Specifications

13
R410A
A
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
(Min~Max)
Nominal heating capacity
(Min~Max)
Power consumption
COP
Energy label
Inrush current (Max. running current)
Sound pressure
Ievel
*1
Sound power level
*1
Air flow
ISO-T1(JIS)
ISO-T1(JIS)
Cooling/Heating
Cooling/Heating
Cooling/Heating
Indoor
Outdoor
Outdoor
Indoor
Outdoor
kW
kW
kW
A
dB(A)
dB(A)
CMM
mm
kg
mm
kg
kg(m)
ø
m
m
m
O/U
O/U
4.0
(1.1~4.7)
4.5
(0.6~5.4)
1.04/1.10
3.85/4.09
5(12)
5.0
(1.1~5.6)
5.4
(0.6~6.3)
1.56/1.45
3.21/3.72
5.6
(1.1~6.3)
6.7
(0.6~6.7)
1.99/2.07
2.81/3.24
C/C
FDTC40ZJXVF
FDTC40VF
SRC40ZJX-S
FDTC50ZJXVF
FDTC50VF
SRC50ZJX-S
FDTC60ZJXVF
FDTC60VF
SRC60ZJX-S
SPECIFICATIONS
Indoor unit
Outdoor unit
Range of
usage
A/AA/A
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Exterior dimensions
Net weight
Panel
Air filter, Q'ty
Remote control(option)
Cooling : 40 Heating : 33
Unit:248x570x570 Panel:35x700x700
18.5(Unit:15 Panel:3.5)
TC-PSA-25W-E
Pocket Plastic net x1 (Washable)
Wired:RC-EX1A, RC-E5, RCH-E3 Wireless:RCN-TC-24W-ER
640x800(+71)x290
45
Rotary
1.5(15)
6.35/12.7
30
20
20
-15~43
*
2
-15~20
Outline drawing (Unit:mm)
Height x Width x Depth
Unit+Panel
Exterior dimensions
Net weight
Type of compressor
Ref.amount precharged
Ref.piping size
Ref.piping length
Vertical height
difference
Cooling
Heating
O/U is higher
O/U is lower
Operating
temperature range
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:46 Me:39 Lo:32
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
5(15)
Height x Width x Depth
Liquid/Gas
Powerful-Hi can be selected. Sound level: 40/50/60ZJXVF 47dB Air flow: 40/50/60ZJXVF 13.5CMM
50
63
54
64
Cooling : 36 Heating : 33 Cooling : 41.5 Heating : 39
Cooling : 54 Heating : 50
63