Specifications

70
(3) Operation chart
Since the Multi KXR series air conditioner units are free multitype to which the indoor units of different capacity and different
model can be combined, the operation characteristics of all combinations are very complicated, therefore only the individual
operation characteristics of indoor and outdoor units are shown. For the combined operation characteristics, calculate them with
the method shown in the next page.
(a) Operating characteristic of outdoor unit
Note (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 “UNITARY AIR-CONDITIONERS”
(b) Operating characteristic of indoor unit
Notes (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 “UNITARY AIR-CONDITIONERS”
(2) The values shown in the above table are common to both cooling and heating operations.
Cooling power consumption
Heating power consumption
Cooling running current
Heating running current
Inrush current (MAX.)
Cooling power factor
Heating power factor
(415 V)
Item
Models
10.2
8.4
15.8
12.8
48
90
91
13.4
11.4
20.0
17.6
70
93
90
FDCP224HKXRE2A FDCP280HKXRE2A
kW
A
A
%
Cooling power consumption
Heating power consumption
Cooling running current
Heating running current
Inrush current (MAX.)
Cooling power factor
Heating power factor
(380 V)
Item
Models
10.2
8.4
17.1
13.7
48
91
93
13.4
11.4
22.0
19.3
70
93
90
FDCP224HKXRE2V FDCP280HKXRE2V
kW
A
A
%
Item
Models FDT Series
FDT Series
(220 V/240 V)
Power consumption (kW)
Running consumption (A)
0.09/0.10
0.40/0.44
0.10/0.12
0.45/0.49
0.10/0.12
0.47/0.50
0.11/0.13
0.50/0.55
0.17/0.20
0.75/0.81
0.21/0.24
0.93/1.02
28 36 45 56 71 90 112 140
Item
Models FDTW Series
FDTW Series
(220 V/240 V)
Power consumption (kW)
Running consumption (A)
0.09/0.10
0.41/0.42
0.10/0.11
0.40/0.44
0.13/0.16
0.60/0.65
0.20/0.24
0.90/0.98
0.23/0.27
1.03/1.13
28 45 56 71 90 112 140
Item
Models FDTS SeriesFDTQ Series(Duct panel)
FDTQ, FDTS Series
Power consumption (kW)
Running current (A)
0.050/0.055
0.23/0.24
22 28 36
FDTQ Series(Direct blow panel)
0.045/0.050
0.21/0.22
22 28 36
0.10/0.11
0.43/0.46
45
(220 V/240 V)
0.12/0.15
0.58/0.63
71