Specifications

43
Outdoor unit
Internal/external Crossing
Indoor unit
Remote control
SL E Board
Network
options
X Y
X Y
X Y
A B
A B
Outdoor unit
Internal/external Crossing
Inside
Inside Inside Inside
RR
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Inside
Inside Inside Inside
RR
SL E
Board
Outdoor unit
Internal/external Crossing
Inside
Inside Inside
RR
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Inside
Inside
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Inside
Inside
SL E
Board
Network
options
Wireless Kit
Wireless
remote control
Basic Connections Plural Controls by Multiple Remote Controls. Mixture of Multiple Units
Plural Controls by Multiple Remote Controls. Mixture of Multiple Units Without Remote Control Wireless Kit
(3) Metal box dimension (unit:mm)
85
40
35
30
90 5
100
70
22.5
2-ø6
SUPERLINK E BOARD (SC-ADNA-E)
This board is used when conducting control of the single package (wired remote control unit) 1-type series using a network
option (SC-SL1N-E, SC-SL2NA-E, etc).
(1) Functions
(a) Transmits the settings from the network option to the indoor units.
(b) Returns the priority indoor unit data in response to a data request from the network option.
(c) Inspects the error status of connected indoor units and transmits the inspection codes to the network option.
(d) A maximum of 16 units can be controlled (if in the same operation mode).
(2) Wiring connection diagram
Set up “000” to “127” using address switch on the SL E board.
• Transmit the information of plural “Master” units to the network.
• Transmit the abnormalities of the “Slave” units to the network.
Setting the plural “Master/Slave” units with the dip SW of the printed circuit board.
Setting the “Master/Slave” remote controls with the dip SW of the remote control board.
Set the SL E board dip SW
to “Master” SW3-1 ON.
The network option SLA-1-
E, SL1N-E is not allowed
(This will disturb switching
of the operation mode)
Control System
Connected to the remote control terminals (no
polarity) (the length should be 600 m or shorter)
Connected to the terminals for
Superlink signal lines
MVVS 0.75 - 1.25mm
2
SL E board
OFF
SW3
SW1
LED2
Run
Abnormal
LED3
SW2
ON
A
B
X
Y
X
Y
A
B
Blue
Blue
Black
White
Master/Sub
address
Network address setting switches
[000]-(127)
200 m or shorter
300 m or shorter
400 m or shorter
600 m or shorter
0.5 mm
2
x 2 cores
0.75 mm
2
x 2 cores
1.25 mm
2
x 2 cores
2.0 mm
2
x 2 cores
SUPERLINK-