Specifications
879
FDC-HKX
(a) Diagnosis by the power supply reset
When any error occurs, reset the power supply as described below to see if it is the result of accidental noise, etc.
Check at the indoor unit side.
Errors due to external noise, etc.
Error code may be displayed or the error may not be displayed normally even if the controller is normal because of external noise
source
(1)
or joined or parallel arrangement of power cables and singal wires. It is because the wire of remote controller, wired
remote controller signal wires for multiple units or the network signal wires may be influenced by external noises whitch are judged
as signals by the microcomputer whitch reacts mistakenly.
When there is any noise source, it is necessary to the shield wire for the remote controller and signal wires.
Note (1) High frequency medical machine, rectifier motor application device, thyristor, broadcast transmission tower, power
transmission line, power line of electric train, automatic door motor, elevator (voltage drop), wireless telephone, high
voltage power distribution line, computer, personal computer and their cables.
These do not necessarily always cause problems but they can be a source of electrical noise.
Are the return air
temperature and Center/
Remote displayed on the
remote controller?
Is any errror
code display
?
Does the error
code disappear?
Does start operation
with display of cool-
ing degree: Hi, ther-
mostat: 23˚C?
Does the error repeat
Check the error
code displayed
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
Error
ON/OFF
switch OFF
ON/OFF
switch OFF
Microcomputer
out of control
(Power supply reset)
Turn off the wiring breaker (power
supply) and back on again 1min.later.
Power supply line error See page 883
Check of error code
Power switch OFF
Power supply line error
Cause is acccidental (noise,
etc.) and the unit is normal.