Specifications

4140
RCN-KIT3-E
Wireless remote control
(Option)
FDF
FLOOR STANDING
R410A
SPECIFICATIONS
The values are for simultaneous Multi operation.
MULTI [ INDOOR UNIT ]
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : The values are for one indoor unit operation.
*
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
SPECIFICATIONS
The values are for simultaneous Multi operation.
Powerful-Hi can be selected. Sound level:140VN(S)XPVD1 42dB, 140VN(S)PVD1 42dB, 200VSPVD1/250VSPVD 54dB
Air flow: 140VN(S)XPVD1 18m
3
/min, 140VN(S)PVD1 18m
3
/min, 200VSPVD1/250VSPVD 29m
3
/min
FDF 71/100/125
Consideration on the Environment
All models employ R410A, with RoHS* directive
Convenience
Equipped with RS232C
for connection directly
to your PC monitoring
and service tasks made
simple with our service
software (“Mente PC”).
Monitoring Function
External switch connection CnT
Remote surveillance system Card key on-off
HOTEL
HOTEL
All indoor units are equipped with an additional
connection point-CnT-to connect indoor units to an
external ON/OFF switch; e.g. time clock, fire alarm,
etc.
Several radical design changes and engineering developments have brought about
a vast improvement in energy efficiency and environmental protection.
All models use refrigerant R410A
characterized by the ozone depletion
coefficient being 0.
In order to avoid the release of hazardous
substances into the environments, all
models have utilized lead-free solder
application. It has been considered to be
difficult to use lead-free solder for practical
applications because it requires higher
solder temperatures at assembly, which can
jeopardize reliability. However our PbF
soldering method can produce a higher
quality lead-free printed circuit board.
Employment of lead-free solder
Employment of
High performance and excellent energy
savings are achieved at the same time by
heat exchanger's increased capacity and
employment of high efficiency DC motor.
Excellent Energy Saving
Adapted to RoHS directive
RoHS:Restriction of Hazardous substances
ENERGY LABEL
No.626/2011 of 4 May 2011: energy
labeling of air-conditioners (below
cooling capacity 12kW).
No.206/2012 of 6 March 2012:
requirement for air-conditioners and
comfort fans.
Seasonal efficiency is the new way of
rating the true efficiency of heating and
cooling products over an entire year.
Set by the EU's new regulation
implementing Eco-Design Directive for
Energy Related Product (ErP) which
specifies the minimum efficiency of air-
conditioners manufacturers must
integrate into their products.
The new Seasonal Efficiency rating
system that must be used for heating
and cooling by all manufacturers are;
SEER - Seasonal Efficiency Ratio
(value in cooling)
SCOP - Seasonal Coefficient of
Performance (value in heating)
The new rating system will indicate the
true efficiency of the energy using
product at specified condition.
SEER and SCOP is defined in European
regulations listed below.
Set model name
FDF140VNXPVD1 FDF140VSXPVD1
Twin
Indoor unit FDF71VD1 FDF71VD1
Outdoor unit FDC140VNX FDC140VSX
Power source
1 Phase 220-240V 50Hz,
1 Phase 220V 60Hz
3 Phase380-415V 50Hz,
3 Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 14.0 ( 5.0 ~ 16.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 16.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )
Power consumption Cooling/Heating kW 4.83 / 4.97 4.83/ 4.97
EER/COP Cooling/Heating 2.90 / 3.22 2.90 / 3.22
Inrush current 220/230/240 V
A
5 5
Max. running current 26 15
Sound power
level*
1
Indoor*
2
Cooling/Heating
dB(A)
61 / 61 61 / 61
Outdoor
Cooling/Heating 72 / 72 72 / 72
Sound
pressure
level*
1
Indoor*
2
Cooling (Hi/Me/Lo)
39 / 35 / 33 39 / 35 / 33
Heating (Hi/Me/Lo)
39 / 35 / 33 39 / 35 / 33
Outdoor
Cooling/Heating 49 / 52 49 / 52
Air flow
Indoor*
2
Cooling (Hi/Me/Lo)
m
3
/min
16 / 14 / 12 16 / 14 / 12
Heating (Hi/Me/Lo)
16 / 14 / 12 16 / 14 / 12
Outdoor
Cooling/Heating 100 / 100 100 / 100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
1,850 x 600 x 320
Outdoor
1,300 x 970 x 370
Net weight
Indoor
kg
49
Outdoor
105
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
3
Heating -20~20
Air filter, Q'ty Plastic net x 1(washable)
Remote control
wired:RC-E5 (installed) wireless:RCN-KIT3-E (option)
Set model name
FDF140VNPVD1 FDF140VSPVD1 FDF200VSPVD1 FDF250VSPVD
Twin
Indoor unit FDF71VD1 FDF71VD1 FDF100VD1 FDF125VD
Outdoor unit FDC140VN FDC140VS FDC200VS FDC250VS
Power source
1 Phase 220-240V 50Hz,
1 Phase 220V 60Hz
3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 14.0 ( 5.0 ~ 14.5 ) 14.0 ( 5.0 ~ 14.5 ) 20.0 ( 7.0 ~ 22.4 ) 25.0 ( 10.0 ~ 28.0 )
Nominal heating capacity (Min~Max) kW 16.0 ( 4.0 ~ 16.5 ) 16.0 ( 4.0 ~ 16.5 ) 22.4 ( 7.6 ~ 25.0 ) 28.0 ( 9.5 ~ 31.5 )
Power consumption Cooling/Heating kW 5.16 / 5.01 5.16 / 5.01 6.50 / 6.42 8.95 / 9.17
EER/COP Cooling/Heating 2.71 / 3.19 2.71 / 3.19 3.08 / 3.49 2.79 / 3.05
Inrush current 220/230/240 V
A
5 5 5 5
Max. running current 24 15 19 22
Sound power
level*
1
Indoor*
2
Cooling/Heating
dB(A)
61 / 61 61 / 61 65 / 65 73 / 73
Outdoor
Cooling/Heating 73 / 73 73 / 73 74 / 74 74 / 74
Sound
pressure
level*
1
Indoor*
2
Cooling (Hi/Me/Lo)
39 / 35 / 33 39 / 35 / 33 50 / 48 / 44 50 / 48 / 44
Heating (Hi/Me/Lo)
39 / 35 / 33 39 / 35 / 33 50 / 48 / 44 50 / 48 / 44
Outdoor
Cooling/Heating 51 / 51 51 / 51 57 / 57 57 / 58
Air flow
Indoor*
2
Cooling (Hi/Me/Lo)
m
3
/min
16 / 14 / 12 16 / 14 / 12 26 / 23 / 19 26 / 23 / 19
Heating (Hi/Me/Lo)
16 / 14 / 12 16 / 14 / 12 26 / 23 / 19 26 / 23 / 19
Outdoor
Cooling/Heating 75 / 73 75 / 73 150 / 145 150 / 145
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
1,850 x 600 x 320
Outdoor
845 x 970 x 370 1,300 x 970 x 370 1,505 x 970 x 370
Net weight
Indoor
kg
49 52
Outdoor
81 83 122 140
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8") 9.52(3/8") / 22.22(7/8") 12.7(1/2") / 22.22(7/8")
Refrigerant line (one way) length m Max.50 Max.70
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
3
Heating -20~20 -15~20
Air filter, Q'ty Plastic net x 1(washable)
Remote control wired:RC-E5 (installed) wireless:RCN-KIT3-E (option)