Specifications
20 21
FDT
FDT 100/125/140VD
CEILING CASSETTE
-4way-
CLASS
A
A
[ INDOOR UNIT ]
RC-E4
(Option)
Wired remote control
RCH-E3
(Option)
RCN-T-36W-E
(Option)
Wireless remote control
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
kW
kW
kW
A
dB(A)
CMM
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDT100VNVD
FDT100VD
FDC100VN
FDT125VNVD
FDT125VD
FDC125VN
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.76/2.74
3.62/4.09
A/A
12.5
(5.0~14.0)
14.0
(4.0~16.0)
4.05/3.77
3.09/3.71
B/A
5(24)
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.98/4.57
2.81/3.50
C/B
SPECIFICATIONS
Indoor unit
Outdoor unit
Range of
usage
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
FDT100VSVD
FDT100VD
FDC100VS
FDT125VSVD
FDT125VD
FDC125VS
FDT140VSVD
FDT140VD
FDC140VS
FDT140VNVD
FDT140VD
FDC140VN
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.76/2.74
3.62/4.09
A/A
12.5
(5.0~14.0)
14.0
(4.0~16.0)
4.05/3.77
3.09/3.71
B/A
5(15)
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.98/4.57
2.81/3.50
C/B
Cooling:75 Heating:73
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Energy label
Inrush current (Max. running current)
Sound
Ievel
*1
Air flow
Exterior dimensions
Net weight
Panel
Air filter, Q'ty
Remote control(option)
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Indoor
Outdoor
Indoor
Outdoor
32.5(Unit:27 Panel:5.5)
Unit:298x840x840 Panel:35x950x950
Height x Width x Depth
Unit+Panel
mm
kg
mm
kg
kg(m)
ø
m
m
m
-15~43*
2
-20~20
845x970x370
3.8(30)
81 83
Cooling
Heating
O/U is higher
O/U is lower
O/U
O/U
Operating
temperature range
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
Rotary
9.52/15.88
50
30
15
Exterior dimensions
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
difference
Height x Width x Depth
Liquid/Gas
Hi:40
Me:37 Lo:35
49
Hi:27
Me:24 Lo:20
Hi:42
Me:40 Lo:37
Cooling:50 Heating:51
Hi:30
Me:27 Lo:23
Hi:43
Me:41 Lo:38
51
Hi:30
Me:27 Lo:23
Hi:40
Me:37 Lo:35
49
Hi:27
Me:24 Lo:20
Hi:42
Me:40 Lo:37
Cooling:50 Heating:51
Hi:30
Me:27 Lo:23
Hi:43
Me:41 Lo:38
51
Hi:30
Me:27 Lo:23
Cooling:75 Heating:73
Powerful-Hi can be selected. Sound level: 100/125/140VNVD 51dB, 100/125/140VSVD 51dB
Air flow: 100/125/140VNVD 37CMM, 100/125/140VSVD 37CMM
FDU 100/125/140VD
FDU
DUCT CONNECTED
-High Static pressure-
FDU 200/250VD
U-FCRA
[For 200/250VD]
(option)
Fan control kit
(100~200Pa)
RC-E4
(Option)
Wired
remote control
RCH-E3
(Option)
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Indoor
Outdoor
Indoor
Outdoor
Height x Width x Depth
Height x Width x Depth
Liquid/Gas
kW
kW
kW
A
dB(A)
CMM
Pa
mm
kg
mm
kg
kg(m)
ø
m
m
m
O/U
O/U
SPECIFICATIONS
Indoor unit
Outdoor unit
Range of
usage
FDU200VSVD
FDU200VD
FDC200VS
FDU250VSVD
FDU250VD
FDC250VS
20.0
(7.0~22.4)
22.4
(7.6~25.0)
50Hz:6.59/6.08
60Hz:6.58/5.84
50Hz:3.03/3.68
60Hz:3.04/3.83
B/A
5(24)
51
57
50Hz:51, 60Hz:60
25.0
(10.0~28.0)
28.0
(9.5~31.5)
50Hz: 9.91/8.50
60Hz:10.21/8.22
50Hz:2.52/3.29
60Hz:2.45/3.41
50Hz:E/C 60Hz:E/B
5(27)
52
Cooling:57 Heating:58
50Hz:68, 60Hz:80
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure
of FDU100/125/140 is 60Pa and that of FDU200/250 is 100Pa.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : External static pressure is changeable to be set by the remote control. Standard external static pressure is factory setting. MAX external static pressure is ''High static
pressure'' setting. The values of sound pressure level become 5dB(A) higher at eternal static pressure of 130Pa.
*
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Energy label
Inrush current (Max. running current)
Sound Ievel
*
1
Air flow
External static pressure
*
2
Exterior dimensions
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Standard:100, Max:200
360x1,570x830
92
1,300x970x370
Scroll
70
*
FDU100VSVD
FDU100VD
FDC100VS
*
FDU125VSVD
FDU125VD
FDC125VS
3Phase 380-415V 50Hz
*
FDU140VSVD
FDU140VD
FDC140VS
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.88/2.99
3.47/3.75
A/A
5(16)
Hi:42 Lo:37
49
Hi:34 Lo:27
12.5
(5.0~14.0)
14.0
(4.0~16.0)
4.04/3.79
3.09/3.69
B/A
5(18)
Cooling:50 Heating:51
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.95/4.43
2.83/3.61
C/A
5(19)
51
Hi:43 Lo:38
Hi:42 Lo:33.5
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
*
FDU140VNVD
FDU140VD
FDC140VN
1Phase
220-240V 50Hz
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.95/4.43
2.83/3.61
C/A
5(28)
51
Hi:43 Lo:38
Hi:42 Lo:33.5
83 122 14081
30
15
-15~43 *
3
Cooling
Heating
O/U is higher
O/U is lower
Operating
temperature range
-20~20 -15~20
Ref.piping length
Vertical height
difference
5.4(30)
9.52/25.4
7.2(30)
12.7/25.4
Rotary
3.8(30)
9.52/15.88
50
845x970x370
CLASS
A
A
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Energy label
Inrush current (Max. running current)
Sound Ievel
*
1
Air flow
External static pressure
Exterior dimensions
Net weight
Air filter, Q'ty
Remote control(option)
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Indoor
Outdoor
Indoor
Outdoor
Height x Width x Depth
Height x Width x Depth
Liquid/Gas
kW
kW
kW
A
dB(A)
CMM
Pa
mm
kg
mm
kg
kg(m)
ø
SPECIFICATIONS
Indoor unitOutdoor unit
Range of
usage
*
Not available in 60Hz
1Phase 220-240V 50Hz
*
FDU100VNVD
FDU100VD
FDC100VN
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.88/2.99
3.47/3.75
A/A
5(25)
Hi:42 Lo:37
49
Hi:34 Lo:27
Standard:50, Max:130
350x1,370x650
63
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
845x970x370
81
Rotary
3.8(30)
9.52/15.88
50
30
15
-20~20
Cooling
Heating
O/U is higher
O/U is lower
Operating
temperature range
-15~43*
2
-15~43*
3
m
m
m
O/U
O/U
Exterior dimensions
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
difference
*
FDU125VNVD
FDU125VD
FDC125VN
12.5
(5.0~14.0)
14.0
(4.0~16.0)
4.04/3.79
3.09/3.69
B/A
5(27)
Hi:43 Lo:38
Cooling:50 Heating:51
Hi:42 Lo:33.5
Standard:50, Max:130
350x1,370x650
63
Cooling:75 Heating:73
Micro Inverter
RCN-KIT3-E
(Option)
Wireless
remote control
Cooling:75 Heating:73
Cooling:150 Heating:145
Micro Inverter
Micro Inverter
Micro Inverter