Specifications
209
Min.
210 mm
Set this face
at level
Nuts,screws
Mounting plate
Secure as tightly as
a wight of 90 kgs
can be supported.
(9) Wall mounted type (FDK)
(a) Selection of installation location
1) Select the best position and direction depending on the shape of room and height of ceiling to ensure that the cooled or
warmed air will be circulated sufficiently.
[Conditions]
a) Fan speed: Hi
b) Location: Free space without obstacles
c) Distance of reach indicates the horizontal distance after the wind touched down the floor.
d) Air yelocity at the throw:0.5 (m/sec.)
2) Where there is no obstacle around the air inlet port or air outlet port.
3) Where a sufficient space can be reserved for the service of air filter and the attachment/removal of panels.
4) Places exposed to oil splashes or steam (e.g. kitchens and machine plants ).
Installation and use at such place will incur deteriorations in the performance or corrosion with the heat exchanger or
damage in molded synthetic resin parts.
5) Where pipes and wires can be arranged conveniently.
6) On the solid floor
7) Where the unit is not exposed directly to sun light.
8)
Place where corrosive gas ( such as sulfurous acid gas ) or inflammable gas ( thinner, gasoline, etc.) is generated or remains.
Installation and use at such places will cause corrosion in the heat exchanger and damage in molded synthetic resin parts.
9) Where a complete draining can be assured.
10
)Where a sufficient space can be reserved for service.
(b) Method to install the mounting plate
1) Indoor unit weighs about 20 kgs. Be sure to check closely the installation place and, if any risk is expected, provide a
sufficient reinforcement with plates or beams. Indoor unit cannot be secured directly on the wall, etc.
Attached mounting plate must be used.
2) When installing a mounting plate on the wall, adjust it at level precisely and fix securely. Use the marketed anchor bolts
(M6) when the wall is made of concrete.
Models
● Cold air throw
Item
FDK22
5.5 78
FDK36, 45
65
FDK28 FDK56, 71
Air throw
Unit : m
200 mm
or more
150 mm
or more
200 mm
or more
Wooden wall
Concrete wall
(Use marketed anchors (M6)
Example of nut anchor Example of bolt anchor
Wood
screw
Mounting
plate
Bolt
Mounting
plate
Nut
Mounting
plate
10 mm
or over