Specifications

1076
FDC-HKXR
YES
YES
YES
NO
NO
NO
Power supply
checked between R~N or
terminal block
Is there
AC 17V checked
between CNA
2
(blue) ~ (blue)
and AC 8V between (red)
~ (red) of outdoor unit
transfomer?
Power supply
reset
Defective outdoor
unit PCB
Unit is normal
Is it
Normalized?
Blown fuse (3.15A) Replacement
Defective transformer
Replcement
Broken power supply wire in
the unit Repair
Is the pairing of
Indoor/outdoor units OK?
Change of unit num-
ber setting
NO
(1)
YES
Is the connection
of network signal
wires good?
NO
Power not supplied.
Power supply wiring
errorRepair.
Note (1) NO outdoor unit corre-
sponding to the indoor
unit.
Repair the door con-
nection, broken wire of
network signal wires.
Indoor unit
Red LED
Green LED
2 time flash
Keeps flashing
Outdoor unit
Red LED
Green LED
Stays OFF
Stays OFF
Outdoor unit
Red LED
Green LED
Stays OFF
Keeps flashing
1
Error display:
[Error on the outdoor unit signal line]
(Detected during operation only)
(iii) Check procedure depending on indication lamps (For the outdoor unit)