Specifications

32 33
FDTC
CEILING CASSETTE -4way Compact (600 X 600mm)-
R410A
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : The values are for one indoor unit operation.
*
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
SPECIFICATIONS
SPECIFICATIONS
The values are for simultaneous Multi operation.
SPECIFICATIONS
The values are for simultaneous Multi operation. The values are for simultaneous Multi operation.
RCN-TC-24W-ER
Wireless
RC-E5RC-EX1A
Wired
RCH-E3
FDTC 40/50/60
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : The values are for one indoor unit operation.
*
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100/125VN(S)PVF 47dB, 140VN(S)TVF 47dB, 200/250VSDVF 47dB
Air flow: 100/125VN(S)PVF 13.5m
3
/min, 140VN(S)TVF 13.5m
3
/min, 200/250VSDVF 13.5m
3
/min
Powerful-Hi can be selected. Sound level: 71VNXPVF 47dB, 100/125VN(S)XPVF 47dB, 140VN(S)XTVF 47dB
Air flow: 71VNXPVF 13.5m
3
/min, 100/125VN(S)XPVF 13.5m
3
/min, 140VN(S)XTVF 13.5m
3
/min
MULTI [ INDOOR UNIT ]
Fits into standard
600 x 600 ceiling
Remote control (Option)
Set model name
FDTC71VNXPVF FDTC100VNXPVF FDTC125VNXPVF FDTC140VNXTVF FDTC100VSXPVF FDTC125VSXPVF FDTC140VSXTVF
Twin Triple Twin Triple
Indoor unit FDTC40VF FDTC50VF FDTC60VF FDTC50VF FDTC50VF FDTC60VF FDTC50VF
Outdoor unit FDC71VNX FDC100VNX FDC125VNX FDC140VNX FDC100VSX FDC125VSX FDC140VSX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 ) 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )
Power consumption Cooling/Heating kW 2.04 / 2.21 3.18 / 3.20 4.10 / 4.10 4.34 / 4.34 3.18 / 3.20 4.10 / 4.10 4.34 / 4.34
EER/COP Cooling/Heating 3.48 / 3.62 3.14 / 3.50 3.05 / 3.41 3.23 / 3.69 3.14 / 3.50 3.05 / 3.41 3.23 / 3.69
Inrush current 220/230/240 V
A
5 5 5 5 5 5 5
Max. running current 17 24 26 26 15 15 15
Sound power
level*
1
Indoor*
2
Cooling/Heating
dB(A)
60 / 60 60 / 60 60 / 60 60 / 60 60 / 60 60 / 60 60 / 60
Outdoor
Cooling/Heating 66 / 66 70 / 70 70 / 70 72 / 72 70 / 70 70 / 70 72 / 72
Sound
pressure
level*
1
Indoor*
2
Cooling (Hi/Me/Lo)
42 / 36 / 30 42 / 36 / 30 46 / 39 / 30 42 / 36 / 30 42 / 36 / 30 46 / 39 / 30 42 / 36 / 30
Heating (Hi/Me/Lo)
42 / 36 / 32 42 / 36 / 32 46 / 39 / 32 42 / 36 / 32 42 / 36 / 32 46 / 39 / 32 42 / 36 / 32
Outdoor
Cooling/Heating 51 / 48 48 / 50 48 / 50 49 / 52 48 / 50 48 / 50 49 / 52
Air flow
Indoor*
2
Cooling (Hi/Me/Lo)
m
3
/min
11.5 / 9 / 7 11.5 / 9 / 7 13.5 / 10 / 7 11.5 / 9 / 7 11.5 / 9 / 7 13.5 / 10 / 7 11.5 / 9 / 7
Heating (Hi/Me/Lo)
11.5 / 9 / 8 11.5 / 9 / 8 13.5 / 10 / 8 11.5 / 9 / 8 11.5 / 9 / 8 13.5 / 10 / 8 11.5 / 9 / 8
Outdoor
Cooling/Heating 60 / 50 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
Unit: 248 x 570 x 570 Panel: 35 x 700 x 700
Outdoor
750 x 880(+88) x 340
1,300 x 970 x 370
Net weight
Indoor
kg
18.5(Unit:15 Panel:3.5)
Outdoor
60 105
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50 Max.100
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
3
Heating -20~20
Panel TC-PSA-25W-E
Air filter, Q'ty Pocket plastic net x 1(Washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-TC-24W-ER