Specifications

864
FDC-HKX
18.5.5 Electric wiring
(1) Power supply wiring
(a) Outdoor unit power supply
Use separate power supplies for the outdoor and indoor unit respectively. (Standard specification)
The table below shows the power specification for outdoor unit only.
Notes (1) The above table shows the power specification of outdoor unit when separate powers are use for outdoor unit and indoor units.
(2) The wire thickness and distance indicated above are for when voltage drop is 2%.
(b) Indoor unit power supply
2.02 wires 54/54
2.02 wires 37/37
Item
Power
source
Power
supply
wire size
(mm
2
)
Wire
length
(m)
Circuit breaker
Switch
capacity
(A)
Reted
current
(A)
Earth
leakage
breaker
(A)
Grounding
wire size
(mm
2
)
1 phase
220/240V
50Hz
Applicable
outdoor unit
FDC140 type
FDC224 type
FDC280 type
15/15 15/15 15/15 2.0
Notes (1) The wire length covers values when necessary indoor units are connected in series with the unit power supply wire as shown below. Also, the wire
thickness and distance indicated above are for when voltage drop is 2%.
(2) These values are based on the conditions that indoor units are connected so that the total capacity becomes the mximum against each outdoor unit.
Earth leakage
breaker
Circuit breaker
Power supply wire
r4
r2
r2
r1
3.5/3.5 38/45 25/25 30/30
5.5/5.5 46/54 30/30 40/40
8.0/8.0 47/58 50/50 60/60
Item
Model
FDC140 type
FDC224 type
FDC280 type
Power
source
Power
supply
wire size
(mm
2
)
Wire
length
(m)
Circuit breaker
Switch
capacity
(A)
Reted
current
(A)
Earth
leakage
breaker
(A)
Grounding
wire size
(mm
2
)
3 phase
380/415V
50Hz
2.0
2.0
3.5
30A 30mA
0.1 sec. or less
40A 100mA
0.1 sec. or less
60A 100mA
0.1 sec. or less