Specifications

749
FDC-HKX
Models FDCP224HKXE2, 280HKXE2
Models FDCJ224HKXE2, 280HKXE2
Wall height H3
Wall height H2
Wall height H4
Wall height H1
suction
Opening for exit gas piping
(φ65)
Power supply connecting
terminal block
Signal line connecting
terminal block
Opening for exit liquid piping
(φ50)
Opening for exit wiring
(φ35)
Opening for
exit wiring
(φ50)
Downward outlet hole for
piping and wiring
Anchor bolts
(M10×4pcs.)
Hole for drain
(8-φ20)
Hole for drain
(φ50)
Opening for
exit piping
(φ88)
Opening for exit gas piping
(φ39)
Opening for
exit liquid
piping
(φ25)
Connect of
liquid piping
φ12.7(1/2")
Opening for
exit wiring
(φ50)
L2
L1
L4
L3
105
170
1450
600
50
1350
20
283.5
567
702
283.5
135
767
850
15
640
15
250
40
250
157
81
69
395
532
123
240
175
50
110
88
123
292
105
80
170
157
102
29
22
H4
H3
H2
H1
700 or less
1000 or less
Open
00
0
Not limited
Not limited
Not limited
Not limited
Not limited
Not limited
Not limited
L1
L2
L3
L4
Open
Open
0
300 300
500
500
300
(Unit: mm)
Dimensions
Installation
example
Notes (1) Make sure to secure the unit with anchor bolts.
(2) When the strong wind blows, place the unit so that discharge outlet faces
the wind direction with right angle.
(3) Make sure to allow the space of 1 m or more above the unit.
(4) Connect the refrigerant piping (both gas side and liquid side) at local site.
(5) If the wall height H1, H3 of installation example III exceeds the limited value,
make sure the value of L1, L3 are to be as follows.
L1 = H1 - 500
L3 = 300 + (H3 - 700) / 2, however, if L3 exceeds 600, there is no limit for the
wall height H3.
Connect of gas piping
224type:φ25.4(1")
280type:φ28.58(1 1/8")
Connect of
liquid piping
φ12.7(1/2")
Dimensions of refrigerant piping
connecting mouth(plan)
Rear surface
175
110
70
100
( )
service
spece