Specifications
36 37
FDEN
CEILING SUSPENDED
R410A
SPECIFICATIONS
The values are for simultaneous Multi operation.
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : The values are for one indoor unit operation.
*
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
SPECIFICATIONS
The values are for simultaneous Multi operation.
SPECIFICATIONS The values are for simultaneous Multi operation.
FDEN 40/50/60/71/100/125
RCN-E1R
Wireless
RC-E5RC-EX1A
Wired
RCH-E3
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : The values are for one indoor unit operation.
*
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
SPECIFICATIONS
The values are for simultaneous Multi operation.
Powerful-Hi can be selected. Sound level: 100VN(S)PVF 46dB,
125VN(S)PVF 48dB,
140VNPVF1 50dB, 140VNTVF 46dB
Air flow: 100VN(S)PVF 11m
3
/min, 125VN(S)PVF 20m
3
/min, 140VNPVF1 20m
3
/min, 140VNTVF 11m
3
/min
Powerful-Hi can be selected. Sound level: 140VSPVF1 50dB, 200VSPVF1 46dB, 250VSPVF 50dB, 140VSTVF 46dB, 200VSTVF1 50dB, 200VSDVF 46dB, 250VSDVF 48dB
Air flow: 140VSPVF1 20
m
3
/min
, 200VSPVF1 28
m
3
/min
, 250VSPVF 32
m
3
/min
, 140VSTVF 11
m
3
/min
, 200VSTVF1 20
m
3
/min
, 200VSDVF 11
m
3
/min
, 250VSDVF 20
m
3
/min
Powerful-Hi can be selected. Sound level: 71VNXPVF 46dB, 100VN(S)XPVF 46dB, 125VN(S)XPVF 48dB, 140VN(S)XPVF1 50dB, 140VN(S)XTVF 46dB
Air flow: 71VNXPVF 11
m
3
/min
, 100VN(S)XPVF 11
m
3
/min
, 125VN(S)XPVF 20
m
3
/min
, 140VN(S)XPVF1 22
m
3
/min
, 140VN(S)XTVF 11
m
3
/min
MULTI [ INDOOR UNIT ]
Remote control (Option)
Set model name
FDEN71VNXPVF FDEN100VNXPVF
Twin
Indoor unit FDEN40VF FDEN50VF
Outdoor unit FDC71VNX FDC100VNX
Power source
1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 )
Nominal heating capacity (Min~Max) kW 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 )
Power consumption Cooling/Heating kW 2.08 / 2.40 3.02 / 3.49
EER/COP Cooling/Heating 3.41 / 3.33 3.31 / 3.21
Inrush current 220/230/240 V
A
5 5
Max. running current 17 24
Sound power
level*
1
Indoor*
2
Cooling/Heating
dB(A)
60 / 60 60 / 60
Outdoor
Cooling/Heating 66 / 66 70 / 70
Sound
pressure
level*
1
Indoor*
2
Cooling (Hi/Me/Lo)
39 / 38 / 37 39 / 38 / 37
Heating (Hi/Me/Lo)
39 / 38 / 37 39 / 38 / 37
Outdoor
Cooling/Heating 51 / 48 48 / 50
Air flow
Indoor*
2
Cooling (Hi/Me/Lo)
m
3
/min
10 / 9 / 7 10 / 9 / 7
Heating (Hi/Me/Lo)
10 / 9 / 7 10 / 9 / 7
Outdoor
Cooling/Heating 60 / 50 100 / 100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
210 x 1,070 x 690
Outdoor
750 x 880(+88) x 340
1,300 x 970 x 370
Net weight
Indoor
kg
28
Outdoor
60 105
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max. 50 Max. 100
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
3
Heating -20~20
Air filter, Q'ty Pocket plastic net x 2(Washable)
Remote control (option)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E1R
Set model name
FDEN125VNXPVF
FDEN140VNXPVF1
FDEN140VNXTVF FDEN100VSXPVF FDEN125VSXPVF FDEN140VSXPVF1 FDEN140VSXTVF
Twin Triple Twin Triple
Indoor unit FDEN60VF FDEN71VF1 FDEN50VF FDEN50VF FDEN60VF FDEN71VF1 FDEN50VF
Outdoor unit FDC125VNX FDC140VNX FDC140VNX FDC100VSX FDC125VSX FDC140VSX FDC140VSX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 ) 14.0 ( 5.0 ~ 16.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 18.0 ) 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 ) 16.0 ( 4.0 ~ 20.0 )
Power consumption Cooling/Heating kW 4.06 / 3.70 4.96 / 4.58 4.90 / 4.53 3.02 / 3.49 4.06 / 3.70 4.96 / 4.58 4.90 / 4.53
EER/COP Cooling/Heating 3.08 / 3.78 2.82 / 3.49 2.86 / 3.53 3.31 / 3.21 3.08 / 3.78 2.82 / 3.49 2.86 / 3.53
Inrush current 220/230/240 V
A
5 5 5 5 5 5 5
Max. running current 26 26 26 15 15 15 15
Sound power
level*
1
Indoor*
2
Cooling/Heating
dB(A)
60 / 60 62 / 62 60 / 60 60 / 60 60 / 60 62 / 62 60 / 60
Outdoor
Cooling/Heating 70 / 70 72 / 72 72 / 72 70 / 70 70 / 70 72 / 72 72 / 72
Sound
pressure
level*
1
Indoor*
2
Cooling (Hi/Me/Lo)
41 / 39 / 38 41 / 39 / 38 39 / 38 / 37 39 / 38 / 37 41 / 39 / 38 41 / 39 / 38 39 / 38 / 37
Heating (Hi/Me/Lo)
41 / 39 / 38 41 / 39 / 38 39 / 38 / 37 39 / 38 / 37 41 / 39 / 38 41 / 39 / 38 39 / 38 / 37
Outdoor
Cooling/Heating 48 / 50 49 / 52 49 / 52 48 / 50 48 / 50 49 / 52 49 / 52
Air flow
Indoor*
2
Cooling (Hi/Me/Lo)
m
3
/min
16 / 14 / 12 16 / 14 / 12 10 / 9 / 7 10 / 9 / 7 16 / 14 / 12 16 / 14 / 12 10 / 9 / 7
Heating (Hi/Me/Lo)
16 / 14 / 12 16 / 14 / 12 10 / 9 / 7 10 / 9 / 7 16 / 14 / 12 16 / 14 / 12 10 / 9 / 7
Outdoor
Cooling/Heating 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
210 x 1,320 x 690 210 x 1,070 x 690 210 x 1,320 x 690 210 x 1,070 x 690
Outdoor
1,300 x 970 x 370
Net weight
Indoor
kg
37 28 37 28
Outdoor
105
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
3
Heating -20~20
Air filter, Q'ty Pocket plastic net x 2(Washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E1R