Specifications

896
FDC-HKX
Current cut is indicated and the compressor cannot operate
Notes (1) when a short-circuit or ground-fault occurs in the
compressor motor, the current cut function is also
activated.
If the insulation resistance is 10M or more, it is
normal.
The insulation resistance may considerably drop
depending on the refrigerant volume in the
compressor, but this is not faulty.
(2) 1-2 seconds after a start :
FDC140 type : Approx. 14A
FDC224 type : Approx. 32A
FDC280 type : Approx. 37A
Model
35Hz
160 ~ 180
40Hz
180 ~ 210
65Hz
290 ~ 320
75Hz
330 ~ 360
95Hz
380 ~ 410
Frequency
Unit : V (AC)Inverter output voltage
All models
(outdoor unit)
Disconnect the compressor wiring
The compressor can operate
Is the current
cut function activated?
YES
YES
YES
YES
Defective inverter
Defective inverter
Is the insullation
resistance of the compressor
(1)
proper?
NO
NO
NO
NO
Is the output
voltage of the inverter
normal?
(Refer to 903 page)
(Refer to 903 page)
When the compressor wiring is
performed, the unit can operate.
Isn't the stating
current
(2)
excessive?
Defective compressor
Defective compressor
Defective inverter