Specifications
46
OUTDOOR UNIT DIMENSIONS (
unit:mm)
Minimum installation space
Intake
outlet
Intake
Service
space
L1
L2
L3
L4
FDC100VN, 125VN, 140VN
100VS, 125VS, 140VS
Mark
A
B
C
D
E
F
Item
Refrigerant gas side pipe
connection tap
Refrigerant liquid side pipe
connection tap
Pipe/cable draw-out port
Drain discharge port
Anchor bolt hole
Cable draw-out port
ø15.88(flare)
ø9.52(flare)
ø
20.3x3places
M10x4places
ø
30.3x3places
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts.An anchor
bolt must not protrude more than 15mm.
(3) Where the unit is subject to strong winds, lay it in such
a direction that the blower outlet faces
perpendicularly to the dominant wind direction.
(4) Leave a 1m or larger space above the unit.
(5) A wall in front of the blower outlet must not exceed the
units height.
(6) The unit name plate is attached on the lower right
corner of the front panel.
500
Open
150
5
Open
5
300
5
Open
300
150
5
321
L1
L2
L3
L4
Dimensions
Examples of
installation
A
51
40
36
100
845
10
11050
195
242
279
970
50 15
55
5027
52
11050
195
B
B
A
A
Terminal block
F
C
C
VIEW A
C
5015
7050
150
40
F
E
370 4040
410 2020
55
60
388262
38
60
190 580 200
60 15
103 15
C
D
FDC71VNX
500
Open
100
250
Open
250
150
250
Open
300
100
250
321
L1
L2
L3
L4
Dimensions
Examples of
installation
Mark
A
B
C
D
E
Item
Service valve connection
(gas side)
Service valve connection
(liquid side)
Pipe/cable draw-out hole
Drain discharge hole
Anchor bolt hole
ø15.88(5/8")
(Flare)
M10x4places
ø20x3places
ø9.52(3/8")
(Flare)
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must
not protrude more the 15mm.
(3) Where the unit is subject to strong winds, lay it in such a
direction that the blower outlet faces perpendicularly to the
dominant wind direction.
(4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not exceed the units
height.
(6) The model name label is attached on the lower right corner of
the front.
165.5 25
Terminal block
B
A
C
30
30
48.5103.5
750
24
Minimum installation space
Intake
outlet
Intake
Service
space
L1
L2
L3
L4
D
E
2-R7.5
27
32
88
880
150580
150
61
310
223
60
15
340
61
47.5
19
380
418