Specifications

22 23
R410A
RCN-KIT3-E
Wireless
FDUM 100/125/140
RC-E5RC-EX1A
Wired
RCH-E3
Filter kit (option)
UM-FL3EF : for 100, 125, 140
external static pressure loss:5Pa
Remote control (Option)
Remote control (Option)
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
External static pressure of indoor units is 60Pa.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level
become 5dB(A) higher at external static pressure of 100Pa.
*
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100VN(S)VF1 44dB, 125VN(S)VF 45dB, 140VN(S)VF 47dB
Air flow: 100VN(S)VF1 36m
3
/min, 125VN(S)VF 39m
3
/min,140VN(S)VF 48m
3
/min
R410A
FDEN 100/125/140
RCN-E1R
Wireless
RC-E5RC-EX1A
Wired
RCH-E3
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100VN(S)VF1 46dB, 125/140VN(S)VF 50dB
Air flow: 100VN(S)VF1 28
m
3
/min
, 125/140VN(S)VF 32
m
3
/min
FDUM FDEN
CEILING SUSPENDEDDUCT CONNECTED -Low/Middle Static pressure-
[ INDOOR UNIT ]
Micro Inverter
Dimensions : refer to page 16Dimensions : refer to page 14
Set model name
FDUM100VNVF1 FDUM125VNVF FDUM140VNVF FDUM100VSVF1 FDUM125VSVF FDUM140VSVF
Indoor unit FDUM100VF1 FDUM125VF FDUM140VF FDUM100VF1 FDUM125VF FDUM140VF
Outdoor unit FDC100VN FDC125VN FDC140VN FDC100VS FDC125VS FDC140VS
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 )
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 )
Power consumption Cooling/Heating kW 2.80 / 3.02 3.90 / 3.88 4.95 / 4.69 2.80 / 3.02 3.90 / 3.88 4.95 / 4.69
EER/COP Cooling/Heating 3.57 / 3.71 3.21 / 3.61 2.83 / 3.41 3.57 / 3.71 3.21 / 3.61 2.83 / 3.41
Inrush current 220/230/240 V
A
5 5 5 5 5 5
Max. running current 24 24 24 15 15 15
Sound power
level*
1
Indoor Cooling/Heating
dB(A)
65 / 65 67 / 67 70 / 70 65 / 65 67 / 67 70 / 70
Outdoor
Cooling/Heating 70 / 70 72 / 72 73 / 73 70 / 70 72 / 72 73 / 73
Sound
pressure
level*
1
Indoor
Cooling (Hi/Me/Lo)
38 / 36 / 30 40 / 34 / 29 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Heating (Hi/Me/Lo)
38 / 36 / 30 40 / 34 / 29 40 / 35 / 30 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Outdoor
Cooling/Heating 49 / 49 50 / 51 51 / 51 49 / 49 50 / 51 51 / 51
Air flow
Indoor
Cooling (Hi/Me/Lo)
m
3
/min
28 / 25 / 19 32 / 26 / 20 35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Heating (Hi/Me/Lo)
28 / 25 / 19 32 / 26 / 20 35 / 28 / 22 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Outdoor
Cooling/Heating 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73
External static pressure*
2
Pa Standard:60 Max:100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
280 x 1,370 x 740
Outdoor
845 x 970 x 370
Net weight
Indoor
kg
54
Outdoor
81 83
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
3
Heating -20~20
Air filter Filter kit : UM-FL3EF (option)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E