Specifications

927
OPTION
OPTION
Wire guide
Wire
Pass the wire through
the clearance.
Note (1) Install the wire guide
securely. Otherwise,
the grille may fail to
elevate or even drop
off.
(e) Panel installation
1 Screw two bolts out of four hanging bolts attached to the panel in to less than 5 mm on the air conditioner unit in a diagonal
relation.
(Screw them in provisionally ; one at the drain pipe side and the other at the opposite on the diagonal line.)
2 Remove first the wire guide and the air inlet grille. Hook next the panel on a pair of hanging bolts and fix provisionally.
3 Tighten securely the bolts tightened provisionally and the remaining two hanging bolts.
4 Connect the connector for louver motor (Red, 2P).
5 Connect the grille lifting motor wires (round terminals) together with the crossover wires extending from the outdoor unit at
the primary side (1, 2/N) on the terminal board provided in the indoor unit control box.
6 Connect the communication connector (White, 5P) led out from the control box of panel unit with the connector (CNV) on
the PCB provided in the indoor unit control box.
7 Connect the connector for receiver (Black, 8P) with the connector in the indoor unit control box.
8 Enclose respective connectors and wire within the flange avoiding interference with movements of cable.
Note(1) When connecting connectors, sufficient care must be taken not to entangle them with the grille lifting cable. Make sure to
couple the connectors having the same color and pin number.
12/N
CNV(5P)
1
2/N
CNV(5P)
Insert the wiring
into this space.
5
7
6
3
12
12
43
Green
Red
Drain pipe
Refrigerant
piping
Receiver
Power wire
Panel
control
box
Control
box
White
Box.
LTD
PWB
(f) Installing the air inlet grille
1) Determine the direction of air inlet grille.
2) Slide the wire guide from the outside to the inside at two mounting positions on each of opposing sides of air inlet grille till
it is set in position.
At the installation, take care of the direction to pass the wire through the clearance at the mounting position and mount it
securely.