Specifications

74
Permissible lengths of piping
From outdoor unit to first branch or to central flow divide controller (if first branch does not exist): Max. 70m [real length]
From first branch to each indoor unit: Max. 30m (each indoor unit) [real length]
From central flow divide controller to central flow divide controller: within 15m [height]
First branch
50m
Max. 30m
Max. 15m
Max. 30m
Max. 70m
(Outdoor unit is lower : 40m)
Individual flow divide
controller
(Highest indoor unit)
(Lowest indoor unit)
Mixed central/individual flow divide system
Outdoor unit
Central flow divide controller
Indoor unit
Permissible lengths of piping
From outdoor unit to first branch or to central flow divide controller (if first branch does not exist): Max. 70m [real length]
From first branch to each indoor unit: Max. 30m (each indoor unit) [real length]
From central flow divide controller to central flow divide controller: within 15m [height]
Central flow divide system
Outdoor unit
Indoor unit
Max. 70m
50m
Max. 30m
Central flow divide controller
Central flow di-
vide controller
(Highest indoor unit)
First branch
Max. 30m
(Outdoor unit below: 40m)
Max. 15m
(Lowest indoor unit)
Max. 15m