Specifications

23
R410A
A
FDU 100/125/140VD
FDU
DUCT CONNECTED
-High Static pressure-
FDU 200/250VF
U-FCRA
[For 200/250VF]
Fan control kit
(100~200Pa) (option)
RC-E5RC-EX1A
Wired
RCH-E3
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Indoor
Outdoor
Outdoor
Indoor
Outdoor
Height x Width x Depth
Height x Width x Depth
Liquid/Gas
kW
kW
kW
A
dB(A)
dB(A)
CMM
Pa
mm
kg
mm
kg
kg(m)
ø
m
m
m
O/U
O/U
SPECIFICATIONS
Indoor unit
Outdoor unit
Range of
usage
FDU200VSVF
FDU200VF
FDC200VS
FDU250VSVF
FDU250VF
FDC250VS
20.0
(7.0~22.4)
22.4
(7.6~25.0)
50Hz:6.59/6.08
60Hz:6.58/5.84
50Hz:3.03/3.68
60Hz:3.04/3.84
B/A
5(24)
51
57
74
50Hz:51, 60Hz:60
25.0
(10.0~28.0)
28.0
(9.5~31.5)
50Hz: 9.91/8.50
60Hz:10.21/8.22
50Hz:2.52/3.29
60Hz:2.45/3.41
50Hz:E/C 60Hz:E/B
5(27)
52
Cooling:57 Heating:58
74
50Hz:68, 60Hz:80
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure
of FDU100/125/140 is 60Pa and that of FDU200/250 is 100Pa.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : External static pressure is changeable to be set by the remote control. Standard external static pressure is factory setting. MAX external static pressure is ''High static
pressure'' setting. The values of sound pressure level become 5dB(A) higher at eternal static pressure of 130Pa.
*
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power consumption
COP
Energy label
Inrush current (Max. running current)
Sound pressure
Ievel
*1
Sound power level
*1
Air flow
External static pressure
*
2
Exterior dimensions
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Standard:100, Max:200
360x1,570x830
92
Scroll
70
*
FDU100VSVD
FDU100VD
FDC100VS
*
FDU125VSVD
FDU125VD
FDC125VS
3Phase 380-415V 50Hz
*
FDU140VSVD
FDU140VD
FDC140VS
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.88/2.99
3.47/3.75
A/A
5(16)
Hi:42 Lo:37
49
70
Hi:34 Lo:27
12.5
(5.0~14.0)
14.0
(4.0~16.0)
4.04/3.79
3.09/3.69
B/A
5(18)
Cooling:50 Heating:51
72
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.95/4.43
2.83/3.61
C/A
5(19)
51
73
Hi:43 Lo:38
Hi:42 Lo:33.5
Procure locally
Wired:RC-EX1A, RC-E5, RCH-E3 Wireless:RCN-KIT3-E
*
FDU140VNVD
FDU140VD
FDC140VN
1Phase
220-240V 50Hz
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.95/4.43
2.83/3.61
C/A
5(28)
51
Hi:43 Lo:38
73
Hi:42 Lo:33.5
83
1,300x970x370
122
1,505x970x370
140
81
30
15
-15~43 *
3
Cooling
Heating
O/U is higher
O/U is lower
Operating
temperature range
-20~20 -15~20
Ref.piping length
Vertical height
difference
5.4(30)
9.52/25.4
7.2(30)
12.7/25.4
Rotary
3.8(30)
9.52/15.88
50
845x970x370
R410AR410A
CLASS
A
AA
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power consumption
COP
Energy label
Inrush current (Max. running current)
Sound pressure
Ievel
*1
Sound power level
*1
Air flow
External static pressure
Exterior dimensions
Net weight
Air filter, Q'ty
Remote control(option)
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Indoor
Outdoor
Outdoor
Indoor
Outdoor
Height x Width x Depth
Height x Width x Depth
Liquid/Gas
kW
kW
kW
A
dB(A)
dB(A)
CMM
Pa
mm
kg
mm
kg
kg(m)
ø
SPECIFICATIONS
Indoor unitOutdoor unit
Range of
usage
*
Not available in 60Hz
1Phase 220-240V 50Hz
*
FDU100VNVD
FDU100VD
FDC100VN
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.88/2.99
3.47/3.75
A/A
5(25)
Hi:42 Lo:37
49
70
Hi:34 Lo:27
Standard:50, Max:130
350x1,370x650
63
Procure locally
Wired:RC-EX1A, RC-E5, RCH-E3 Wireless:RCN-KIT3-E
845x970x370
81
Rotary
3.8(30)
9.52/15.88
50
30
15
-20~20
Cooling
Heating
O/U is higher
O/U is lower
Operating
temperature range
-15~43*
2
-15~43*
3
m
m
m
O/U
O/U
Exterior dimensions
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
difference
*
FDU125VNVD
FDU125VD
FDC125VN
12.5
(5.0~14.0)
14.0
(4.0~16.0)
4.04/3.79
3.09/3.69
B/A
5(27)
Hi:43 Lo:38
Cooling:50 Heating:51
72
Hi:42 Lo:33.5
Standard:50, Max:130
350x1,370x650
63
Cooling:75 Heating:73
RCN-KIT3-E
Wireless
Cooling:75 Heating:73
Cooling:150 Heating:145
Micro Inverter
Micro Inverter
Remote control (Option)
Control box
Fan motor
High static pressure
silent fan
Slide type fan system
Thin type duct connection
opening
Adaptability to higher static pressures
High static pressure of 200 Pa (FDU200/250VF)