Specifications

The Indoor Units up to the Maximum of 48 Units per One System
can be Controlled.
Daily/weekly program can be set by the
standard operation.
OOperation reservation for one week can be set.
OThe ON/OFF time can be set for three times a day
with a minute as the smallest unit. Setting OFF only
also prevents forgetting to set the off time.
OSetting the operation reservation day of the week to
the holiday setting makes it possible to temporarily
cancel an operation reservation.
OThe current time, day of the week, and a 24-hours
time graph for the day's program operation time can be
displayed.
Using together with the SLA-2A-E makes it
possible to set a schedule for each group.
OOne unit of weekly timer can control the maximum
of 48 indoor units in one system. And furthermore, by
combination with SLA-2A-E, the schedule setting for
each group (16 groups at the maximum) becomes
possible.
Example of combined system with SLA-2A-E
OIt is necessary to use together with SLA-2A-E for the
group start/stop by the weekly timer. The allowable
number of unit that can be connected to SLA-2A-E is
only one unit per one system and connection exceeding
Monitor mode
Display of current day of the week, time, and
program condition
Time setting
Setting of current day of the week, and time
Timer setting
Setting of timer program
Holiday setting
Setting of day of the week for the holiday
Weekly timer
(SCA-WT-E)
Center lock function is equipped.
ODisconnecting the jumper wire (J1) of SLA-2A-E, the
demand function is converted to the center lock
function.
OWhen the non-voltage contact input is supplied from
the commercial timer to the demand input contact of
SLA-2A-E, the unit which has been set to demand
setting in SLA-2A-E is converted to the center mode.
ODuring the center lock, the center/remote changeover
switch becomes invalid.
Operation
Allowed Prohibited
"Center" between this interval
Allowed
Stop
OFF
ON
Operation
Stop
Indoor unit
(Non-voltage)
contact input
New weekly timerSLA2A-E
Commercial timer, etc.
New weekly timer
Contact input
Indoor unit
Remote control
operation
R
The schedule and group setting for
each group by use together with
SLA-2A-E are performed at the SLA-
2A-E side.
OFF Start/stop in batch
ON
SW9-1
SW9-1
SW9=Control chahge over switch
(SW9-1 and sw9-2)
Power outage duration
stop
Operation
stop
Operation
(Example)
1
2
Out In In In In
SLA2A-E
SLA1-E
SLA1-E
SLA1-E
WT-E
Function item list
14
this is not allowed.
OSwitch the control changeover switch (SW 9) to the
appropriate side considering whether SLA-2A is used
together or the disposition after power outage recovery.
Power outage compensation function is equipped.
ODuring power outage or the power is off, the condition
set by the weekly timer is held. After restoration, the
monitor mode is displayed conforming to the time when
restored.
OSwitching the control changeover switch(SW9-2) to
ON, transmits an operation (stop) command after power
outage recovery using the timer setting mode under
recovery.
When the timer setting mode (as shown in the graph
below) is 1, a stop command is transmitted because the
system is in the stop mode at power outage recovery.
When it is 2, an operation command is transmitted
because the system is in the operation mode at power
outage recovery.
OPay attention that the control changeover switch is set
to OFF at delivery, therefore no operation (stop)
command is sent after power outage recovery.
Item
Equipment
Center console SLA-1-E
Center console SLA-2A-E
Individual control (Number of packaged air-conditioners)
Group control (Number of groups)
Start/stop (simultaneous, group and individual)
Group setting
Operation mode
(Cooling, dehumidification, heating, blowing and automatic)
Priority indication (Center/remote)
Room temperature setting
Wind volume switching
Forced stop
Power failure stop/recovery control
Demand control
Filter sign reset
Check sign reset
Operation condition (Operation/stop)
Priority indication (Center/remote)
Operation mode
(Cooling, dehumidification, heating, blowing and automatic)
Wind volume (Fast, strong and weak)
Set temperature
Automatic swing (ON/OFF)
Room temperature display
Filter sign
Check sign (Error/warning)
Remote controller function list
Control Monitoring