FDC-HKXR 20.
FDC-HKXR CONTENTS 20.1 GENERAL INFORMATION ...................................................................... 937 20.1.1 Specific features ............................................................................... 937 20.1.2 How to read the model name ........................................................... 939 20.1.3 Table of models ................................................................................. 939 20.1.4 Table of indoor units panel (Optional) ................................
FDC-HKXR 20.1 GENERAL INFORMATION 20.1.1 Specific features (1) Fuzzy control (a) Response speed and stability are enhanced. • The system automatically controls changes of return air temperature, set temperature and room temperature according to the fuzzy control. • The system response speed, can keep room temperature constant, and can adjust room temperature to set temperature quickly. Inverter Hz Set temp. Temp. difference Gradient of temp. operation FUZZY operation Temp. (Return air thermistor) E.E.
FDC-HKXR (3) Installation of automatic address setting function • The address setting method are divided into three types according to wiring method: “Automatic Address Setting,” “Remote control Address Setting.” and “Manual Address Setting.” In case of the Automatic Address Setting, no address needs be set as usual. (4) Connectable indoor capacity Capacity from 50% to 130% is possible.
FDC-HKXR 20.1.2 How to read the model name Example: FDC P 2001 H KXR E 2 CE marking model Application power source...See the specifications Multi KXR series Heat pump type Nominal capacity R407C models Model name Indoor unit : FDT, FDTW, FDTS, FDR, FDUM FDE, FDK, FDFL, FDFU Outdoor unit : FDC 20.1.
FDC-HKXR 20.2 SELECTION DATA 20.2.
FDC-HKXR Models FDTJ45HKXE2, 56HKXE2, 71HKXE2 Models FDTJ45HKXE2(3) FDTJ56HKXE2(3) W 4500 5600 7100 W 5000 6300 8000 Item 1 Nominal cooling capacity* Nominal heating capacity*2 Power source FDTJ71HKXE2(3) 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth Net weight Hi: 38 Me: 35 Lo: 34 mm Unit:260 kg Hi: 40 Me: 38 Lo: 36 840 840 Panel:30 950 950 Unit:24 Panel:7 Refrigerant equipment Heat exchanger Louver fine & inner grooved tubing Refrigerant contr
FDC-HKXR Models FDTJ90HKXE2, 112HKXE2, 140HKXE2 Models FDTJ90HKXE2(3) FDTJ112HKXE2(3) W 9000 11200 14000 W 10000 12500 16000 Item 1 Nominal cooling capacity* Nominal heating capacity*2 Power source FDTJ140HKXE2(3) 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth Net weight Hi: 42 Me: 40 Lo: 38 Unit: 260 Panel:30 mm kg 840 950 Hi: 49 Me:46 Lo: 42 840 950 Unit: 320 Panel:30 Unit:24 Panel:7 Hi: 50 Me: 47 Lo: 45 840 950 Unit:28 Panel:7 Refrigerant equipmen
FDC-HKXR (b) 2-way outlet ceiling recessed type (FDTW) Models FDTWJ28HKXE2B, 45HKXE2B, 56HKXE2B Models Item FDTWJ28HKXE2B(3) FDTWJ45HKXE2B(3) FDTWJ56HKXE2B(3) Nominal cooling capacity*1 W 2800 4500 5600 Nominal heating capacity*2 W 3200 5000 6300 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Exterior dimensions Height Width Depth Net weight Hi: 39 Me:36 Lo: 33 mm Unit:280 817 620 kg Panel:8 1055 680 Unit:19 Panel:7 Refrigerant equipment Heat exchanger Louver fins & inner g
FDC-HKXR Models FDTWJ71HKXE2B, 90HKXE2B Models FDTWJ71HKXE2B(3) Item FDTWJ90HKXE2B(3) Nominal cooling capacity*1 W 7100 9000 Nominal heating capacity*2 W 8000 10000 dB(A) Hi: 41 Me: 38 Lo: 35 Power source 1 Phase 220/240V 50Hz Noise level Exterior dimensions Height Width Depth Net weight mm Hi: 41 Me: 39 Lo: 36 Unit:330 1054 kg 620 Panel:8 1300 680 Unit:26 Panel:9 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Va
FDC-HKXR Models FDTWJ112HKXE2B, 140HKXE2B Models FDTWJ112HKXE2B(3) Item FDTWJ140HKXE2B(3) 1 Nominal cooling capacity* W 11200 14000 Nominal heating capacity*2 W 12500 16000 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth Net weight Hi: 44 Me: 41 Lo: 38 mm Hi: 45 Me: 42 Lo: 39 Unit:345 1524 kg 620 Panel:8 1770 Unit:38 Panel:11 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigerant control Electronic Expansio
FDC-HKXR (c) 1-way outlet ceiling recessed type (FDTS) Models FDTSJ22HKXE2B, 28HKXE2B, 36HKXE2B Model Item FDTSJ22HKXE2B(3) FDTSJ28HKXE2B(3) FDTSJ36HKXE2B(3) Nominal cooling capacity*1 W 2200 2800 3600 Nominal heating capacity*2 W 2500 3200 4000 dB(A) Hi: 39 Lo: 38 Power source 1 Phase 220/240V 50Hz Noise level Exterior dimensions Height Width Depth mm Net weight Kg Hi: 40 Me: 39 Lo: 38 Unit:194 1040 650 Panel:10 1290 770 Unit:26 Panel:6 Refrigerant equipment Heat exchanger Lou
FDC-HKXR Models FDTSJ45HKXE2B, 71HKXE2B Model FDTSJ45HKXE2B(3) Item FDTSJ71HKXE2B(3) 1 Nominal cooling capacity* W 4500 7100 Nominal heating capacity*2 W 5000 8000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Exterior dimensions Height Width Depth Net weight Hi: 43 Me: 40 Lo: 38 Unit:194 Panel:10 mm kg 1040 1290 Hi: 44 Me: 40 Lo: 38 Unit:194 Panel:10 650 770 Unit:26 Panel:6 Refrigerant equipment Heat exchanger 1300 1500 650 790 Unit:30 Panel:7 Louver fins & inner grooved t
FDC-HKXR (d) Cassetteria type (FDR) Models FDRJ22HKXE2, 28HKXE2 Models FDRJ22HKXE2(4) Item Air inlet panel Panel model (Option) FDRJ28HKXE2(4) Silent panel Canvas panel Silent panel Canvas panel R-PNLS-26W-E R-PNLC-26W-E R-PNLS-26W-E R-PNLC-26W-E Nominal cooling capacity*1 W 2200 2800 Nominal heating capacity*2 W 2500 3200 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth Net weight mm kg Hi: 41 Me: 39 Lo: 36 Hi: 42 Me: 40 Lo: 37 Hi: 42 Me:
FDC-HKXR Models FDRJ45HKXE2, 56HKXE2 Models FDRJ45HKXE2(4) Item Air inlet panel Panel model (Option) FDRJ56HKXE2(4) Silent panel Canvas panel Silent panel Canvas panel R-PNLS-26W-E R-PNLC-26W-E R-PNLS-26W-E R-PNLC-26W-E Nominal cooling capacity*1 W 4500 5600 Nominal heating capacity*2 W 5000 6300 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth Net weight mm kg Hi: 43 Me: 40 Lo: 37 Hi: 44 Me: 41 Lo: 38 Hi:43 Me: 40 Lo: 37 Unit:(299+α) 750
FDC-HKXR Models FDRJ71HKXE2, 90HKXE2 Models FDRJ71HKXE2(4) Item Air inlet panel Panel model (Option) FDRJ90HKXE2(4) Silent panel Canvas panel Silent panel Canvas panel R-PNLS-36W-E R-PNLC-36W-E R-PNLS-36W-E R-PNLC-36W-E Nominal cooling capacity*1 W 7100 9000 Nominal heating capacity*2 W 8000 10000 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth Net weight mm kg Hi: 43 Me: 40 Lo: 37 Hi: 44 Me: 41 Lo: 38 Hi: 43 Me: 40 Lo: 37 Hi: 44 Me: 41
FDC-HKXR Models FDRJ112HKXE2, 140HKXE2 Models FDRJ112HKXE2(4) Item Air inlet panel Panel model (Option) FDRJ140HKXE2(4) Silent panel Canvas panel Silent panel Canvas panel R-PNLS-46W-E R-PNLC-46W-E R-PNLS-46W-E R-PNLC-46W-E Nominal cooling capacity*1 W 11200 14000 Nominal heating capacity*2 W 12500 16000 Power source 1 Phase 220/240V 50Hz Noise level Exterior dimensions Height Width Depth Net weight dB(A) Hi: 45 Me: 42 Lo: 38 mm Unit:406 1370 635 Panel:10 1660 750 kg Unit:50 Pane
FDC-HKXR (e) Satellite ducted type (FDUM) Models FDUMJ36HKXE2, 45HKXE2 Models FDUMJ36HKXE2(3) Item FDUMJ45HKXE2(3) Nominal cooling capacity*1 W 3600 4500 Nominal heating capacity*2 W 4000 5000 dB(A) Hi: 34 Me: 32 Lo: 29 Power source 1 Phase 220/240V 50Hz Noise level Exterior dimensions Height Width Depth Net weight Hi: 35 Me: 32 Lo: 29 mm 299 kg 750 635 34 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve +Capill
FDC-HKXR Models FDUMJ56HKXE2, 71HKXE2, 90HKXE2 Models Item FDUMJ56HKXE2(3) FDUMJ71HKXE2(3) FDUMJ90HKXE2(3) 1 Nominal cooling capacity* W 5600 7100 9000 Nominal heating capacity*2 W 6300 8000 10000 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth Net weight mm Hi: 35 Me: 32 Lo: 29 299 750 kg Hi: 35 Me: 32 Lo: 29 635 299 34 Hi: 36 Me: 33 Lo: 30 950 635 40 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigeran
FDC-HKXR Models FDUMJ112HKXE2, 140HKXE2 Models FDUMJ112HKXE2(3) Item FDUMJ140HKXE2(3) Nominal cooling capacity*1 W 11200 14000 Nominal heating capacity*2 W 12500 16000 dB(A) Hi: 38 Me: 35 Lo: 32 Power source 1 Phase 220/240V 50Hz Noise level Exterior dimensions Height Width Depth Net weight Hi: 39 Me: 37 Lo: 34 mm 350 kg 1370 635 57 59 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve +Capillary tube Air handli
FDC-HKXR (f) Ceiling suspension type (FDE) Models FDEJ36HKXE2B, 45HKXE2B Models Item FDEJ36HKXE2B(3) FDEJ45HKXE2B(3) 4500 Nominal cooling capacity*1 W 3600 Nominal heating capacity*2 W 4000 5000 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth Net weight Hi: 43 Me:40 Lo: 38 mm 184 kg 1000 650 22 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve + Capillary tube Air handling
FDC-HKXR Models FDEJ56HKXE2B, 71HKXE2B Models FDEJ56HKXE2B(3) Item FDEJ71HKXE2B(3) 1 Nominal cooling capacity* W 5600 7100 Nominal heating capacity*2 W 6300 8000 dB(A) Hi: 43 Me:40 Lo: 38 Power source 1 Phase 220/240V 50Hz Noise level Exterior dimensions Height Width Depth Net weight mm 184 kg 1000 Hi: 44 Me:40 Lo: 38 650 184 1260 22 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve + Capillary tube Air handl
FDC-HKXR Models FDEJ112HKXE2B, 140HKXE2B Models FDEJ112HKXE2B(3) Item FDEJ140HKXE2B(3) 1 Nominal cooling capacity* W 11200 14000 Nominal heating capacity*2 W 12500 16000 dB(A) Hi: 49 Me:46 Lo: 42 Power source 1 Phase 220/240V 50Hz Noise level Exterior dimensions Height Width Depth Net weight mm 239 kg 1260 Hi: 50 Me:47 Lo: 42 650 239 Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve +Capillary tube Air handling equipment Fan type & Q'ty 650 40 R
FDC-HKXR (g) Wall mounted type (FDK) Models FDKJ22HKXE2, 28HKXE2, 36HKXE2, 45HKXE2 Models Item FDKJ22HKXE2(3) FDKJ28HKXE2(3) FDKJ36HKXE2(3) FDKJ45HKXE2(3) Nominal cooling capacity*1 W 2200 2800 3600 4500 Nominal heating capacity*2 W 2500 3200 4000 5000 dB(A) Hi: 42 Lo: 37 Power source 1 Phase 220/240V 50Hz Noise level Exterior dimensions Height Width Depth Net weight Hi: 42 Me:40 Lo: 37 mm 375 kg 950 Hi: 44 Me:41 Lo: 37 194 19 Refrigerant equipment Heat exchanger Louver fins &
FDC-HKXR Models FDKJ56HKXE2, 71HKXE2 Model FDKJ56HKXE2(3) FDKJ71HKXE2(3) W 5600 7100 W 6300 Item 1 Nominal cooling capacity* Nominal heating capacity*2 8000 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth Net weight Hi: 46 Me:43 Lo: 39 mm 375 1148 kg Hi: 47 Me:44 Lo: 40 194 375 Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve + Capillary tube Air handling equipment Fan type & Q'ty Tangential fan 1 W 194
FDC-HKXR (h) Floor standing exposed type (FDFL) Models FDFLJ28HKXE2, 45HKXE2, 71HKXE2 Model Item FDFLJ28HKXE2(3) FDFLJ45HKXE2(3) FDFLJ71HKXE2(3) Nominal cooling capacity*1 W 2800 4500 7100 Nominal heating capacity*2 W 3200 5000 8000 dB(A) Hi: 41 Me:38 Lo: 36 Power source 1 Phase 220/240V 50Hz Noise level Exterior dimensions Height Width Depth Net weight mm 630 kg Hi: 43 Me:41 Lo: 40 1196 225 630 32 Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve +
FDC-HKXR (i) Floor standing hidden type (FDFU) Models FDFUJ28HKXE2, 45HKXE2, 56HKXE2, 71HKXE2 Model Item FDFUJ28HKXE2(3) FDFUJ45HKXE2(3) FDFUJ56HKXE2(3) FDFUJ71HKXE2(3) Nominal cooling capacity*1 W 2800 4500 5600 7100 Nominal heating capacity*2 W 3200 5000 6300 8000 dB(A) Hi: 41 Me:38 Lo: 36 Power source 1 Phase 220/240V 50Hz Noise level Exterior dimensions Height Width Depth Net weight mm Hi: 43 Me:41 Lo: 40 630 1077 kg 225 630 25 Louver fins & inner grooved tubing Refrigerant
FDC-HKXR (2) Outdoor unit Models FDCP2001HKXRE2, 2501HKXRE2 Models Item FDCP2001HKXRE2(3) Power source FDCP2501HKXRE2(3) 3 Phase 380/415V 50Hz Nominal cooling capacity*1 W 22400 Nominal heating capacity*2 W 25000 28000 31500 60 dB(A) Noise level Exterior dimensions Height Width Depth mm Net weight 1700 kg Refrigerant equipment compressor type & Q' ty Motor 1350 600 340 361 RS5555HAS11 RS5570HAS11 5.5 kW 7.
FDC-HKXR (3) Operation chart Since the Multi KXR series air conditioner units are free multitype to which the indoor units of different capacity and different model can be combined, the operation characteristics of all combinations are very complicated, therefore only the individual operation characteristics of indoor and outdoor units are shown. For the combined operation characteristics, calculate them with the method shown in the next page.
FDC-HKXR FDK, FDFL, FDFU Series (220 V/240 V) Models Item FDK Series 22 28 36 FDFL, FDFU Series 45 56 71 28 45,56 71 Power input (kW) 0.05/0.06 0.06/0.07 0.08/0.09 0.09/0.11 0.09/0.10 0.09/0.10 0.09/0.10 Running current (A) 0.26/0.28 0.31/0.33 0.36/0.39 0.41/0.48 0.41/0.42 0.40/0.41 0.40/0.41 Notes (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
FDC-HKXR • Correction factor of compressor power input Model FDCP2001HKXRE2 Model FDCP2501HKXRE2 1.0 Power consumption correction coefficietnt Power consumption correction coefficietnt 1.0 0.8 0.6 0.4 0.2 Total capacity of indoor units operating simulataneously 45 105 (Below, the coefficients are the same.) 164 224 0.8 0.6 0.4 0.2 Total capacity of indoor units operating simulataneously (Below, the coefficients are the same.) 45 90 105 (Below, the coefficients are the same.
FDC-HKXR 20.2.2 Range of usage & limitations System FDCP2001HKXRE2 FDCP2501HKXRE2 Item Indoor intake air temperature (Upper, lower limits) Refer to the selection chart.
FDC-HKXR 20.2.3 Exterior dimensions (1) Indoor unit (a) Ceiling recessed type (FDT) Models FDTJ28HKXE2, 36HKXE2, 45HKXE2, 56HKXE2, 71HKXE2, 90HKXE2 Unit : mm Decorative Panel Holes for suspension bolts (M10 to M8 ×4pcs.) 860~890 (Ceiling hole size) Fresh air opening for ducting 780 (Suspension bolts pitch ) 950 630 C 400 B→ Liquid piping 28, 36, 45 type: φ6.35(1/4") 56, 71, 90 type: φ9.52(3/8") Gas piping 28, 36, 45 type: φ12.7(1/2") 56, 71, 90 type: φ15.
FDC-HKXR Models FDTJ112HKXE2, 140HKXE2 Unit : mm Decorative Panel Holes for suspension bolts (M10 to M8 ×4pcs.) 860~890 (Ceiling hole size) Fresh air opening for ducting 780 (Suspension bolts pitch ) 950 630 C 400 B→ Liquid piping φ9.52(3/8") 267 Drain hose (Accessories) (Local setting) 332 420 637 D 422 675 (Suspension bolts pitch) Exhaust air opening for ducting Air outlet 310 Air inlet grille VIEW A Gas piping φ19.
FDC-HKXR (b) 2-way outlet ceiling recessed type (FDTW) Models FDTWJ28HKXE2B, 45HKXE2B, 56HKXE2B Unit : mm Drain hose (Accessories) (Local setting) 278 64 47 Hole Suspension fitting Fresh air opening for ducting (knock out) 97 50 Holes of tapping screws 5 - φ4 264 91 Center of panel 640 70 Suspension bolts (M10 × 4 pcs.
FDC-HKXR Models FDTWJ71HKXE2B, 90HKXE2B Unit : mm 1054 382 240 240 200 200 295~ 325 Liquid piping φ9.52(3/8") ↑ 240 Holes for tapping screws 8 – φ4 128 Drain (VP25) (condensate pump drain) Hole for wiring 20 Drain (VP20) (Natural drainage) Exhaust air opening for ducting (knock out) Decorative Panel 64 Gas piping φ15.88(5/8") 230 8 750 or less Hole 78 20 310 A 20 10 364 330 Hole 88 640 50 95 620 410 100 140 10 148 460 VIEW A 219 212 Hole 20 66 (Max.
FDC-HKXR Models FDTWJ112HKXE2B, 140HKXE2B 310 50 64 110 103 Hole 130 70 50 Suspension fitting Fresh air opening for ducting (knock out) 97 Center of panel 640 (Ceiling hole size) Control box Holes for tapping screws 5-ø4 Suspension bolts (M10 × 4 pcs.
FDC-HKXR (c) 1-Way outlet ceiling recessed type (FDTS) Models FDTSJ22HKXE2B, 28HKXE2B, 36HKXE2B, 45HKXE2B 70 35 50 25 383 25 168 Panel center 200 45 250 150 60 285 315 180 435 90 Drain hose (Accessories) (Local setting) VIEW A Suspension bolts (M10×4 pcs.) 295~325 235 940 115 194 ←C 10 165 100 600 or less Max. Drain up 70 710 (Ceiling hole size) B→ 600 (Suspension bolts pitch) 40 555 Holes for tapping screws (φ4-6pcs.
FDC-HKXR Model FDTSJ71HKXE2B Unit : mm 1440 (Ceiling hole size) 1250 (Suspension bolts pitch) 675 70 200 60 Drain hose(Accessories) (Local setting) 295~325 1200 200 165 170 30 10 194 100 600 or less Max. Drain up Suspension bolts (M10×4pcs.) 150 VIEW A 90 100 45 250 140 35 50 25 168 Panel center ←C 30 70 Fresh air opening for ducting (Knock out) Air outlet 1180 210 35 60 100 Air inlet grille 140 50 40 90 85 110 770 70 290 45 70 140 Holes for tapping screws (φ4-6pcs.
FDC-HKXR (d) Cassetteria type (FDR) Model FDRJ22HKXE2 Silent Panel (Model: R-PNLS-26W-E) Unit : mm 980 (Ceiling hole size) 786 (Suspension bolts pitch) 433 353 71 45 Panel center 70 465 405 ↑ 213 MIN95 40 MIN156 MIN81 650 or less MIN320 480 A Drain(VP25) (Natural drainage) 460 Holes for tapping screws 4-φ4.
FDC-HKXR Model FDRJ22HKXE2 Canvas Panel (Model: R-PNLC -26W-E) 804 (Ceiling hole size) 786 (Suspension bolts pitch) 353 433 9 45 Fresh air opening for ducting (Knock out) 284 69 150 193 69 Drain (Connectable with VP25) Liquid piping φ6.35(1/4") Gas piping φ12.7(1/2") Control box Panel center 352 525 (Ceiling hole size) 90 ↓ 45 545 (Suspension bolt pitch) 70 C Drain hose (Accessories) (Load setting) 9 Unit : mm 405 59 VIEW C 71 Supply air duct Max.
FDC-HKXR Models FDRJ28HKXE2, 45HKXE2, 56HKXE2 Silent Panel (Model: R-PNLS-26W-E) Unit : mm 980 (Ceiling hole size) 786 (Suspension bols pitch) 137 Fresh air opening for ducting (Knock out) (Local setting) 353 284 45 panel center 71 Supply air duct 150 690 (Ceiling hole size) 545 (Suspension bolt pitch) 45 59 405 75 275 270 Control box 70 69 C↓ VIEW C Drain (Connectable with VP25) Gas piping 28, 45 type: φ12.7 (1/2") 56 type: φ15.88 (5/8") Liquid piping 28, 45 type: φ6.
FDC-HKXR Models FDRJ28HKXE2, 45HKXE2, 56HKXE2 Canvas Panel (Model: R-PNLC-26W-E) Unit : mm Drain hose (Accessories) 804 (Ceiling hole size) 9 786 (Suspension bolts pitch) 353 284 Fresh air opening for ducting (Knock out) 45 C↓ Control box 150 193 69 Drain (Connectable with VP25) Panel center Liquid piping 28, 45 type: φ6.35 (1/4") 56 type: φ9.52 (3/8") Gas piping 28, 45 type: φ12.7 (1/2") 56 type: φ15.
FDC-HKXR Models FDRJ71HKXE2, 90HKXE2 Silent Panel (Model: R-PNLS-36W-E) Unit : mm 1180 (Ceiling hole size) 986 (Suspension bolts pitch) 533 137 453 Drain hose (Accessories) (Local setting) Fresh air opening for ducting (Knock out) 45 Panel center 71 465 Drain (VP20) (Natural drainage) ↑A MIN95 40 405 MIN156 MIN320 Hole for wiring (φ35) 250 460 213 205 1240 150 φ149 Holes for tapping screws (4-φ4.
FDC-HKXR Models FDRJ71HKXE2, 90HKXE2 Canvas Panel (Model: R-PNLC-36W-E) Unit : mm Drain hose (Accessories) (Local setting) 1004 (Ceilinghole hole size) 986 (Suspension bolts pitch) 453 69 Drain (Connectable with VP25) Control box Liquid piping φ9.52(3/8") 59 71 Supply air duct 950 510 480 465 405 149 260 35 B→ 40 215 199 285 635 80 274 285 295~325 130 165 VIEW C 299 Suspension bolts (M10 × 4pcs.) 500 Gas piping φ15.88(5/8") Max.
FDC-HKXR Models FDRJ112HKXE2, 140HKXE2 Silent Panel (Model: R-PNLS-46W-E) Unit : mm 1600 (Ceiling hole size) 1406 (Suspension bolts pitch) 663 270 58 45 Panerl center Supply air duct 175 320 320 70 Liquid piping φ19.05(3/4") 295~325 320 VIEW C 80 (Max. Drain up) 1370 495 Drain (Connectable with VP25) 76 Gas piping φ19.05(3/4") Suspension bolts (M10 ×4pcs.
FDC-HKXR Models FDRJ112HKXE2, 140HKXE2 Canvas Panel (Model: R-PNLC-46W-E) Unit : mm 1424 (Ceiling hole size) 1406 (Suspension bolts pitch) 743 663 150 Drain (Connecteble with VP25) 495 Liquid piping φ9.52(3/8") 59 1370 465 405 86 0 200 295~325 250 235 510 325 320 635 480 350 320 600 or less 320 130 175 80 Max. Drain up 71 Supply air duct VIEW C Gas piping φ19.05(3/4") 310 352 Panel center 40 70 45 69 Control box Suspension bolts (M10 × 4pcs.
FDC-HKXR (e) Satellite ducted type (FDUM) Models FDUMJ36HKXE2, 45HKXE2, 56HKXE2 Unit : mm 786 (Suspension bolts pitch) 750 18 80 B 205 Hole of tapping screws (4-φ4) Drain hose (Accessories) (Local setting) Drain (Connectable with VP25) 284 A→ 213 φ149 Control box φ170 Liquid piping 36, 45 type: φ6.35(1/4") 56 type: φ9.52(3/8") 118 472 (Suspension bolts pitch) 45 ↑ 18 59 Fresh air opening for ducting (Knock out) Gas piping 36, 45 type: φ12.7(1/2") 56 type: φ15.
FDC-HKXR Models FDUMJ71HKXE2, 90HKXE2 Unit : mm 986 (Suspension bolts pitch) 950 18 472 (Suspension bolts pitch) 45 ↑ 18 80 B 205 284 118 A→ 59 71 213 Holes of tapping screws 4-φ4 φ149 Control box Drain hose (Accessories) (Local setting) Drain (Connectable with VP25) φ170 Liquid piping φ9.52(3/8") Fresh air opening Gas piping for ducting φ15.
FDC-HKXR Models FDUMJ112HKXE2, 140HKXE2 Unit : mm 1406 (Suspension bolts pitch) 1370 ↑ 18 205 80 B Holes of tapping screws (4-φ4) 213 φ149 Control box 284 A→ Drain hose (Accessories) (Local setting) Drain (Connectable with VP25) Liquid piping φ9.
FDC-HKXR (f) Ceiling suspension type (FDE) Models FDEJ36HKXE2B, 45HKXE2B, 56HKXEB2 Unit : mm 984 (Suspension bolts pitch) 15 15 Holes for suspension bolts (M8 to M10 × 4 pcs.
FDC-HKXR Model FDEJ112HKXE2B Unit : mm 1244 (Suspension bolts pitch) 15 15 Holes for suspension bolts (M8 to M10 × 4pcs.
FDC-HKXR (g) Wall mounted type (FDK) Models FDKJ22HKXE2, 28HKXE2, 36HKXE2, 45HKXE2 Unit : mm 950 23 387 387 130 23 4 194 7.7 59 65 710 155 820 155 77.5 25 25 20 20 25 20 20 77.5 65 155 Space for installation and service 200 Mounting plate φ8 × 48 pcs.
FDC-HKXR Model FDKJ71HKXE2 23 Unit : mm 1436 486 387 387 130 23 194 4 7.7 Outlet for piping (On both side) 65 377.5 155 108 Space for installation and service Mounting plate 200 10 38 50 377.5 Detail of mounting plate 150 200 or more or more 45 φ8 × 48 pcs. (Holes on mounting plate) or more 155 108 1306 155 25 25 20 20 25 20 20 8 10 64 59 65 1196 65 58 90 Outlet for electric wiring 375 280 ←A Piping cover Hole on wall for 55 Gas piping φ 9.
FDC-HKXR (i) Floor standing hidden type (FDFU) Models FDFUJ28HKXE2, 45HKXE2, 56HKXE2, 71HKXE2 Note (1) Value in ( Unit : mm ) indicates 71 type.
FDC-HKXR (2) Remote controller (Optional parts) Wall 0.3mm2, 3cores (O.D.φ5.6) Wire (Recessed) LCD display Junction box (Locally Purchased) 120 16 Remote controller mounting dimensions 120 60 46 47 17 7 120 89 83.
FDC-HKXR (3) Individual flow divide controller (Optional Part) HPFD01R-E 117.5 Indoor refrigerant piping connection pipe Liquid pipe φ9.52 (3/8") flare. with included different diameter adapter coupling φ6.35 (1/4") pipe Hanging bolt position (M10 provided at site) 61 Indoor connection wire (length 200) (with insert terminal) Outdoor refrigerant piping connection pipe Liquid pipe φ9.52 (3/8") flare. with included different diameter adapter coupling φ6.35 (1/4") pipe 37.5 73.
Wire entry hole (φ50) 15 640 35 36 24 250 850 pass-through hole (φ100) Back 50 Piping and wiring bottom 118 Drain waste water hole (6-φ20) 170 φ19.05 (3/4") Refrigerant discharge gas piping connection pipe Anchor bolt hole (4 locations for M10) 150 250 240 163 80 250 187 168 145 2001: with φ25.4 (1") pipe 2501: with φ28.58 (1 1/8") pipe Refrigerant Intake gas piping connection pipe φ12.
FDC-HKXR 20.2.4 Exterior appearance (1) Indoor unit (a) Ceiling recessed type (FDT) ● Decorative panel Pearl white (b) 2-way outlet ceiling recessed type (FDTW) Air outlet Air inlet ● Decorative panel (i) Standard type Panel part No. Type Panel color With Auto swing Pearl white TW-PSA-22W-E TW-PSA-32W-E Applicable model FDTW28, 45, 56 type TW-PSA-42W-E FDTW71, 90 type FDTW112, 140 type (ii) Attachment of ceiling material type Panel part No.
FDC-HKXR (c) 1-way outlet ceiling recessed type (FDTS) Panel Ceramic white Air inlet grille Ceramic white ● Decorative panel Panel part No. TS-PSA-26W-E TS-PSA-36W-E Type Panel color With Auto swing Misty white Applicable model FDTS22, 28, 36, 45 type FDTS71 type (d) Cassetteria type (FDR) Silent panel type Canvas-duct panel type Ceramic white Ceramic white (e) Satellite ducted type (FDUM) ..........................................
FDC-HKXR (g) Wall mounted type (FDK) 3 2 No. Parts name 1 Side plate 2 Front panel 3 Air inlet grill 4 Air outlet louver 5 Bottom plate 6 Right and Left louvers Color 1 1 4 6 5 Ceramic white Light gray (h) Floor standing exposed type (FDFL) Dark gray (Air outlet grill) Ceramic white (Body) Black (Bottom plate) (i) Floor standing hidden type (FDFU) ........................
FDE series have external installation as the expansion valve box. Indoor unit B Intake Thermistor (Th1-A) ø9.52 (3/8") - Note (1) The solenoid valve is open during magnetic inductance and closed when there is not magnetic inductance.
FDC-HKXR 20.2.6 Selection chart (1) Correct the cooling and heating capacity in accordance with the conditions as follows.The net cooling and heating capacity can be,obtained in the following way. Indoor unit Each indoor unit = System performance Indoor unit capacity Indoor unit capacity when operating simultaneously.
FDC-HKXR (c) When the outdoor unit is located at a lower height than the indoor unit in cooling operation and when the outdoor unit is located at a higher height than the indoor unit in heating operation, the following values should be subtracvted from the values in the above table.
FDC-HKXR FDCP2501HKXRE2 Total capacity of indoor units operating simultaneously Capacity Correction Calculations (The procedure for both cooling and heating is the same.) Example Conditions • Unit (50 Hz) Outdoor unit FDCP2501HKXRE2 1 unit Indoor unit FDTJ90HKXE2 - 1 unit FDTJ140HKXE2 - 1 unit FDTWJ28HKXE2B - 1 unit FDTSJ22HKXE2B - 1 unit • Piping length (Shall be common among units) .......... 60 meters (suitable length) • Difference in height between indoor and ...........
FDC-HKXR (3) Sensible heat capacity (a) FDT Series Model FDTJ28HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 12 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 2.89 2.83 2.76 2.68 2.60 2.53 2.46 SHC 2.58 2.55 2.52 2.49 2.46 2.43 2.40 18.0°CWB TC 2.98 2.91 2.85 2.77 2.70 2.63 2.56 SHC 2.60 2.57 2.55 2.52 2.49 2.46 2.43 19.0°CWB TC 3.05 2.99 2.92 2.86 2.80 2.72 2.64 SHC 2.61 2.59 2.56 2.54 2.52 2.49 2.46 20.0°CWB TC 3.13 3.07 3.01 2.95 2.88 2.81 2.74 SHC 2.63 2.61 2.58 2.56 2.54 2.
FDC-HKXR Model FDTJ71KHXE2 Air flow 3 (m /min) 16 Indoor air temperature Outdoor air temp. 17.0°CWB (°CDB) TC 7.33 7.18 7.00 6.80 6.60 6.42 6.23 27 29 31 33 35 37 39 SHC 5.31 5.24 5.15 5.06 4.97 4.89 4.81 18.0°CWB TC 7.55 7.39 7.22 7.04 6.85 6.67 6.48 SHC 5.34 5.27 5.19 5.11 5.03 4.95 4.87 19.0°CWB TC 7.75 7.58 7.41 7.26 7.10 6.90 6.70 SHC 5.35 5.28 5.21 5.14 5.07 4.99 4.91 20.0°CWB TC 7.94 7.78 7.63 7.47 7.31 7.13 6.94 SHC 5.36 5.29 5.23 5.16 5.10 5.02 4.95 21.0°CWB TC 8.13 7.99 7.83 7.66 7.
FDC-HKXR (b) FDTS Series Model FDTSJ22HKXE2B Air flow 3 (m /min) 11 Indoor air temperature Outdoor air temp. (°CDB) 17.0°CWB TC 2.27 2.22 2.17 2.11 2.05 1.99 1.93 27 29 31 33 35 37 39 SHC 2.04 2.02 2.00 1.98 1.95 1.93 1.91 18.0°CWB TC 2.34 2.29 2.24 2.18 2.12 2.07 2.01 SHC 2.06 2.04 2.02 2.00 1.98 1.95 1.93 19.0°CWB TC 2.40 2.35 2.30 2.25 2.20 2.14 2.08 SHC 2.08 2.06 2.04 2.02 2.00 1.98 1.95 20.0°CWB TC 2.46 2.41 2.36 2.31 2.27 2.21 2.15 SHC 2.09 2.07 2.05 2.03 2.02 2.00 1.98 21.0°CWB TC 2.
FDC-HKXR Model FDTSJ71HKXE2B Air flow 3 (m /min) 18 Indoor air temperature Outdoor air temp. (°CDB) 17.0°CWB TC 7.36 7.19 7.01 6.83 6.60 6.43 6.22 27 29 31 33 35 37 39 SHC 5.56 5.49 5.41 5.33 5.23 5.15 5.06 18.0°CWB TC 7.57 7.40 7.23 7.06 6.89 6.66 6.48 SHC 5.59 5.52 5.45 5.37 5.30 5.21 5.13 19.0°CWB TC 7.77 7.61 7.44 7.27 7.10 6.93 6.72 SHC 5.61 5.55 5.48 5.41 5.34 5.27 5.18 20.0°CWB TC 7.92 7.80 7.65 7.48 7.31 7.14 6.97 SHC 5.61 5.56 5.50 5.44 5.37 5.30 5.24 21.0°CWB TC 8.14 7.97 7.82 7.70 7.
FDC-HKXR Model FDRJ56HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 14 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 5.80 5.67 5.53 5.39 5.21 5.07 4.91 SHC 4.36 4.30 4.24 4.18 4.10 4.04 3.97 18.0°CWB TC 5.97 5.84 5.70 5.57 5.43 5.25 5.11 SHC 4.39 4.33 4.27 4.21 4.16 4.08 4.02 19.0°CWB TC 6.13 6.00 5.87 5.73 5.60 5.47 5.30 SHC 4.40 4.35 4.29 4.24 4.18 4.13 4.06 20.0°CWB TC 6.25 6.15 6.04 5.90 5.77 5.63 5.50 SHC 4.40 4.36 4.32 4.26 4.21 4.16 4.10 21.0°CWB TC 6.42 6.28 6.17 6.07 5.
FDC-HKXR Model FDRJ140HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 34 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 14.50 14.17 13.83 13.47 13.02 12.68 12.26 SHC 10.78 10.63 10.48 10.31 10.12 9.97 9.78 18.0°CWB TC 14.92 14.59 14.25 13.92 13.58 13.13 12.77 SHC 10.84 10.69 10.55 10.40 10.26 10.07 9.91 19.0°CWB TC 15.32 15.01 14.67 14.34 14.00 13.66 13.24 SHC 10.88 10.75 10.60 10.46 10.32 10.19 10.01 20.0°CWB TC 15.62 15.37 15.09 14.76 14.42 14.08 13.75 SHC 10.87 10.77 10.65 10.
FDC-HKXR Model FDUMJ71HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 18 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 7.36 7.19 7.01 6.83 6.60 6.43 6.22 SHC 5.56 5.49 5.41 5.33 5.23 5.15 5.06 18.0°CWB TC 7.57 7.40 7.23 7.06 6.89 6.66 6.48 SHC 5.59 5.52 5.45 5.37 5.30 5.21 5.13 19.0°CWB TC 7.77 7.61 7.44 7.27 7.10 6.93 6.72 SHC 5.61 5.55 5.48 5.41 5.34 5.27 5.18 20.0°CWB TC 7.92 7.80 7.65 7.48 7.31 7.14 6.97 SHC 5.61 5.56 5.50 5.44 5.37 5.30 5.24 21.0°CWB TC 8.14 7.97 7.82 7.70 7.
FDC-HKXR (e) FDE Series Model FDEJ36HKXE2B Air flow 3 (m /min) Outdoor air temp. (°CDB) 14 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 3.73 3.64 3.56 3.46 3.35 3.26 3.15 SHC 3.34 3.30 3.26 3.23 3.18 3.15 3.10 18.0°CWB TC 3.84 3.75 3.66 3.58 3.49 3.38 3.28 SHC 3.36 3.33 3.30 3.26 3.23 3.18 3.15 19.0°CWB TC 3.94 3.86 3.77 3.69 3.60 3.51 3.41 SHC 3.39 3.36 3.32 3.29 3.26 3.23 3.19 20.0°CWB TC 4.02 3.95 3.88 3.79 3.71 3.62 3.54 SHC 3.40 3.38 3.35 3.32 3.29 3.26 3.23 21.0°CWB TC 4.13 4.
FDC-HKXR Model FDEJ112HKXE2B Air flow 3 (m /min) Outdoor air temp. (°CDB) 28 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 11.60 11.33 11.07 10.77 10.42 10.15 9.81 SHC 8.72 8.60 8.48 8.35 8.20 8.08 7.93 18.0°CWB TC 11.94 11.67 11.40 11.13 10.86 10.51 10.21 SHC 8.77 8.66 8.54 8.42 8.31 8.16 8.04 19.0°CWB TC 12.25 12.01 11.74 11.47 11.20 10.93 10.60 SHC 8.80 8.70 8.59 8.48 8.37 8.26 8.12 20.0°CWB TC 12.50 12.30 12.07 11.80 11.54 11.27 11.00 SHC 8.80 8.72 8.63 8.52 8.42 8.31 8.20 21.
FDC-HKXR Model FDKJ36HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 10 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 3.73 3.64 3.56 3.46 3.35 3.26 3.15 SHC 2.93 2.89 2.86 2.82 2.77 2.73 2.68 18.0°CWB TC 3.84 3.75 3.66 3.58 3.49 3.38 3.28 SHC 2.95 2.91 2.88 2.84 2.81 2.76 2.72 19.0°CWB TC 3.94 3.86 3.77 3.69 3.60 3.51 3.41 SHC 2.96 2.93 2.90 2.86 2.83 2.79 2.75 20.0°CWB TC 4.02 3.95 3.88 3.79 3.71 3.62 3.54 SHC 2.97 2.94 2.91 2.88 2.85 2.81 2.78 21.0°CWB TC 4.13 4.04 3.97 3.90 3.
FDC-HKXR (g) FDFL, FDFU Series Models FDFLJ28HKXE2, FDFUJ28HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 12 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 2.90 2.83 2.77 2.69 2.60 2.54 2.45 SHC 2.58 2.55 2.52 2.49 2.46 2.43 2.40 18.0°CWB TC 2.98 2.92 2.85 2.78 2.72 2.63 2.55 SHC 2.60 2.57 2.55 2.52 2.49 2.46 2.43 19.0°CWB TC 3.06 3.00 2.93 2.87 2.80 2.73 2.65 SHC 2.62 2.59 2.57 2.54 2.52 2.49 2.46 20.0°CWB TC 3.12 3.07 3.02 2.95 2.88 2.82 2.75 SHC 2.63 2.61 2.59 2.56 2.54 2.52 2.
FDC-HKXR 20.2.7 Characteristics of fan (1) Cassetteria type (FDR) How to interpret the blower characteristics table ● External static pressure table Duct specs. 40(4) 45(4.5) 85(8.5) 45(4.5) 85(8.5) FDR45 56 type FDR71 type 14 - - 18 30(3) 65(6.5) 45(4.5) 80(8) 50(5) 85(8.5) FDR90 type 20 25(2.5) 60(6) 45(4.5) 80(8) 50(5) 85(8.5) FDR112 type 28 40(4) 70(7) 50(5) 80(8) 55(5.5) 85(8.5) FDR140 type 34 40(4) 70(7) 50(5) 80(8) 55(5.5) 85(8.5) Static pressure Pa (mmAq) 45(4.5) 85(8.
FDC-HKXR Models FDRJ45HKXE2, 56HKXE2 Model FDRJ71HKXE2 120(12) 120(12) d• pee h sr limit g i H pe Up Hi e sp it ed •M ed 60(6) lim r pe Up it ow gh S Hi ta ium rd• a nd gh gh Hi gh Hi s gh sp ar w •L an St rd gh Hi d• da ium ed •M rd da ow 2-spot blower internal resistance (0)0 [Standard] 2-spot blower internal resistance Square duct blower internal resistance [Standard] 3-spot blower internal resistance (-2)-20 12 14 Air flow (m /min) 13 14 Lower limit 18
FDC-HKXR Model FDRJ140HKXE2 120(12) d ee sp m iu da an St w Lo d• ee sp d ee sp it h g m Hi w li Lo a St 40(4) h ig ed M d• gh 60(6) •H ee • rd t da limi n a r St ppe U Hi H rd• igh 20(2) •M rd w da Lo d• ar an St nd Static pressure Pa (mmAq) h ig H sp 80(8) gh Hi • ed pe it s m gh li Hi per p U 100(10) ium ed 3-spot blower internal resistance (0)0 (0)0 4-spot blower internal resistance [Standard] Square duct blower internal resistance Internal resistance without suction
FDC-HKXR (2) Satellite ducted type (FDUM) ● External static pressure table Duct specs. 1 spot closing Standard Square duct How to interpret the blower characteristics table Example : Case of FDUMJ71HKXE2 40(4) 90(9) 50(5) 90(9) 18 35(3.5) 70(7) 50(5) 85(8.5) 55(5.5) FDUM90 type 20 30(3) 65(6.5) 50(5) 85(8.5) 55(5.5) FDUM112 type 28 50(5) 80(8) 60(6) FDUM140 type 34 50(5) 75(7.5) 60(6) 90(9) 90(9) 90(9) 65(6.5) 95(9.5) 85(8.5) 65(6.5) 95(9.
FDC-HKXR Model FDUMJ71HKXE2 Model FDUMJ90HKXE2 120(12) 120(12) 100(10) ee da an ow St L d• gh Hi rd• 40(4) Sta w ium Me rd• 20(2) ed 2-spot blower internal resistance nda •Lo ard •M rd nd da Sta Static pressure Pa (mmAq) d• ee p s it gh lim Hi w Lo sp Static pressure Pa (mmAq) m iu ed M d• ee sp U rd• da 60(6) Stan gh an diu 0(0) t mi r li e pp Hi St 20(2) gh Hi gh m iu w d• r da an St w Lo Lo d• ee sp 40(4) h ig •H Hi ed M d• gh Hi d ee sp it h ig
FDC-HKXR 20.2.8 Noise level Notes (1) The data are based on the following conditions. Ambient air tempetature: Indoor unit 27˚C DB, 19˚C WB. Outdoor unit 35˚C DB (2) The data in the chart are measuted in an unechonic room. (3) The noise levels measured in the field are usually higher than the data because of reflection. (1) Indoor unit Measured based on JIS B 8616 Mike position as below Mike position as below (a) Ceiling recessed type (FDT) 1.
FDC-HKXR Model FDTWJ90HKXE2B Model FDTWJ112HKXE2B Model FDTWJ140HKXE2B Noise level 41 dB (A) at HIGH Noise level 44 dB (A) at HIGH Noise level 45 dB (A) at HIGH 39 dB (A) at MEDIUM 41 dB (A) at MEDIUM 42 dB (A) at MEDIUM 36 dB (A) at LOW 38 dB (A) at LOW 39 dB (A) at LOW 70 70 70 60 N60 50 50 N50 40 40 N40 30 30 N2 125 250 0 500 60 60 50 50 N50 40 40 N40 30 30 1000 2000 4000 N2 20 8000 63 125 250 500 60 60 N60 50 50 N50 40 40 N40 30 30 N30 0 20 1000 2000 4000 N2 20
FDC-HKXR (d) Cassetteria type (FDR) Unit 1.5m Measured based on JIS B 8616 Mike position as below Mike (center & low points) Mid octave band frequency (Hz) Sound pressure level (Standard 0.0002 µ bar) dB Model FDRJ28HKXE2 Models FDRJ45HKXE2, 56HKXE2 Noise level 43 dB (A) at HIGH Noise level 44 dB (A) at HIGH 41 dB (A) at MEDIUM 41 dB (A) at MEDIUM 38 dB (A) at LOW 38 dB (A) at LOW Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.
FDC-HKXR Mid octave band frequency (Hz) Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.
FDC-HKXR 1m (f) Ceiling suspension type (FDE) Unit 1m Measured based on JIS B 8616 Mike position as below Noise level 44 dB (A) at HIGH 40 dB (A) at MEDIUM 38 dB (A) at LOW Mid octave band frequency (Hz) Model FDEJ112HKXE2B Noise level 49 dB (A) at HIGH 46 dB (A) at MEDIUM 42 dB (A) at LOW Sound pressure level (Standard 0.0002 µ bar) dB Model FDEJ71HKXE2B Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.
FDC-HKXR Model FDKJ56HKXE2 Noise level 46 dB (A) at HIGH 43 dB (A) at MEDIUM 39 dB (A) at LOW Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.
B TB A N BL BL WH RD Y/GN Fan motor Internal thermostat for FMI Capacitor for FMI Drain motor Float switch (For overflow prevention) Louver motor Limit switch Stepping motor (For Exp.
FMI 49FI CFI DM FS LM LS SM X1,2,3,6 X4 X5 Mark BL BL Parts name B A TB Y/GN WH RD F(3.15A) Fan motor Internal thermostat for FMI Capacitor for FMI Drain motor Float switch (For overflow prevention) Louver motor Limit switch Stepping motor (For Exp.
*1 FMI1,2 49FI CFI1,2 DM FS LM LS SM X1,2,3 X4 X5 RD L H RD CnF2 OR Y/GN WH CnW4 RD 8V CnM CnB2 RD CnK2 BL CnK BL CnW3 BL BL RD CnW2 CnO Y/GN BL BL CnW4 BL 17V BL RD RD WH WH RD RD Trl WH WH 220/240V RD CnL RD 2 1 *1 Val RD L H OR X1 CnF3 X2 CnD CFl2 UH BR OR CnF3 FMl2 (49FI) M Parts name ThI-A ThI-R SW1 SW2 SW3 SW4 SW6 Trl Val LED·R LED·G Mark Thermistor Thermistor Indoor unit address ten's place Indoor unit address unit's place Outdoor unit add
BL BL WH Y/GN CnS Y/GN CnO CnK2 BL CnK BL WH RD 2 X1 CnF4 X2 Val 8 L Printed circuit board 1 OR OR WH Y/GN CnD CFl1 UH CnF4 CnF2 H 6 CnF4 FMI1 (49FI) M 7 X3 L BL X3 X2 X1 CnF2 CnF5 H OR OR CnF5 FMI2 (49FI) M BK X4 Parts name Fan motor Capacitor for FMI Drain motor Float switch Stepping motor (For Exp.
Mark Parts name Fan motor Capacitor for FMI Drain motor Float switch (For overflow prevention) Stepping motor (For Exp.v) Auxiliary relay (For FMI) Auxiliary relay (For DM) Internal thermostat for FMI Thermistor Thermistor Meaning of marks FMI1,2 CFI1,2 DM FS SM X1,2,3 X4 49FI ThI-A ThI-R Y/GN BL CnM CnO CnK2 BL CnK BL B N TB A BL RD WH Y/GN F(3.
B A TB Mark FMI1,2 CFI1,2 49FI LM LS SM X1,2,3 X5 ThI-A ThI-R WH RD WH Y/GN RD BL BL CnM BL BL RD RD CnO CnK2 BL CnK BL CnW3 Y/GN CnK2 CnW4 BL 17V BL CnW2 RD WH RD 2 1 VaI *1 L X3 X2 X1 OR OR H60 CnF3 FMI2 (49FI) M X5 X4 BR Y/GN CnD CFI2 H50 CnF3 X2 X1 L 8 H 6 OR OR CnF2 FMI1 (49FI) M Cn F6 7 X3 CFI1 UH CnF2 Cn F5 Fan motor Capacitor for FMI Internal thermostat for FMI Louver motor Limit switch Stepping motor (For Exp.
FMI CFI 49FI LM LS SM X1,2,3 X5 ThI-A ThI-R Y/GN BL BL Y/GN CnF1 Parts name H WH OR OR CnF1 CnF2 M BL BL FMI1 (49FI) L BK BK *1 RD RD Y/GN WH WH Fan motor Capacitor for FMI Internal thermostat for FMI Louver motor Limit switch Stepping motor (For Exp.v) Auxiliary relay (For FMI) Auxiliary relay (For LM) Thermistor Thermistor Meaning of marks Mark B TB A WH F(3.
Parts name Fan motor Capacitor for FMI Internal thermostat for FMI Stepping motor (For Exp.
FDC-HKXR (2) Individual flow divide controller Power source (between indoor unit) Power source 1 phase 220/240V 50Hz Notes (1) This illustration shows the circuit diagram for when 1 indoor unit is connected with a central flow divide controller and relay kit (flow divide controller accessory). (2) “.......” denotes the local wiring. (3) The option shows when a remote start/stop and monitoring kit is connected.
CM FM1,2 IM 52C 49F1,2 CH CF1,2 X1 X2 X3 X4 X7 X8~10 X11 X12 X13 X14 X20 20SS Mark Parts name Compressor motor Fan motor (outdoor unit) Motor for cooling inverter Magnetic contactor for CM Internal thermostat for FMo Crankcase heater Capacitor for FMo Auxiliary relay (for 52C) Auxiliary relay (for 20SS) Auxiliary relay (for 20SL) Auxiliary relay (for SV1) Auxiliary relay (for 20VF, 20VU) Auxiliary relay (for FMo1) Auxiliary relay (for FMo2) Auxiliary relay (for SVS) Auxiliary relay (for SVL) Auxiliary re
FDC-HKXR 20.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER (1) Remote controller (Optional parts) FDR,FDUM,FDFL and FDFU series are not provided with AUTO SWING switch. Panel shown below will appear if you open the cover. All contents of display on the LCD are indicated simultaneously for the purpose of explanation. Pull the knob on the cover to this side to open it downward. Filter sign Operation mode display When this sign is indicated, clean the filter.
FDC-HKXR (2) Automatic Operation Once the [Auto] mode is selected by remote control, the operating mode is automatically selected according to the setting temperature and the intake air temperature of the indoor unit and cooling or heating operation is performed. The determination is performed when the thermostat has been in the OFF mode for 10 minutes or more continuously.
FDC-HKXR (5) Dehumidifying (Thermal dry) D C Low -2 B A +2 ▲ High Room temperature setting point • Indoor unit fan will be operated in D block as shown below. 20 sec. Lo OFF 4 min.
FDC-HKXR (7) Value shift adjustment of room air temperature detection in heating Under the standard specifications, the room temperature is adjusted at the setting temperature by controlling the indoor unit capacity based on the setting temperature of thermostat and the suction air temperature. However, where the unit is installed in the ceiling and warm air tends to stay around the ceiling, temperature in the living space may not be adjusted at the setting temperature.
FDC-HKXR (10) Condensate pump motor (DM) control (Only FDT, FDTW, FDTS, FDR, FDUM models) (a) Drain motor is started no sooner than the compressor is turned ON during cooling or dehumidifying operation. The drain motor continues to operate for 2 minutes after the stop of unit operation, stop with the error stop, thermostat stop and at switching from cooling or dehumidifying operation to blowing or heating operation.
FDC-HKXR (11) Defrosting (a) Conditions for starting defrosting When all the following conditions are met, the defrosting operation will start: -2°C Outdoor unit heat exchanger temp. (ThO-R) 1) The cumulative operating time of the compressor comes up to 45 minutes after completion of a defrosting operation, or it comes up to 30 minutes after a heating operation starts (the remote controller is turned on). 2) Five minutes has passed after the compressor was turned off and on.
FDC-HKXR (12) Multiple Units Control-Simultaneous Control of 16 unit with one remote controller (a) Function Multiple units (even of outdoor different systems, 16 units maximum) can be simultaneously controlled by using a remote control switch (a special order item). The remote control switch is used to set the “operation mode”, and all the unit can be operated and stopped at intervals of 0.5 to 1 second in the order of unit number. Thermostat and protective functions of each unit functions independently.
FDC-HKXR (ii) When SW5-1 on the PCB of indoor unit is turned on at the field. Input signal to CnT becomes valid at OFF → ON only and the motion of air conditioner [ON/OFF] is inverted.
FDC-HKXR LP,HP-B controls Under these controls, the high and low level pressures are controlled with the solenoid valves, outdoor fan and other so as to operate the outdoor unit in the optimum condition in accordance with changing load on the indoor unit. Operation patterns consist of the following 12 types and respective functional parts are controlled per each pattern.
FDC-HKXR (17) Compressor operating frequency increase control (a) In the case that at least one in-door unit requires the maximum frequency supply during cooling or heating operation for 6 minutes continuously, the compressor operating frequency is increased by 10 Hz. After that, the maximum frequency is increased by 10 Hz every continuous 6 minutes; however, the upper limit is 30 Hz. (b) When requirement of the maximum frequency ceases, the control is released.
FDC-HKXR (19) Devices related to unit protection and maintenance (a) Test Run Mode The test run mode can be set from the outside by using the switch SW3-4,5 on the outdoor unit control circuit board (i) Switch function Switch SW3-4 SW3-5 Function ON • To operate all connected indoor units. • Indoor units demands the maximum frequency and outdoor units are operated with the maximum frequency according to request from the indoor unit.
FDC-HKXR (iii) Three minutes delay timer The compressor (inverter) will remain in stop state for 3 minutes, when the compressor is stopped by thermostat, ON/OFF swich, and /or by occurrence of trouble. When the power source is turned ON, the 3-minutes delay timer is cancelled.
FDC-HKXR (k) Protection of Power Transistor from Overheat When the temperature of the power transistor increases to the set temperature, stop the inverter immediately and let is reset by itself 3 minutes later. If the power transistor is overheated again within 2 hours, turn off 52C, bring it to an abnormal stop and the inspection displays (Remote controller : E41, indoor unit green LED : Continuous flashing, red LED : OFF, outdoor unit green LED : Continuous flashing, red LED : 4 times flash) will appear.
FDC-HKXR 20.5 APPLICATION DATA SAFETY PRECAUTIONS • Please read these “Safety Precautios” first then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two headings, WARNING and CAUTION , those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the WARNING section.
FDC-HKXR 20.5.1 Installation of indoor unit This is same as multi KX series. Refer to page 841~881. 20.5.2 Installation of the remote controller (Optional parts) This is same as multi KX series. Refer to page 882. 20.5.3 Installation of outdoor unit (1) Selection of installation location (a) A palce where air will not be stagnant. (b) A place where the exhaust air will not be shorteyeled. (c) A place with enough space for air flow around the unit.
FDC-HKXR 2) When there is an obstacle above the unit Note (1) The side air outlet indicates that a wind direction variable adapter available on the optional parts is fitted to the unit.
FDC-HKXR 7) Installation where there is obstacle on all four sides. Note (1) The up air outlet indicates that a wind direction variable adaptor available on the optional parts is fitted on the unit. (b) Installation of multiple units 1) Continuous installation on side-to-side [The front side is open] [Keep a space of more than 10 mm between the units] Note (1) There shall be no obstacle above the unit. [Remarks] When the unit is installed continuously side by side, any multiple units can be installed.
FDC-HKXR 3) Face-to-face installation Dimension Distance L1 Item Diagonal 1500 or more 1000 or more 500 or more 500 or more Up air outlet Unit: mm L2 Note (1) Make the air outlet the diagonal air outlet (standard) or the up air outlet (option).
FDC-HKXR (3) Installation Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following. (a) Fix the unit to the foundation with anchor bolts. Unit: mm 1050 (b) When installing the unit, be sure to fix the pedestal of the unit with bolts. (c) Install the unit securely not to be fallen by earthquake or strong of wind. (d) Prepare a concrete foundation referring to the above figure.
FDC-HKXR 20.5.4 Refrigerant piping (1) Precautions no refrigerant piping work for prevention against compressor lock Compressor trouble including lock and motor burn-out is due to faulty parts but mainly concerned in installation and refrigerant piping conditions, The precautions for refrigerant piping are as belows. (a) Be sure to perform brazing while flowing nitrogen. 1) Without flowing nitrogen gas, a lot of oxide film (CU2O) is generated.
FDC-HKXR (2) Refrigerant piping size selection Branch line Outdoor unit connection pipe Indoor unit connection pipe Downstream indoor unit capacity total (1) less than 160 22,28,36,45 (not including 160) less than 90 type 90 or more (not including 90) FDCP2001 type FDCP2501 type 160 or more Liquid piping φ12.7 × 1.0 mm φ12.7 × 1.0 mm φ12.7 × 1.0 mm φ9.52 × 0.8 mm φ9.52 × 0.8 mm Intake gas piping φ25.4 × 1.4 mm φ28.58 × 1.4 mm φ25.4 × 1.4 mm φ19.05 × 1.2 mm φ15.88 × 1.
FDC-HKXR (Example) Outdoor unit Discharge gas piping Liquid piping Intake gas piping Flow divider pipe set for vertical divides Indoor unit Individual flow divide controller (DIS-V1KXR3E) Indoor unit Individual flow divide controller When the outdoor unit are installed at a higher level than the individual flow divide controller and a vertical flow divider is required for the piping connections of 2 or more individual flow divide controllers for 1 module, use the "flow divider pipe set" for vertical d
FDC-HKXR Good Note 1: When making branch connections (for both gas and liquid lines), be sure that the proper horizontal branches and vertical branches are used. No No Vertically Good Floor Floor Horizontally Floor Floor • Selection piping size Item Piping size(mm) Selection procedure A Same as the outdoor unit piping size (FDCP2501HKRE2) B Total capacity of connected indoor units Intake gas line Gas line ø19.05 ø28.58 Liquid line ø12.7 (236) ø19.05 ø25.4 ø12.7 ø19.05 ø9.
FDC-HKXR (3) Specification of unit piping (Pipe diameter. Connecting method) (a) Unit 1) Outdoor unit Unit: mm (in) Item Model 2) Gas line Pipe diameter FDCP2001HKXRE2 φ25.4 (1") FDCP2501HKXRE2 φ28.58 (1 1/8") Pipe diameter Connecting method φ12.7 (1/2") Brazing Brazing φ12.7 (1/2") Indoor unit Unit: mm (in) Gas line Item Pipe diameter Model 3) Liquid line Connecting method Liquid line Connecting method Pipe diameter 22, 28 type φ12.7 (1/2") 36 type φ12.7 (1/2") 45 type φ12.
FDC-HKXR (c) How to connect piping 1) Connection to front directions. a) Remove the front hall blank, pass through he hole the intake gas side, gas side and liquid pipes. and then connect then to the service valves and the on-site piping. (Because the liquid side pipe is on-site piping, bend it to the dimensions shown in the illustration at low.) 80 88 75 103 97 250 85 70 100 62 65 80 145 187 2) Connection to lower direction.
FDC-HKXR (4) Heat insulation (i) There is a need to insulate both gas and liquid piping with heat insulation for protection against heat and condensation. 1) Always use heat insulation to prevent condensation on the gas piping from becoming drain water and causing leakage during cooling and to prevent people from being burned by the high temperature of the surface of the gas piping as discharge gas flows through it. 2) Use heat insulation (pipe cover) on the flare connection sections of the indoor unit.
FDC-HKXR (7) Refrigerant charge amount (a) Additional; charge amount Item Additional charge amount per 1 m of liquid pipe Factory charge amount at time of shipment Indoor unit φ12.7 φ9.52 φ6.35 Outdoor unit Model FDCP2001HKXRE2 0.12 kg/m 0.06 kg/m 0.03 kg/m 11.
FDC-HKXR (c) Individual flow divide controller (Same power supply with the indoor units) Power supply wiring thickness (mm2 × number of wires) Item Power supply Supported model Signal wire thickness (mm2 × number of wires) 1-phase 2.0/2.0 × 2 220/240V 50Hz Note (1) Do not misconnect the central flow divide controller signal wire. 2.0 × 2 HPFD1R-E (2) Precaution in electric wiring.
FDC-HKXR Outdoor/Indoor units connection procedures Outdoor unit AB Individual flow divide controllor Power source (indoor unit side) Power source wire [Individual flow divide controller accessory wire (2m) To next units by turn L • N C N U Individual flow divide controller accessory wire (2m) Cn Cn B T4 Cn T L • N AB XYZ C N U Cn Cn B T4 1 Relay kit (Individual flow divide controller acessory) Cn T Indoor unit 2 XYZ Signal wire (between indoor unit) AB XYZ Remote controller wire XYZ Re
FDC-HKXR (b) If plural outdoor units are used 1) A maximum of 48 indoor units can be connected by using the crossover wiring method, with 2 wires for each side of the outdoor and indoor units. Outdoor unit Outdoor unit AB AB Outdoor unit Outdoor unit AB AB Double cores 0.75 ~ 2 mm2 Total length of signal wires: 1000 m or less AB AB Indoor unit AB Indoor unit AB Indoor unit Indoor unit 2) Indoor/outdoor wiring method for multiple floors.
FDC-HKXR (b) When controlling plural units. 1) Use the same procedure shown in the drawing above for the wiring of the power supply, both indoor and outdoor units and remote controller When the wiring length for the remote controller exceeds 100 m, use the wiring procedure shown in the drawing below. 2) Connect each of the indoor units for group controlling (3 cables) a) Connect the cables to the terminal blocks of X, Y, and Z for the indoor unit remote controller.
FDC-HKXR (6) Setting of unit address Addresses can be set either with the automatic address setting, remote control address setting or manual address setting depending on the combinations of address switches (see table) of the indoor and outdoor units. Operate the address switches before turning power on. Indoor unit Outdoor unit Address setting method Outdoor No. Outdoor No. Indoor No.
FDC-HKXR 1) 2) 3) Set the address switch of outdoor unit at 49. (This is set at 49 at shipment from factory.) Set the address switch of indoor unit at 49. (This is set at 49 at shipment from factory) Turn power on for the indoor and outdoor units. Addresses are set automatically. (No. in a range of 0 - 11.) For the auto address setting, power must be ON for both the indoor and outdoor units. If power is supplied to the indoor unit only, "Outdoor No." is indicated on the remote controller.
FDC-HKXR Detail of setting from the remote controller 1) If the power switch is turned on, the outdoor No. on the display flashes, and "--" on the return air temperature display section and "U--" on the time display section are lit. If power is not supplied to the outdoor unit, the outdoor No. only lights and you cannot set the address. In such occasion, to turn power on also for the outdoor unit. 2) Indoor No. increases 0, 1, 2, ... and up at each push on the room temperature setting ▲ switch.
FDC-HKXR 20.5.6 Test run (1) Before starting operation (a) Measure resistances between the electrical parts terminal block and grounded area using a 500 V Megger, insulator. Resistance must be higher than 1 MΩ. (b) Confirm whether the power source breaker (main switch) of the unit has been turned on for over 12 hours to energize the crankcase heater in advance of operation. (c) Make sure that the compressor bottom has been warmed.
FDC-HKXR (3) Cooling test run operation (Cooling test run can be performed in winter.) (a) Operation method ● In the normal cooling mode, hold down the “Temperature Set” switch while pushing the “Set” switch. ● Setting temperature is changed at 5˚C and the cooling test run is operated for 30 minutes. It stops after 30 minutes.
FDC-HKXR 20.6. MAINTENANCE DATA 20.6.1 Diagnosis of Microcomputer circuit (1) Confirmation of the error code on the remote controller (by pressing the inspection switch) and the inspection display and normal display lamps on PCBs of indoor/ outdoor units The microcomputer detects errors on electrical components, whitch include the microcomputer itself, errors on the power supply line and errors (overload, etc.
1 time flash Stays OFF 2 time flash Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing E11 E12 Keeps flashing 1 time flash Keeps flashing E10 E28 Stays OFF Keeps flashing E9 Stays OFF Stays OFF 1 time flash 1 time flash Keeps flashing 1 time flash Keeps flashing 2 time flash E7 Keeps flashing 2 time flash 3 time flash Keeps flashing Keeps flashing 32-sec time flash Stay OFF or Lights continuously 2 time flash Stays OFF Keeps flashing Keeps flashing
Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing E31 E34 E36 E37 E38 E39 E40 1070 E41 E42 E43 E45 E46 Stays OFF 7 time flash 9 time flash 1 time
FDC-HKXR 3) Display sequence of error, inspection display lamp a) One kind error Display corresponding to the error is shown. b) More than one errors. Section Error code of remote controller Display section • Displays the error of higher prority (When plural errors are persisting.) Inspection LED(red) of indoor unit PCB Inspection LED (red) of outdoor unit PCB •••••• • Displays the present errors. (When a new error has occurred after the former error was reset.
FDC-HKXR • Outdoor unit side Error detail Error code Timing of error detection 52C secondary side L3-phase wiring is open. An abnormal stop occurs when the L3-phase voltage is 0 V for 5 seconds running. (Detected with 52C ON only) Discharge temperature abnormality A stop occurs when this abnormality occurs for 2 seconds running at 130°C After a stop for 3 minutes, an recovery is automatically made. An abnormal stop occurs when this abnormality occurs twice for 60 minutes.
FDC-HKXR (a) Diagnosis by the power supply reset When any error occurs, reset the power supply as described below to see if it is the result of accidental noise, etc. Check at the indoor unit side.
FDC-HKXR (2) Reference Effect of noise • When noises inturude into the remote controller. Abnormal or irregular display such as the flashing of irrelevant display (lamp) (for example, LEDs of cooling and heating illuminated simultaneously or the like) is observed even if the remote controller is not operated or the remote controller and, as the result, the operation of units may be disabled or similar abnormal phenomenons are observed.
FDC-HKXR (ii) Parts layout on the outdoor unit PCB Operation output 18 17 16 19 20 23 • Function of DIP switch CNH 2 Name CNY(White) 2 CNI(White) L6 7 2 L9 ON IC4 SW2 CNE(White) X1 9 83 ON External input SW3-2 Outdoor unit number address setting switch (SW: Order of 1) OFF ON SW3-3 OFF Outdoor unit number address setting switch (SW: Order of 10) Name ON Checker 6 IC3 SW Test Forced Heat Cool Trial Snowing Defrosting Reset J3 J2 J1 OFF L7 L8 L10 IC8 IC5 C5 R17 R18 IC10 +
FDC-HKXR (iii) Check procedure depending on indication lamps (For the outdoor unit) 1 [Error on the outdoor unit signal line] Error display: (Detected during operation only) Indoor unit Red LED 2 time flash Green LED Keeps flashing Outdoor unit Red LED Stays OFF Green LED Stays OFF Power supply checked between R~N or terminal block YES Is there AC 17V checked between CNA2 (blue) ~ (blue) and AC 8V between (red) ~ (red) of outdoor unit transfomer? YES Power supply reset Is it YES Normalized?
FDC-HKXR 2 [Outdoor unit signal line error, power supply error] Error display: Indoor unit Red LED 2time flash Green LED Keeps flashing Outdoor unit Red LED Stays OFF Green LED Stays OFF (1) Did turn off the power of outdoor unit during operation? YES Power supply ON NO(1) • Blown fuse? • Broken or loose wire at L1, L2 or N Phase? • Was not there the power failure? Note (1) This case is limited to the separate power supplies to indoor/outdoor units.
FDC-HKXR 3 [Duplicated unit No. of outdoor units] Error display: Indoor unit Stays OFF Keeps flashing Red LED Green LED Red LED Green LED Is the unit No. duplicated on outdoor units? YES Outdoor unit 8 time flash Keeps flashing Correction NO Defective outdoor unit PCB Replacement (Defective unit No.
FDC-HKXR 6 [Defective outdoor unit heat exchanger thermistor] Error display: Outdoor unit Indoor unit Red LED Stays OFF Green LED Keeps flashing Is the outdoor unit heat exchanger hermistor connector OK? YES Red LED Keeps flashing Green LED Keeps flashing Are the outdoor unit heat exchnger thermistor characteristics OK, is there any broken wire? NO YES NO Defective outdoor unit PCB → Replacement (Defective outdoor unit heat exchanger thermistor input circuit) Outdoor unit heat exchanger th
FDC-HKXR [Defective discharge gas thermistor] Error display: Outdoor unit Red LED Stays OFF Green LED Keeps flashing Is the discharge gas thermistor connector connection OK? Red LED Keeps flashing Green LED Keeps flashing Are thr discharge gas thermistor characteristics OK, is there no broken wire? YES NO NO Defective discharge gas thermistor → Replacement Repair 9 T< = 80°C 5 50 0 0 Stays OFF Keeps flashing Red LED Green LED 20 50 80 100 120 Temperature [T] (°C) 3 time flash Keep
FDC-HKXR 10 [Power transistor overheating] Error display: Outdoor unit Indoor unit Red LED Stays OFF Green LED Red LED Keeps flashing Does the FMO rotate? YES Power transistor overheating(1) 4 time flash Green LED Keeps flashing Is the outdoor unit installation space proper? YES NO Does the IM (Inverter cooling fan) rotate? YES NO YES Defective inverter (Refer to 1090 page) NO Repair Note (1) The LD2 on the inverter control PCB lights for 3 minutes.
FDC-HKXR Current cut is indicated and the compressor cannot operate Is the insullaiton resistance of the compressor(1) proper? Disconnect the compressor wiring NO Defective compressor YES The compressor can operate Is the current cut function activated? Notes (1) When a short-circuit or ground-fault occurs in the compressor motor, the current cut function is also activated. Notes (1) If the insulation resistance is 10MΩ or more, it is normal.
FDC-HKXR 12 [Excessive number of indoor units connected] Error display: Outdoor unit Indoor unit Red LED Stays OFF Green LED Red LED Keeps flashing 7 time flash Green LED Keeps flashing (1) Doesn't the number of indoor unit connected exceed the specified value? YES Repair Notes (1) The maximum number of connectable unit of each model is as follows: 9. (2) Outdoor No. setting check for indoor units (to see if outdoor No.
FDC-HKXR • When communication is checked by the connector CnI, each value will be as follows. Contents of communication Connector CnI 14 1 Common 2 12V power supply 3 Transmission from outdoor unit 4 Reception from outdoor unit 5 Watch dog (communication from inverter PCB to outdoor unit PCB) 6 Inverter overheat 7 Current cut 12V Green LED Swings at 4.
FDC-HKXR 2) Louver motor does not operate Inspect at the indoor unit side. Does the louver operate at power on? Operate more than 1 min.
FDC-HKXR 4) Heating operation does not start NO Is heat outputted? Defective indoor unit PCB → Replace. YES (1) Are solenoid valve control relays OK? NO Defective relay → Replace. YES Is AC 200V applied at shunt controller connector CnB? YES Defective SVH (high pressure gas side solenoid valve) → Replace. 1086 NO Defective relay (XH) → Replace. Note (1) This is applicable only when a concentrated shunt controller is used.
FDC-HKXR (3) When the remote controller indication is nomal but the compressor cannot operate: (No check indication) • Give instructions so that the requested best frequency may be output, irrespective of the thermostat condition, from outdoor to indoor. A ccordingly, if the indoor/outdoor transmission is faulty, the compressor cannot operate. • When the SW3-4 is turned on, error indication is not provided if the indoor unit is not connected.
FDC-HKXR (4) Proceduer for checking the outdoor unit irrespective of indoor/outdoor transmission Turn off the outdoor unit power supply (Or pull out the connector CnA2 on the outdoor unit PCB) Set 45 in outdoor unit No. Turn ON the outdoor unit PCB(SW3-7) Turn ON the outdoor unit power supply Open the 63H1 Is the 52C turnd ON? (When connecting the CnA2 on the outdoor unit PCB) (Pull out Faston No.17 on the PCB) NO Does a voltage Appear at the 52C coil.
FDC-HKXR (5) Procedure for checking the inverter (No output is provided at the compressor (U,V and W).
FDC-HKXR ◆ Troubleshooting on the inverter side (1) Troubleshooting procedure (For the details of 1 to 7, refer to Outfoor Unit Check Pointd on the next page.) NO Check the outdoor unit control PCB. NO Is DC280V is YES provided at the Cn2 on the inverter PCB? Is 52C turned ON? Does the LD1 (green) on the inverterYES PCB flashing YES Defective inverter PCB → Replacement.
N L3 L2 L1 TB Green Control board Normality LED2 check: If this LED flashing, the operation of the microcomputer is normal.
FDC-HKXR MEMO 1092
19.2.
19.2.
19.2.6 Selection chart (1) Correct the cooling and heating capacity in accordance with the conditions as follows.
19.3.
19.5 APPLICATION DATA SAFETY PRECAUTIONS 19.5.
19.
20.2.
20.2.
20.2.6 Selection chart (1) Correct the cooling and heating capacity in accordance with the conditions as follows.
20.3.
20.5 APPLICATION DATA SAFETY PRECAUTIONS 20.5.
20.6.