM56KXE6 Room 04 U05 C03 Room 04
FDC112KXEN6 03
FDUM56KXE6 Room 05 U06 C04 Room 05
FDT71V ○
S1
FDC140VN -
FDT71V
Room 06
U07 * C05 Room 06
FDT36KXE6 ○ U05
FDT36KXE6 ↑ U06
FDT45KXE6 ↑ U07
FDC155KXES6 05
FDT45KXE6
Room 07
U08
C10 Room 07
FDC112KXES6 06 FDT112KXE6 Room 08 U10 C11 Room 08
FDTW28KXE6 ○ U11
FDTW28KXE6
Room 09
U12
C12 Room 09
FDTS45KXE6 ○ U13
S2
FDC140KXES6 07
FDTS45KXE6
Room 10
U14
C13 Room 10
Note: Although Table A.1 is an example of an imaginary building, it corresponds with Fig. 6.3.1,
Fig. 6.4.1, and Fig. A.1.
Note: indicates that indoor unit is part of a remote control group. It is necessary to assign a
SL Address U00U01・・・ to each indoor unit even if it is a part of a group.
Note: * indicates the SL Address of the SUPERLINK adapter SC-ADN (SC-AD, SC-AD-L). For
single PAC, it is necessary to connect with a remote control line to the SUPERLINK of
SC-WGWNA-A through adapter SC-ADN. The second unit for Room 05 is the wireless twin
unit for single PAC.
Note: A cell number is the monitoring and control unit of SC-WGWNA-A. The same monitoring
and control applies to indoor units in a group (i.e., having the same cell number).
Note: Although the model name of the indoor and outdoor unit is unnecessary, it is recommended
to fill them in as a reference for distinguishing units from each other.