Specifications
4342
Up to 96 cells (some cells can have two or
more indoor units and total number of indoor
units can be up to 128 units) are controlled
from the Internet Explorer.
In case of SC-BGWNA256-A/B, up to 256 cells
(some cells can have two or more indoor units
and total number of indoor units can be up to
256 units) are controlled centrally from a BMS.
In case of SC-BGWNA-B/BGWNA256-B, communication test by
qualified person regarding electric cost calculation function is
required before commissioning.
Up to 96 indoor units (48 indoor unit x 2) are
linked as an open network. Centrally controlled
through LonWorks.
Outdoor unit
Internal/external Crossing
Indoor unit
Remote control
SL E Board
Network
options
X Y
X Y
X Y
A B
A B
Outdoor unit
Internal/external Crossing
Inside
Inside Inside Inside
RR
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Inside
Inside Inside Inside
RR
SL E
Board
Outdoor unit
Internal/external Crossing
Inside
Inside Inside
RR
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Inside
Inside
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Inside
Inside
SL E
Board
Network
options
Wireless Kit
Wireless
remote control
Basic Connections Plural Controls by Multiple Remote Controls. Mixture of Multiple Units
Plural Controls by Multiple Remote Controls. Mixture of Multiple Units Without Remote Control Wireless Kit
(3) Metal box dimension (unit:mm)
85
40
35
30
90 5
100
70
22.5
2-ø6
SUPERLINK E BOARD (SC-ADNA-E)
This board is used when conducting control of the single package (wired remote control unit) 1-type series using a network
option (SC-SL1N-E, SC-SL2NA-E, etc).
(1) Functions
(a) Transmits the settings from the network option to the indoor units.
(b) Returns the priority indoor unit data in response to a data request from the network option.
(c) Inspects the error status of connected indoor units and transmits the inspection codes to the network option.
(d) A maximum of 16 units can be controlled (if in the same operation mode).
(2) Wiring connection diagram
Set up “000” to “127” using address switch on the SL E board.
• Transmit the information of plural “Master” units to the network.
• Transmit the abnormalities of the “Slave” units to the network.
Setting the plural “Master/Slave” units with the dip SW of the printed circuit board.
Setting the “Master/Slave” remote controls with the dip SW of the remote control board.
Set the SL E board dip SW
to “Master” SW3-1 ON.
The network option SLA-1-
E, SL1N-E is not allowed
(This will disturb switching
of the operation mode)
SC-SL1N-E
SC-ADNA-E
KX6 series
Start/stop control of up to 16 indoor units is
possible either individually or collectively. With
simple operations, you can effect centralized
control.
Centralized control of up to 64 indoor units. It
can allow connection with a weekly timer
without using any interface.
Easy operation realized with a large color LCD
and touch panel. Up to 128 indoor units can be
controlled, when SUPERLINK-2 systems are
connected.
SC-SL1N-E
SC-WGWNB-A/B*
(SC-WGWNB-B is with electric power calculation function)
PC windows central control
SC-BGWNA-A/B
SC-BGWNA256-A/B*
(BACnet gateway)
(SC-BGWNA-B/BGWNA256-B are with electric power calculation function)
BMS interface unit
SC-LGWNA-A*
(LonWorks gateway)
SC-SL2NA-E
Central Control
SC-SL4-AE/BE
Control SystemControl System
SC-ADNA-E
RAC series
(SRK/SRF-ZMX-S)
SC-ADNA-E
SC-BIKN-E
Connected to the remote control terminals (no
polarity) (the length should be 600 m or shorter)
Connected to the terminals for
Superlink signal lines
MVVS 0.75 - 1.25mm
2
SL E board
OFF
SW3
SW1
LED2
Run
Abnormal
LED3
SW2
ON
A
B
X
Y
X
Y
A
B
Blue
Blue
Black
White
Master/Sub
address
Network address setting switches
[000]-(127)
200 m or shorter
300 m or shorter
400 m or shorter
600 m or shorter
0.5 mm
2
x 2 cores
0.75 mm
2
x 2 cores
1.25 mm
2
x 2 cores
2.0 mm
2
x 2 cores
SC-SL2NA-E
SUPERLINK-SUPERLINK-
*Additional engineering service cost etc. is required. Please consult your dealer when using these system.
Production by order Production by orderProduction by order