Comfort setting cooling
General
In the default setting, cooling operation is not allowed. In order
to activate, change the setting on the menu 9.3.3 Cooling
system to “On”.
NOTE
The climate system must manage cooling operation.
Setting must be made by the installer when
commissioning the system.
Settings must be made by the installer when commissioning
the system.
If a room sensor is connected, it starts and stops cooling based
on both the room and the outdoor temperature. The lowest
calculated supply water temperature is set in menu 2.2.4.
Cooling operated from the outdoor sensor in
operating mode AutoC
If the cooling system is set to “On in menu 9.3.3 and the
outdoor temperature is greater or equivalent to the set start
temperature for cooling in menu 8.2.4, cooling starts.
Cooling stops when the outdoor temperature drops below the
set value minus the set value in menu 8.2.5.
The calculated supply water temperature is determined from the
selected cooling curve in menu 2.2.2 and the offset for cooling
curve, menu 2.2.1. Limitations, which are not in the diagram,
are included in the control system’s permitted min temperature.
framledningstemp