Specifications

FDC-HKXR
951
Models FDRJ112HKXE2, 140HKXE2
Item
Nominal cooling capacity*
1
Panel model (Option)
Air inlet panel Silent panel
R-PNLS-46W-E R-PNLC-46W-E R-PNLS-46W-E R-PNLC-46W-E
Canvas panel Canvas panelSilent panel
W
W
W
CMM
kg
Pa(mmAq) Standard:50(5.0), Hi speed:80(8.0)
Unit:50
Panel:9
Unit:50
Panel:7
Unit:52
Panel:9
Unit:52
Panel:7
Hi: 28 Me: 25 Lo: 22 Hi: 34 Me: 31 Lo: 27
45 1,
dB(A)
mm
Unit:406 1370 635
Panel:10 1660 750
Nominal heating capacity*
2
Power source
Net weight
Refrigerant control
Starting method
Fresh air intake
Air filter Q'ty
Shock & vibration absorber
Insulation (noise & heat)
Room temperature control
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Outdoor units to be combined
Motor
Air flow(Standard)
Exterior dimensions
Height Width Depth
Refrigerant equipment
Heat exchanger
Internal thermostat for fan motor.
Frost protection thermostat
Air handling equipment
Fan type & Q'ty
Available static pressure
( at Me)
Operation control
Operation switch
Installation data
Refrigerant piping size
Noise level
Models
FDRJ112HKXE2
(4)
11200
FDRJ140HKXE2
(4)
14000
12500
1 Phase 220/240V 50Hz
Electronic Expansion Valve +Capillary tube
Line starting
Side or back
Long life filter 2(Washable)
Rubber sleeve(for fan motor)
Polyurethane foam
Flare piping
Connectable with VP25
Necessary (both Liquid & Gas lines)
Mounting kit
Silent panel, Canvas panel, Canvas duct
FDCP2001HKXRE2, 2501HKXRE2
Thermostat by electronics
mm(in)
Safety equipment
Remote control switch (Optional:RCD-HKX-E2)
Hi: 45 Me: 42 Lo: 38 Hi: 46 Me: 43 Lo: 39 Hi: 46 Me: 43 Lo: 39 Hi: 47 Me: 44 Lo: 40
Louver fins & inner grooved tubing
16000
Unit:(350+α) 1370 635
Panel:10 1484 585
Unit:(350+α) 1370 635
Panel:10 1484 585
Unit:406 1370 635
Panel:10 1660 750
90 1 50 1, 100 1
(1)The data are measured at the following conditions.Notes
(2)This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3)Canvas panel is used in combination with following canvas duct
Canvas duct: HA01484
(4)The number "2",following the type of each model,represents"CE-marked model"especially for European Union, and for European nations which
require CE marking.
(5)Add the canvas duct lenght to the unit height for the canvas type.
Item
Indoor air temperature Outdoor air temperature
Standards
ISO-T1,JIS B8616
Operation
DB WB DB WB
Cooling*
1
27
Heating*
2
20
19 35
7
24
6
Centrifugal fan 3