Specifications
14 15
Control box
Fan motor
High static pressure
silent fan
Slide type fan system
Thin type duct connection
opening
Point
1
Enhanced installation workability
Point
2
Adaptability to higher static pressures
Quiet, Lightweight and Compact
With the FDU71, the noise level is
only 37dB (low), weight is only 40kg
and height is only 297mm.
In addition 600mm Drain Pump is
mounted in FDU71/100/125/140VD.
The indoor unit is completely
hidden in the ceiling, so this is
suitable for spaces with classy
interior decoration.
Outline drawing (Unit:mm)
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Energy label
Inrush current (Max. running current)
Sound Ievel
*
1
Air flow
External static pressure
Exterior dimensions
Net weight
Air filter, Q'ty
Remote control(option)
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Indoor
Outdoor
Indoor
Outdoor
Height x Width x Depth
Height x Width x Depth
Liquid/Gas
kW
kW
kW
A
dB(A)
CMM
Pa
mm
kg
mm
kg
kg(m)
ø
*
FDU125VNXVD
FDU125VD
FDC125VNX
*
FDU100VNXVD
FDU100VD
FDC100VNX
SPECIFICATIONS
Indoor unitOutdoor unit
Range of
usage
*
FDU140VNXVD
FDU140VD
FDC140VNX
*
Not available in 60Hz
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure
of FDU71/100/125/140 is 60Pa and that of FDU200/250 is 100Pa.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : External static pressure is changeable to be set by the remote control. Standard external static pressure is factory setting. MAX external static pressure is ''High static
pressure'' setting. The values of sound pressure level become 5dB(A) higher at eternal static pressure of 130Pa.
*
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
R410A
CLASS
A
A
FDU 71/100/125/140VD
FDU
DUCT CONNECTED
-High Static pressure-
FDU71VD
FDU100,125,140VD
FDU200,250VD
FDU 200/250VD
Height
297mm
U-FCRA
[For 200/250VD]
(option)
Fan control kit
(100~200Pa)
RC-E4
(Option)
Wired
remote control
RCH-E3
(Option)
1Phase 220-240V 50Hz
12.5
(5.0~14.0)
14.0
(4.0~17.0)
3.44/3.67
3.63/3.81
A/A
5(29)
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.78/2.90
3.60/3.86
A/A
5(25)
Hi:42 Lo:37
Hi:34 Lo:27
14.0
(5.0~16.0)
16.0
(4.0~18.0)
4.20/4.30
3.33/3.72
A/A
5(30)
Cooling:49 Heating:52
Standard:50, Max:130
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
Rotary
Installation workability
(FDU200,250VD)
Using piping attachment that
has flared connection and
brazed connection ends, there
is no need conduct brazing
work inside the outdoor unit.
Brazed
connection
ø22.2mm
232mm
Flared
connection
ø19.05mm
Cooling
Heating
O/U is higher
O/U is lower
Operating
temperature range
m
m
m
O/U
O/U
Exterior dimensions
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
difference
4.5(30)
100
-15~43*
2
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power Consumption
COP
Energy label
Inrush current (Max. running current)
Sound Ievel
*
1
Air flow
External static pressure
Exterior dimensions
Net weight
Air filter, Q'ty
Remote control(option)
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Indoor
Outdoor
Indoor
Outdoor
Height x Width x Depth
Height x Width x Depth
Liquid/Gas
kW
kW
kW
A
dB(A)
CMM
Pa
mm
kg
mm
kg
kg(m)
ø
SPECIFICATIONS
Indoor unitOutdoor unit
Range of
usage
*
FDU125VSXVD
FDU125VD
FDC125VSX
*
FDU100VSXVD
FDU100VD
FDC100VSX
*
FDU140VSXVD
FDU140VD
FDC140VSX
*
Not available in 60Hz
3Phase 380-415V 50Hz
12.5
(5.0~14.0)
14.0
(4.0~18.0)
3.44/3.67
3.63/3.81
A/A
5(18)
10.0
(4.0~11.2)
11.2
(4.0~16.0)
2.78/2.90
3.60/3.86
A/A
5(16)
14.0
(5.0~16.0)
16.0
(4.0~20.0)
4.20/4.30
3.33/3.72
A/A
5(19)
Cooling:49 Heating:52
Hi:43 Lo:38Hi:42 Lo:37
Hi:34 Lo:27
Cooling
Heating
O/U is higher
O/U is lower
Operating
temperature range
m
m
m
O/U
O/U
Exterior dimensions
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
difference
4.5(30)
9.52/15.88
100
-20~20
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
Rotary
30
15
-15~43*
2
1,300x970x370
105
350x1,370x650
63
Standard:50, Max:130
Hi:42 Lo:33.5
RCN-KIT3-E
(Option)
Wireless
remote control
600mm
High static pressure of 200 Pa (FDU200/250VD)
extends the degree of freedom in the designing
of air conditioners.
Hi:43 Lo:38
Hi:42 Lo:33.5
*
FDU71VNXVD
FDU71VD
FDC71VNX
7.1
(3.2~8.0)
8.0
(3.6~9.0)
2.15/2.15
3.30/3.72
A/A
5(17)
Hi:41 Lo:37
Cooling:51 Heating:48
Hi:20 Lo:17
Cooling:60 Heating:50
297x850x650
40
750x880(+88)x340
60
2.95(30)
50
350x1,370x650
63
1,300x970x370
105
-20~20
100
[ INDOOR UNIT ]
This is a real and earnest
model for duct air-conditioning.
A unit external static pressure
of up to 200 Pa
(FDU200/250VD) is possible.
Precise air flow designing is
possible.
9.52/15.88
30
15
Cooling:48 Heating:50 Cooling:48 Heating:50
100
Cooling:48 Heating:50