Specifications

FDCP140HKXE2B
FDKP45HKXE2
RCD-HKX-S-E
DIS-1KX30-E
DIS-1KX10-E
x1
x3
x3
x1
x1
Outdoor unit
Indoor unit
Remote controller
Branch pipe
Branch pipe
FDCP280HKXE2B
FDTWP36HKXE2
RCD-HKXSE
DIS-1KX30E
DIS-1KX10E
x1
x8
x8
x6
x1
Outdoor unit
Indoor unit, including panel
Remote controller
Branch pipe
Branch pipe
5
Selection of the independent branch pipe set
(
When five FDTP56HKXE2 units are connected to FDCP280HKXE2B
)
Selection of branch pipe
FDC P280HKXE2B
FDT P56HKXE2 FDT P56HKXE2 FDT P56HKXE2 FDT P56HKXE2 FDT P56HKXE2
1
2
3
4
4
3
2
1
Downstream total capacity is 280 (56 type x 5 units) > The downstream is 101 or more, so select DIS-IKX30-E
Downstream total capacity is 224 (56 type x 4 units) > The downstream is 101 or more, so select DIS-IKX30-E
Downstream total capacity is 168 (56 type x 3 units) > The downstream is 101 or more, so select DIS-IKX30-E
Downstream total capacity is 112 (56 type x 2 units) > The downstream is 101 or more, so select DIS-IKX30-E
B
C
A
Upstream
Branch pipe
The branch pipe size is selected
from the downstream B and C
total (=A) capacity.
Downstream
FDC
Optional independent branch pipe set
Corresponding outdoor unit
(horsepower)
Type
MHI Part No.
140HKXE2B
(
5
)
224HKXE2B/D
(
8
)
280HKXE2B/D
(
10
)
When downstream is less than 101
When downstream is 101 or more, 371 or less
DIS-1KX10-E
DIS-1KX30-E
The branch pipe must be used according to the total downstream capacity of the indoor unit.
(One set is always required for each branch.)
[ R407C ] FDCP140HKXE2B
[ R22 ] FDCJ140HKXE2B
[ R407C ] FDCP224HKXE2B
FDCP280HKXE2B
[ R22 ] FDCJ224HKXE2B
FDCJ280HKXE2B
(STOCK ONLY)
FDCJ224HKXE2D
FDCJ280HKXE2D
(NEW)
Outdoor unit
Breakdown of system components
Example of KX2 system 5HP
Example of KX2 system 10HP