Specifications

24
R410AR410A
CLASS
A
AA
RCN-KIT3-E
Wireless
FDUM 100/125/140VF
RC-E5RC-EX1A
Wired
RCH-E3
Filter kit (option)
UM-FL3EF : for 100, 125, 140
external static pressure loss:5pa
Remote control (Option)
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power consumption
COP
Energy label
Inrush current (Max. running current)
Sound pressure
Ievel
*1
Sound power level
*1
Air flow
Static pressure
Exterior dimensions
Net weight
Air filter, Q'ty
Remote control(option)
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Indoor
Outdoor
Outdoor
Indoor
Outdoor
Height x Width x Depth
kW
kW
kW
A
dB(A)
dB(A)
CMM
Pa
mm
kg
mm
kg
kg(m)
ø
m
m
m
O/U
O/U
SPECIFICATIONS
Indoor unit
Outdoor unit
Range of
usage
FDUM100VNVF
FDUM100VF
FDC100VN
FDUM125VNVF
FDUM125VF
FDC125VN
FDUM140VNVF
FDUM140VF
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.80/3.02
3.57/3.71
A/A
12.5
(5.0~14.0)
14.0
(4.0~16.0)
3.90/3.88
3.21/3.61
A/A
5(24)
Hi:40 Me:34 Lo:29
Cooling:50 Heating:51
72
Hi:32 Me:26 Lo:20
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.95/4.69
2.83/3.41
C/B
Hi:40 Me:35 Lo:30
51
73
Hi:35 Me:28 Lo:22
FDUM100VSVF
FDUM100VF
FDC100VS
FDUM125VSVF
FDUM125VF
FDC125VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
FDUM140VSVF
FDUM140VF
FDC140VS
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.80/3.02
3.57/3.71
A/A
12.5
(5.0~14.0)
14.0
(4.0~16.0)
3.90/3.88
3.21/3.61
A/A
5(15)
Hi:40 Me:34 Lo:29
Cooling:50 Heating:51
72
Hi:32 Me:26 Lo:20
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.95/4.69
2.83/3.41
C/B
Hi:40 Me:35 Lo:30
51
73
Hi:35 Me:28 Lo:22
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure
of indoor units is 60Pa.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Hi:38 Me:36 Lo:30
49
70
Hi:28 Me:25 Lo:19
Hi:38 Me:36 Lo:30
49
70
Hi:28 Me:25 Lo:19
Standard:60, Max:100
81 83
Cooling
Heating
O/U is higher
O/U is lower
Operating
temperature range
Ref.piping length
Vertical height
difference
Exterior dimensions
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Height x Width x Depth
Liquid/Gas
Cooling:75 Heating:73
Powerful-Hi can be selected. Sound level: 100VN(S)VF 44dB, 125VN(S)VF 45dB, 140VN(S)VF 47dB
Air flow: 100VN(S)VF 36CMM, 125VN(S)VF 39CMM,140VN(S)VF 48CMM
R410A
A
FDUM
DUCT CONNECTED -Low/Middle Static pressure-
Micro Inverter
280x1,370x740
54
Procure locally
Wired:RC-EX1A, RC-E5, RCH-E3 Wireless:RCN-KIT3-E
845x970x370
Rotary
3.8(30)
9.52/15.88
50
30
15
-15~43*
2
-20~20
[ INDOOR UNIT ]
Micro Inverter