Specifications
1049
FDC-HKXR
3) Face-to-face installation
Dimension Unit: mm
Distance
Item
Diagonal
Up air outlet
L
1
1500 or more
500 or more
L
2
1000 or more
500 or more
Note (1) Make the air outlet the diagonal air outlet (standard) or the up air outlet (option).
4) Side-to-side & face-to-face installation
[Keep a space of more than 10 mm between the unit]
Dimension Unit: mm
Distance
Item
Diagonal
Up air outlet
L
1
1500 or more
800 or more
L
2
1000 or more
800 or more
Note (1) Make the air outlet the diagonal air outlet (standard) or the up air outlet (option).
5) In the case where the unit is exposed to strong wind.
a) Face the unit air outlet at a 90º angle from the direction of the wind.
b) Securing outdoor unit (in the case of exposure to severe weather conditions)
Fix the unit in the following way.
• Use overtuming prevention brackets.
• Rig with wires.
(Use rigging wires that are resistant to corrosion and sufficient in
strength. For example SUS304-W1, wire thick-ness 2.9 mm)