Specifications
963
FDC-HKXR
(3) Operation chart
Since the Multi KXR series air conditioner units are free multitype to which the indoor units of different capacity and different
model can be combined, the operation characteristics of all combinations are very complicated, therefore only the individual
operation characteristics of indoor and outdoor units are shown. For the combined operation characteristics, calculate them with the
method shown in the next page.
(a) Operating characteristic of outdoor unit
Cooling input
Heating input
Cooling running current
Heating running current
Inrush current (MAX.)
Cooling power factor
Heating power factor
10.2/10.2
8.4/8.4
15.9/14.6
13.3/12.2
5
97/97
96/96
12.4/12.4
9.2/9.2
21.8/20.0
15.6/14.3
5
86/86
90/90
(380 V/415 V)
Item
Models
FDCP2001HKXRE2 FDCP2501HKXRE2
kW
A
A
%
Note (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR-CONDITIONERS”
(b) Operating characteristic of indoor unit
Item
Models FDT Series
FDT Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.09/0.10
0.40/0.44
0.10/0.12
0.45/0.49
0.10/0.12
0.47/0.50
0.11/0.13
0.50/0.55
0.17/0.20
0.75/0.81
0.21/0.24
0.93/1.02
28 36 45 56 71 90 112 140
Item
Models FDTW Series
FDTW Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.09/0.10
0.43/0.44
0.10/0.11
0.48/0.50
0.12/0.13
0.57/0.59
0.18/0.20
0.86/0.89
0.20/0.24
0.90/0.98
28 45 56 71 90 112 140
Notes (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR-CONDITIONERS”
(2) The values shown in the above table are common to both cooling and heating operations.
Item
Models FDR, FDUM Series
FDR, FDUM Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.11/0.13
0.51/0.56
0.09/0.11
0.41/0.46
0.14/0.16
0.63/0.67
0.15/0.17
0.68/0.71
0.16/0.19
0.73/0.79
0.24/0.28
1.07/1.17
0.28/0.32
1.28/1.32
22 28, 36 45 56 71 90 112 140
Item
Models FDTS Series
FDTS Series
Power input (kW)
Running current (A)
0.07/0.08
0.33/0.36
22 28 36
0.10/0.11
0.43/0.46
45
(220 V/240 V)
0.12/0.15
0.58/0.63
71
Item
Models FDE Series
FDE Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.10/0.11
0.43/0.46
0.12/0.15
0.58/0.63
36 45 56 71
0.20/0.24
0.90/0.98
112
0.24/0.29
1.10/1.20
140