Specifications
1918
Dimensions (Unit:mm)
R410A
Piping and drain hose connection can be selected out of 4-directions
and the selection makes installation workability more effective.
Due to slim design (Depth: 320mm), easy transportation and
installation are realized.
Easy Maintenance
The surface of heat exchanger can be appeared only removing the
front panel. Easy cleaning of heat exchanger is possible.
Point
1
Wide and powerful air flow
SPECIFICATIONS
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
FDF
FLOOR STANDING
Powerful-Hi can be selected. Sound level:71VNXVD1 42dB, 100VN(S)XVD1 54dB, 125/140VN(S)XVD 54dB
Air flow: 71VNXVD1 20m
3
/min, 100VN(S)XVD1 29m
3
/min, 125/140VN(S)XVD 29m
3
/min
[ INDOOR UNIT ]
RCN-KIT3-E
Wireless
remote control
(Option)
Wide and powerful air flow increase your comfort, realizing high
efficiency in combination with our highly advanced outdoor units.
Point
2
Easy Transportation and Installation workability
FDF 71/100/125/140
Set model name
FDF71VNXVD1 FDF100VNXVD1 FDF125VNXVD FDF140VNXVD
Indoor unit FDF71VD1 FDF100VD1 FDF125VD FDF140VD
Outdoor unit FDC71VNX FDC100VNX FDC125VNX FDC140VNX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 )
Power consumption Cooling/Heating kW 2.21 / 2.21 2.83 / 3.04 3.89 / 3.88 4.65 / 4.69
EER/COP Cooling/Heating 3.21 / 3.62 3.53 / 3.68 3.21 / 3.61 3.01 / 3.41
Inrush current 220/230/240 V
A
5 5 5 5
Max. running current 17 24 26 26
Sound power
level*
1
Indoor Cooling/Heating
dB(A)
61 / 61 65 / 65 73 / 73 73 / 73
Outdoor
Cooling/Heating 66 / 66 70 / 70 70 / 70 72 / 72
Sound
pressure
level*
1
Indoor
Cooling (Hi/Me/Lo)
39 / 35 / 33 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44
Heating (Hi/Me/Lo)
39 / 35 / 33 50 / 48 / 44 50 / 48 / 44 50 / 48 / 44
Outdoor
Cooling/Heating 51 / 48 48 / 50 48 / 50 49 / 52
Air flow
Indoor
Cooling (Hi/Me/Lo)
m
3
/min
18 / 16 / 14 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19
Heating (Hi/Me/Lo)
18 / 16 / 14 26 / 23 / 19 26 / 23 / 19 26 / 23 / 19
Outdoor
Cooling/Heating 60 / 50 100 / 100 100 / 100 100 / 100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
1,850 x 600 x 320
Outdoor
750 x 880(+88) x 340 1,300 x 970 x 370
Net weight
Indoor
kg
49 52
Outdoor
60 105
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50 Max.100
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
2
Heating -20~20
Air filter, Q'ty Plastic net x 1(washable)
Remote control wired:RC-E5 (installed) wireless:RCN-KIT3-E(option)
Set model name
FDF100VSXVD1 FDF125VSXVD FDF140VSXVD
Indoor unit FDF100VD1 FDF125VD FDF140VD
Outdoor unit FDC100VSX FDC125VSX FDC140VSX
Power source 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )
Power consumption Cooling/Heating kW 2.83 / 3.04 3.89 / 3.88 4.65 / 4.69
EER/COP Cooling/Heating 3.53 / 3.68 3.21 / 3.61 3.01 / 3.41
Inrush current 220/230/240 V
A
5 5 5
Max. running current 15 15 15
Sound power
level*
1
Indoor Cooling/Heating
dB(A)
65 / 65 73 / 73 73 / 73
Outdoor
Cooling/Heating 70 / 70 70 / 70 72 / 72
Sound
pressure
level*
1
Indoor
Cooling (Hi/Me/Lo)
50 / 48 / 44 50 / 48 / 44 50 / 48 / 44
Heating (Hi/Me/Lo)
50 / 48 / 44 50 / 48 / 44 50 / 48 / 44
Outdoor
Cooling/Heating 48 / 50 48 / 50 49 / 52
Air flow
Indoor
Cooling (Hi/Me/Lo)
m
3
/min
26 / 23 / 19 26 / 23 / 19 26 / 23 / 19
Heating (Hi/Me/Lo)
26 / 23 / 19 26 / 23 / 19 26 / 23 / 19
Outdoor
Cooling/Heating 100 / 100 100 / 100 100 / 100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
1,850 x 600 x 320
Outdoor
1,300 x 970 x 370
Net weight
Indoor
kg
52
Outdoor
105
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
2
Heating -20~20
Air filter, Q'ty Plastic net x 1(washable)
Remote control wired:RC-E5 (installed) wireless:RCN-KIT3-E(option)