Specifications
208
b) Installation space dimensions
(Plug in dimensions)
c) Mount the unit using suspension bolts
d) Securely tighten the nuts and fix the indoor unit place.
e) Attach the side panels and fit in ceilling board in the space around the unit and the work is finished.
4) Gradient for drainage
Mounting with proper gradient for drainage is needed as shown below.
● In right and left directions ● Front and rear directions
Note (1) In case of left-hand side drainage, the gradient will be to
the opposite side.
Caution ● In case of gradient is contrary, water may leak out.
● Indoor side of drain pipe must be thermally insulated.
Unit upper
side
Ceiling board
(FDE36,45,56,71)
(FDE112,140)
80
24
10
10
10
160
Suspension bolts
Flat washer (accessory parts)
Hexagonal nuts (accessory parts)
Fit in ceiling boards here
0~3 mm
0~3 mm
Unit: mm