Specifications

720
FDC-HKX
Item
Models FDR, FDUM Series
FDR, FDUM Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.11/0.13
0.51/0.56
0.09/0.11
0.41/0.46
0.14/0.16
0.63/0.67
0.15/0.17
0.68/0.71
0.16/0.19
0.73/0.79
0.24/0.28
1.07/1.17
0.28/0.32
1.28/1.32
22 28, 36 45 56 71 90 112 140
Item
Models FDTS Series
FDTS Series
Power input (kW)
Running current (A)
0.07/0.08
0.33/0.36
22 28 36
0.10/0.11
0.43/0.46
45
(220 V/240 V)
0.12/0.15
0.58/0.63
71
Item
Models FDK Series FDFL Series
FDK, FDFL Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.06/0.07
0.31/0.33
0.05/0.06
0.26/0.28
0.08/0.09
0.36/0.39
0.09/0.11
0.41/0.48
0.09/0.10
0.41/0.42
0.09/0.10
0.40/0.41
0.09/0.10
0.40/0.41
2822 36 45 56 71 28 45 71
Item
Models FDE Series
FDE Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.10/0.11
0.43/0.46
0.12/0.15
0.58/0.63
36 45 56 71
0.20/0.24
0.90/0.98
112
0.24/0.29
1.10/1.20
140
Notes (1) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(2) The values shown in the above table are common to both cooling and heating operations.
(c) Calculation of total operation characteristics
Since the operation characteristics of series Multi-KX depend on combination of indoor unit, calculate the total operation characteristics
of the system by using the formulas below according to specifications of each indoor unit or outdoor unit.
1) Total power input
Total power input (kW) = Power input of outdoor unit + (Power input of indoor unit)
2) Total running current
Total running current (A) = Running current of outdoor unit + [ (Running current) × 2/3]
3) Total power factor
Total power factor (%) = [Total power input (W) /
3 × Total running current (A) × Power source] × 100
Total operation characteristics = Operation characteristic value of outdoor unit + Operation characteristic value of indoor unit
[Example]
(Conditions) Operation Voltage ········Indoor unit: 220 V, 50 Hz
Outdoor unit: 380 V, 50 Hz
Operation mode ···········Cooling and Heating
Unit·······························Outdoor unit: FDCJ224HKXE2 × 1 unit
Indoor unit: FDTJ71HKXE2 × 2 units
FDTJ45HKXE2 × 2 units