Specifications

225
less than 101
Discharge gas piping
Intake gas piping
Liquid piping
Discharge gas piping
Intake gas piping
Liquid piping
DIS-IKXR3-E (Horizontal branch piping set for 3 pipes)
DIS-IKXR2-E (Branch piping set for 2 pipes)
φ
12.7
φ
19.05
φ
15.88
101 to less than 180
180 to less than 364
FDCP224HKXRE2A (V) FDCP280HKXRE2A (V)
φ
19.05
φ
19.05
φ
9.52
φ
12.7
φ
19.05
φ
15.88
φ
9.52
φ
12.7
φ
28.58
φ
12.7
φ
12.7
φ
25.4
φ
25.4
φ
25.4
Outdoor unit
Central flow divide controller
Indoor unit side
Discharge gas piping
Intake gas piping Liquid piping
Outdoor unit side
HPFD02R-E (for 2 units) , HPFD04R-E (for 4 units), HPFD06R-E (for 6 units)
Branch piping set
Main piping
Item
Medel
Item
Classification
φ
12.7
φ
19.05
φ
15.88
φ
19.05
φ
19.05
φ
9.52
φ
12.7
φ
12.7
φ
12.7
φ
28.58
φ
28.58
φ
25.4
φ
15.88
φ
19.05
φ
9.52
φ
15.88
φ
19.05
φ
9.52
*
*
*
For 6 branches For 4 branches For 2 branches
Total indoor unit
down-flow ca-
pacity after the
second branch.
Pipe size for central flow divide controller
Part No : HPFD02R-E, HPFD04R-E, HPFD06R-E
Notes (1) Confirm that the flare connectors of the refrigerant pipe connection port on the central flow divide controller is surely closed where indoor unit is not
connected.
(2) Connect the indoor unit to the pipe connection port in sequence from the front right side (*mark in the illustration below) of the central flow divide
controller. (Do not leave the right side port unconnected.)
Ensure to connect from the right side even if the number of indoor units to be connected is less than the number of branches.
Outdoor unit
Main piping
Individual flow divide controller
Branch piping set
Discharge gas piping
FDCP224HKXRE2A (V)
Item
Medel
Intake gas piping
Liquid piping
Discharge gas piping
FDCP280HKXRE2A (V)
Intake gas piping
Liquid piping
less than 56
56 to less than 101
101 to less than 180
180 to less than 364
Indoor unit side
Outdoor unit side
HPFD01R-E
DIS-1KXR3-E, DIS-V1KXR3-E, DIS-1KXR2-E
φ
19.05
φ
19.05
φ
12.7
φ
12.7
φ
15.88
φ
19.05
φ
15.88
φ
15.88
φ
25.4
φ
25.4
φ
15.88
φ
15.88
φ
19.05
φ
25.4
φ
19.05
φ
15.88
φ
12.7
φ
12.7
φ
9.52
φ
6.35
φ
9.52
φ
9.52
φ
12.7
φ
12.7
φ
19.05
φ
19.05
φ
12.7
φ
12.7
φ
15.88
φ
15.88
φ
15.88
φ
19.05
φ
28.58
φ
28.58
φ
15.88
φ
15.88
φ
19.05
φ
19.05
φ
15.88
φ
25.4
φ
12.7
φ
12.7
φ
9.52
φ
6.35
φ
9.52
φ
9.52
φ
12.7
φ
12.7
Individual
flow divide
controller
Total indoor unit
down-flow ca-
pacity after the
second branch.
(2) Refrigerant piping size selection
(a) Central flow divide system
(b) Individual flow divide system