866
FDC-HKX
<III><II><I> <IV>
Power source
<V> <VI> <VII> <VIII>
Outdoor unit
3phase 380/415V50Hz
Power source
1phase 220/240V50Hz
Earth leakage
breaker
Earth leakage
breaker
Circuit Breaker
Earth
Signal wire (Between outdoor and indoor units)
Signal wire (Between indoor units)
Circuit breaker
Indoor
unit
remote
controller wire
Remote controller
Remote controller wire
A B
X Y Z
X Y Z
A B
L
N
X Y Z
X Y Z
A B
L
N
Signal wire (Between outdoor and indoor units)
Signal wire (Between indoor units)
Remote
controller
Remote
controller
<II><I>
Indoor unit
Indoor unit side
power supply wire
Outdoor unit
• Do not connect high voltage wire 380/415V to signal wires, as these wires are DC 5V. Signal wires should be connected so that the
terminal Nos. conform with each other for between outdoor and between indoor units. However, they will work properly if different
polarities are connected. (Connect (A) and (A), (B) and (B).)
Outdoor/Indoor units connection procedures
Models
FDC224, 280type
Signal wire