Specifications

906
OPTION
OPTION
Name Center Console SLA-1-E Center Console SLA-2A-E
Type SC-SLA1-E SC-SLA2A-E
Power source 1 phase AC220V or AC240V 50Hz
Main unit 120 × 120 × 15 120 × 180 × 16
Power source kit 100 × 85 × 50
Product weight (kg) 0.64 0.96
Power consumption (VA) 5 6
Displays LED (inspections)
Operation switches Function keys: 18 Function keys: 31
Number of package connection units
Max. 16 units Max. 48 units
External operation input 1 point No voltage a contact
Emergency stop capability —— 1 point No voltage a contact
Weekly timer input —— SCA-WT-E 1 unit
Alarm output ——
Operation output —— 1 point DC5V 30 mA (Max.)
Error output —— 1 point DC5V 30 mA (Max.)
Ambient temperature and humidity 0 to 40°C, 75% or less (no condensation)
Power source 0.75 mm
2
(direct attachment)
Signal wires 0.75 mm
2
to 2 mm
2
, length max. 1,000 m (terminal block connection)
Power wires The wiring from the main unit to the power source kit is included.
Individual unit start/stop ON/OFF for each unit
Group start/stop —— ON/OFF for each group
Simultaneous start/stop ON/OFF for all units at the same time (Start in order at 1 sec. interval).
Inspection reset —— Resets the inspection sign for each unit.
Filter sign ——
Emergency stop ——
When this signal is received all units are stopped.
Power recovery control
Demand operation ——
External
dimensions
(H x W x D) mm
Wiring
specifications
The filter sign can be reset for each individual unit,
group, or all units simultaneously.
Reoperation after recovery
(Settings save)
When this signal is received the thermostat
of the specified unit is turned off.
Liquid crystal display, red LED
(inspections, filter sign)
Stopped state after power outage
(Settings save)
Devices
Installation
environment
Control
Input/Output
19.1 SPECIFICATIONS (SLA-1-E, SLA-2A-E)