Specifications
3938
SRK 50/60
R410A
We used the same aerodynamic
analysis technology as used in
developing jet engines.
Point
1
Jet Air Scroll
SPECIFICATIONS
The data are measured under the following conditions (ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : The values are for one indoor unit operation.
*
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
SRK
WALL MOUNTED
CFD (computational fluid dynamics),
used in blade shape design of jet
engines, has been applied to the design
of air channels in air conditioners to
develop the ideal air channel system (air
circulation). The airflow of the jets
created in this system enable a large
volume of air to be blown with minimum
power consumption, yet the air flow is
uniform, quiet and reaches points a long
distance from the blower.
Powerful airflow is realized by Jet technology.
Good for large living rooms and shops.
Increase your comfort.
Point
2
Long Reach Air Flow
15m
15m15m15m
SRK50/60ZMX
(in cooling operation)
Fast Slow
Colors in the figure show the air speed.
Max four indoor units are connectable.
SC-BIKN-E
RC-EX1A
RC-E5
SC-BIKN-E
Only used with outdoor units of TWIN, TRIPLE, MULTI System.
The values are for simultaneous Multi operation.
SPECIFICATIONS
The values are for simultaneous Multi operation.
Dimensions (Unit:mm)
890
309
60
21
881.9
6026
46.5
61.5
46.5
61.5
220
122.1
3
9
3.1
Piping hole
right
(right, left)61.5
Terminal block
MULTI [ INDOOR UNIT ]
RC-E5
Wired remote control
(Option)
RCH-E3
RC-EX1A
Set model name
SRK100VNXPZMX SRK125VNXPZMX SRK140VNXTZMX SRK100VSXPZMX SRK125VSXPZMX SRK140VSXTZMX
Twin Triple Twin Triple
Indoor unit SRK50ZMX-S SRK60ZMX-S SRK50ZMX-S SRK50ZMX-S SRK60ZMX-S SRK50ZMX-S
Outdoor unit FDC100VNX FDC125VNX FDC140VNX FDC100VSX FDC125VSX FDC140VSX
Power source
1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0)
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 ) 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )
Power consumption Cooling/Heating kW 2.66 / 2.60 3.60 / 3.48 3.98 / 3.68 2.66 / 2.60 3.60 / 3.48 3.98 / 3.68
EER/COP Cooling/Heating 3.76 / 4.31 3.47 / 4.02 3.52 / 4.35 3.76 / 4.31 3.47 / 4.02 3.52 / 4.35
Inrush current 220/230/240 V
A
5 5 5 5 5 5
Max. running current 24 26 26 15 15 15
Sound power
level*
1
Indoor*
2
Cooling/Heating
dB(A)
60 / 64 64 / 64 60 / 64 60 / 64 64 / 64 60 / 64
Outdoor
Cooling/Heating 70 / 70 70 / 70 72 / 72 70 / 70 70 / 70 72 / 72
Sound
pressure
level*
1
Indoor*
2
Cooling (Hi/Me/Lo/Ulo)
47 / 40 / 27 / 25 51 / 41 / 29 / 25 47 / 40 / 27 / 25 47 / 40 / 27 / 25 51 / 41 / 29 / 25 47 / 40 / 27 / 25
Heating (Hi/Me/Lo/Ulo)
48 / 40 / 33 / 26 48 / 41 / 34 / 27 48 / 40 / 33 / 26 48 / 40 / 33 / 26 48 / 41 / 34 / 27 48 / 40 / 33 / 26
Outdoor
Cooling/Heating 48 / 50 48 / 50 49 / 52 48 / 50 48 / 50 49 / 52
Air flow
Indoor*
2
Cooling (Hi/Me/Lo/Ulo)
m
3
/min
13.5 / 11 / 8 / 7 14.5 / 12.5 / 8.5 / 7 13.5 / 11 / 8 / 7 13.5 / 11 / 8 / 7 14.5 / 12.5 / 8.5 / 7 13.5 / 11 / 8 / 7
Heating (Hi/Me/Lo/Ulo)
17 / 14.5 / 10.5 / 8 17.5 / 15 / 11 / 8.5 17 / 14.5 / 10.5 / 8 17 / 14.5 / 10.5 / 8 17.5 / 15 / 11 / 8.5 17 / 14.5 / 10.5 / 8
Outdoor
Cooling/Heating 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
309 x 890 x 220
Outdoor
1,300 x 970 x 370
Net weight
Indoor
kg
15
Outdoor
105
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
3
Heating -20~20
Air filter, Q'ty Polypropylene net x 2(washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 & Interface kit:SC-BIKN-E
Set model name
SRK100VNPZMX SRK125VNPZMX SRK140VNTZMX SRK100VSPZMX SRK125VSPZMX SRK140VSXTZMX
Twin Triple Twin Triple
Indoor unit SRK50ZMX-S SRK60ZMX-S SRK50ZMX-S SRK50ZMX-S SRK60ZMX-S SRK50ZMX-S
Outdoor unit FDC100VN FDC125VN FDC140VN FDC100VS FDC125VS FDC140VS
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5)
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 )
Power consumption Cooling/Heating kW 2.72 / 2.86 4.25 / 4.29 4.53 / 4.05 2.72 / 2.86 4.25 / 4.29 4.53 / 4.05
EER/COP Cooling/Heating 3.68 / 3.92 2.94 / 3.26 3.09 / 3.95 3.68 / 3.92 2.94 / 3.26 3.09 / 3.95
Inrush current 220/230/240 V
A
5 5 5 5 5 5
Max. running current 24 24 24 15 15 15
Sound power
level*
1
Indoor*
2
Cooling/Heating
dB(A)
60 / 64 64 / 64 60 / 64 60 / 64 64 / 64 60 / 64
Outdoor
Cooling/Heating 70 / 70 72 / 72 73 / 73 70 / 70 72 / 72 73 / 73
Sound
pressure
level*
1
Indoor*
2
Cooling (Hi/Me/Lo/Ulo)
47 / 40 / 27 / 25 51 / 41 / 29 / 25 47 / 40 / 27 / 25 47 / 40 / 27 / 25 51 / 41 / 29 / 25 47 / 40 / 27 / 25
Heating (Hi/Me/Lo/Ulo)
48 / 40 / 33 / 26 48 / 41 / 34 / 27 48 / 40 / 33 / 26 48 / 40 / 33 / 26 48 / 41 / 34 / 27 48 / 40 / 33 / 26
Outdoor
Cooling/Heating 49 / 49 50 / 51 51 / 51 49 / 49 50 / 51 51 / 51
Air flow
Indoor*
2
Cooling (Hi/Me/Lo/Ulo)
m
3
/min
13.5 / 11 / 8 / 7 14.5 / 12.5 / 8.5 / 7 13.5 / 11 / 8 / 7 13.5 / 11 / 8 / 7 14.5 / 12.5 / 8.5 / 7 13.5 / 11 / 8 / 7
Heating (Hi/Me/Lo/Ulo)
17 / 14.5 / 10.5 / 8 17.5 / 15 / 11 / 8.5 17 / 14.5 / 10.5 / 8 17 / 14.5 / 10.5 / 8 17.5 / 15 / 11 / 8.5 17 / 14.5 / 10.5 / 8
Outdoor
Cooling/Heating 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
309 x 890 x 220
Outdoor
845 x 970 x 370
Net weight
Indoor
kg
15
Outdoor
81 83
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max. 50
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
3
Heating -20~20
Air filter, Q'ty Polypropylene net x 2(washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 & Interface kit:SC-BIKN-E