Specifications
212
[Conditions]
(1) Fan speed: Hi
(2) Location: Free space without obstacles
(3) Distance of reach indicates the horizontal distance after the wind touched down the floor.
(4) Air velocity at the throw: 0.5 (m/sec.)
2) Where there is no obstacle around the Air inlet port or Air outlet port.
3) Where a sufficient space can be reserved for the service of air filter and the attachment/removal of panels.
4) Places exposed to oil splashes or steam (e.g. kitchens and machine plants).
Installation and use at such places will incur deteriorations in the performance or corrosion with the heat exchanger or
damage in molded synthetic resin parts.
5) Where pipes and wires can be arranged conveniently.
6) On the solid floor
7) Where the unit is not exposed directly to sun light.
8)
Places where corrosive gas (such as sulfurous acid gas) or inflammable gas ( thinner, gasoline, etc.) is generated or remains.
Installation and use at such place will cause corrosion in the heat exchanger and damage in molded synthtic resin parts.
9) Where a complete draining can be assured.
10
)Where a sufficient space can be reserved for service.
Floor standing installation
• Floor fixation • Wall fixation
(10) Floor standing exposed type (FDFL)
(a) Selection of installation location
1) A place where good air circulation and delivery can be obtained.
● Cold air throw
(b) Bolt positions
1) Bolt positions for metal settings used for floor fixation.
• Metal fitting used for floor fixation (accessories).
Unit : mm
2) Bolt positions for wall fixation
Models
Air throw 4
All models
Unit : m
600 or more
150 or more
150 or more
600 or more
1000 or more
Floor
Front side
10 30 Slotted holes
M8
98
32
Rear side
806(1091)
195 195
1196(1481)
View from the floor
1196(1481)
786(1071)
Level adjusting screw
4 12 24
M10
Slotted holes for
wall mounting
470
250220
205 205
Unit : mm
Unit : mm
Note (1) Value in ( ) indicates 71 type.