Specifications

274
Defective indoor unit PCB Replace.
NO
YES
YES
(1)
Defective SVH (high
pressure gas side solenoid
valve) Replace.
NO
YES
Defective relay (XH) Replace.
Defective relay Replace.
Is heat
outputted?
NO
Are solenoid
valve control relays
(XH1~6)
OK?
Is AC 220/240V
applied at flow divide
controller connector
CnB?
Heating operation does not start
4)
Note (1) This is applicable only when a central flow
divide controller is used.