User manual

2. Technical specifications
Model FD-PAC / FDC71VN
Model
Technical specifications
Control kit Outdoor unit
FD-PAC FDC71VN
Nominal coolingcapacity (1) W 7100 (3200 ~ 8000)
Nominal heating capacity (1) W 8000 (3600 ~ 9000)
Power source 1 fase, 220/230/240V, 50Hz, N, PE
Operation data (3)
Cooling power consumption kW 2,01/2,01
Running current (cooling) A 8,9/9,2
Power factor (cooling) % 98/99
Heating power consumption kW 2,21/2,21
Running current (heating) A 9,8/10,2
Power factor (heating) % 99
Inrush current A 5,0
Moise level dB(A) - 48
Exterior dimensions (height x width x depth) mm 400 x 300 x 120 750 x 968 x 340
Nett weight Kg 8 60
Compressor type - -
Compressor motor kW - -
Refrigerant oil L - (M-MA32R)
Carterheating W - 33 (carterheating)
Starting method - Direct
Heat exchanger - Air (straight fin)
Defrost control Microprocessor controller de-icer
Refrigerant R410A
Refrigerant amount kg - 2,95 (pre-charged to 30 mtr)
Refrigerant expansion Elektronic expansion valve
Air handling equipment, fan type - Axial fan x 1
Motor - 55 x 1
Air flow m³/h Min.1200 3600
Air entrance temperature cooling min./ max. °C 16 / 32 -
Air entrance temperature heating min./ max. °C 10 / 32 -
Water entrance temperature cooling min./
max.
°C 16 / 32 -
Water entrance temperature heating min./
max.
°C 10 / 32 -
Safety equipment
-
Internal thermostat for fanmotor,
anomalous discharge temperature
protection
Refrigerant piping mm Liquid line 10mm, Gas line 16mm
Piping size mm Liquid line 9,52 mm (3/8”), Gas line 15,88mm (5/8”)
Connecting method Flare piping
Isolation Necessary (liquid and gasline)
Drain hose mm - Drain pan3x Ø20 mm
Accessoires -
Paneel (separate packing) -
Optional accessoires - -
Remote controller RC-E3 -
Notes
(1) The data are measured at the following conditions.
Item
Mode
Indoor temperature Outdoor temperature
standard
d.b. temp. w.b. temp. d.b. temp. w.b. temp.
Cooling 27°C 19°C 35°C 24°C
ISO-T1, JIS
B8616
Heating 20°C - 7°C 6°C
(2) This airconditioner is manufactured and tested in conformity with the following standards: ISO-T1”unitary
airconditioner”.
(3) The operation data indicate when the airconditioner is operated at 230V, 50hz.
(4) Values in ( ~ ) show the minimum to maximum range.
(5) Adjustment of the estimated output via DIP switch (see page 16).