FDC-HKXR
E11 Keeps flashing Stays OFF Keeps flashing Stays OFF
Remote controller addresses have been set while more than one units of remote
controller are connected.
2) Check Indicator Table
Whether a failure exists or not on the indoor unit and outdoor unit can be known by the contents of remote controller error code, indoor / outdoor unit green LED (power pilot lamp and
microcomputer normality pilot lamp) or red LED (check pilot lamp).
No-indication
E1
E2
E3
E5
E6
E7
E9
E10
Indoor unit LED
Green
Keeps flashing
Lights continuously
Stays OFF
Keeps flashing
Keeps flashing
Stay OFF or Lights
continuously
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Red
Stays OFF
Stays OFF
Stays OFF
3 time flash
Stays OFF
32-sec time flash
3 time flash
1 time flash
Stays OFF
2 time flash
2 time flash
2 time flash
2 time flash
1 time flash
1 time flash
1 time flash
Stays OFF
Outdoor unit LED
Green
Keeps flashing
Lights continuously
Stays OFF
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Stays OFF
Keeps flashing
Keeps flashing
Stay OFF or Lights
continuously
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
Red
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stay OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
6 time flash
32-sec time flash
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Cause
Normal
Indoor unit PCB fault, CPU runaway
Power OFF, L3 phase wiring is open, power source failure
Remote controller wires X and Y are reversely connected.* For wire breaking at
power ON, the LED is OFF. Remote controller wire is open. (X wire breaking: A
beep is produced and no indication is made. Z wire breaking: No beep and no
indication) The remote controller wires Y and Z are reversely connected. (32-sec
time flash)
Indoor unit PCB fault
The remote controller wires are connected to A and B on the terminal block.
The indoor/outdoor signal wire are connected in loop form. The indoor unit
microcomputer runs away.
The PAC remote controller is connected to the KX. The remote controller wire Y is
open. The remote controller wires X and Y are reversely connected. (The LED
flash twice a second.) Two remote controllers are provided.* For wire breaking at
power ON,the LED is OFF.
No. duplication at indoor unit addressing. More than 49 indoor unit are connected.
No. duplication at remote controller addressing
Outdoor unit power supply OFF (detected only during operation)
The corresponding outdoor unit address No is not found. (Detected only during
opreation) Indoor/outdoor signal line wire breaking Indoor unit PCB fault.
Indoor/outdoor transmission error. Wire A and B swapping after power ON.
Outdoor unit microcomputer failure
Indoor unit heat exchanger thermistor failure
Indoor unit return air thermistor failure
The float SW operates (with FS only). Drain up kit wiring fault.
When multi-unit control by remote controller is performed, the number of units is
over (more than 17 units). Two remote controllers are provided for one controller
is performed.
Remote
controller
error code
Keeps flashing
Keeps flashing
Keeps flashing
Keeps flashing
1 time flash
Stays OFF
Stays OFF
Stays OFF
Outdoor No,
0 ~ 47
48, 49
Indoor No,
48, 49
0 ~ 47
Remote controller thermistor failure
E12
E28
Address No. combination error or addressing is performed with the following
combinations.