Specifications
1716
Dimensions (Unit:mm)
model
FDEN40,50
FDEN60,71
FDEN100~140
a
1022
1272
1572
b
990
1240
1540
c
1070
1320
1620
d
215
215
255
e
210
210
250
Dimension Table
68
410
690
135 145
271
235
109
53
195
52
290(Suspension bolts pitch)
Holes for suspension bolts
(M8 to M10
x
4pcs.Not included)
Liquid piping
Gas piping
Drain hole
connection(1)
(VP20 (O.D.26))
300
100
150
5
Space for installation and service
or more
or more
or more
or more
Obstacles
10
53
Note(1) The slope of drain piping
inside the unit is able
to take incline of 10mm.
Drain hole
76
75
110
135
308
b
d
c
40
24
e 5
173
40
24
a (Suspension bolts pitch)
Air outlet
Liquid piping
Gas piping
Indication board
Air inlet grille
connection(1)
(VP20(O.D.26))
Drain hole
connection(1)
(VP20(I.D.20))
FDEN 40/50/60/71/100/125/140
R410A
The refrigerant pipe from the unit can be arranged in three directions,
rear, right and up. The drain pipe can be arranged in two directions, left
and right. This will allow a free layout of piping for various installation
conditions. The unit can only be serviced from the bottom.
Increased freedom of a piping layout
Point
1
Improved installation workability
Rear
Right
Up
All models fit compactly on ceiling. (Height-210mm or 250mm).
Plain, modern design featuring rounded edges gives room a
comfortable atmosphere.
FDEN40VF, 50VF weights 30kg the lightest level in the industry.
Convenient and quick installation.
Height
210mm
Point
2
Compact and modern design
SPECIFICATIONS
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
FDEN
CEILING SUSPENDED
Powerful-Hi can be selected. Sound level: 40/50ZMXVF 46dB, 60ZMXVF 48dB, 71VNXVF1 50dB, 100VN(S)XVF1 46dB, 125/140VN(S)XVF 50dB
Air flow: 40/50ZMXVF 11m
3
/min, 60ZMXVF 20m
3
/min, 71VNXVF1 20m
3
/min, 100VN(S)XVF1 28m
3
/min, 125/140VN(S)XVF 32m
3
/min
[ INDOOR UNIT ]
RCN-E1R
Wireless
RC-E5RC-EX1A
Wired
RCH-E3
Remote control (Option)
Set model name
FDEN40ZMXVF FDEN50ZMXVF FDEN60ZMXVF FDEN71VNXVF1 FDEN100VNXVF1
Indoor unit FDEN40VF FDEN50VF FDEN60VF FDEN71VF1 FDEN100VF1
Outdoor unit SRC40ZMX-S SRC50ZMX-S SRC60ZMX-S FDC71VNX FDC100VNX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 4.0 ( 1.1 ~ 4.7 ) 5.0 ( 1.1 ~ 5.6 ) 5.6 ( 1.1 ~ 6.3 ) 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 )
Nominal heating capacity (Min~Max) kW 4.5 ( 0.6 ~ 5.4 ) 5.4 ( 0.6 ~ 6.3 ) 6.7 ( 0.6 ~ 7.1 ) 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 )
Power consumption Cooling/Heating kW 1.02 / 1.10 1.53 / 1.46 1.78 / 1.87 2.11 / 2.11 2.80 / 2.88
EER/COP Cooling/Heating 3.92 / 4.09 3.27 / 3.70 3.15 / 3.58 3.36 / 3.79 3.57 / 3.89
Inrush current 220/230/240 V
A
5 5 5 5 5
Max. running current 12 15 15 17 24
Sound power
level*
1
Indoor Cooling/Heating
dB(A)
60 / 60 60 / 60 60 / 60 62 / 62 64 / 64
Outdoor
Cooling/Heating 63 / 63 63 / 63 64 / 64 66 / 66 70 / 70
Sound
pressure
level*
1
Indoor
Cooling (Hi/Me/Lo)
39 / 38 / 37 39 / 38 / 37 41 / 39 / 38 41 / 39 / 38 44 / 41 / 39
Heating (Hi/Me/Lo)
39 / 38 / 37 39 / 38 / 37 41 / 39 / 38 41 / 39 / 38 44 / 41 / 39
Outdoor
Cooling/Heating 50 / 50 54 / 50 54 / 54 51 / 48 48 / 50
Air flow
Indoor
Cooling (Hi/Me/Lo)
m
3
/min
10 / 9 / 7 10 / 9 / 7 16 / 14 / 12 16 / 14 / 12 26 / 23 / 21
Heating (Hi/Me/Lo)
10 / 9 / 7 10 / 9 / 7 16 / 14 / 12 16 / 14 / 12 26 / 23 / 21
Outdoor
Cooling/Heating 36 / 33 40 / 33 41.5 / 39 60 / 50 100 / 100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
210 x 1,070 x 690 210 x 1,320 x 690 250 x 1,620 x 690
Outdoor
640 x 800(+71) x 290 750 x 880(+88) x 340 1,300 x 970 x 370
Net weight
Indoor
kg
28 37 37 49
Outdoor
45 60 105
Ref.piping size
Liquid/Gas ømm 6.35(1/4") / 12.7(1/2") 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.30 Max.50 Max.100
Vertical height differences
Outdoor is higher/lower
m Max.20 / Max.20 Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
2
Heating -15~20 -20~20
Air filter, Q'ty Pocket Plastic net x2(Washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E1R
Set model name
FDEN125VNXVF FDEN140VNXVF FDEN100VSXVF1 FDEN125VSXVF FDEN140VSXVF
Indoor unit FDEN125VF FDEN140VF FDEN100VF1 FDEN125VF FDEN140VF
Outdoor unit FDC125VNX FDC140VNX FDC100VSX FDC125VSX FDC140VSX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 ) 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )
Power consumption Cooling/Heating kW 3.86 / 3.77 4.98 / 4.69 2.80 / 2.88 3.86 / 3.77 4.98 / 4.69
EER/COP Cooling/Heating 3.24 / 3.71 2.81 / 3.41 3.57 / 3.89 3.24 / 3.71 2.81 / 3.41
Inrush current 220/230/240 V
A
5 5 5 5 5
Max. running current 26 26 15 15 15
Sound power
level*
1
Indoor Cooling/Heating
dB(A)
67 / 67 67 / 67 64 / 64 67 / 67 67 / 67
Outdoor
Cooling/Heating 70 / 70 72 / 72 70 / 70 70 / 70 72 / 72
Sound
pressure
level*
1
Indoor
Cooling (Hi/Me/Lo)
46 / 44 / 43 46 / 44 / 43 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43
Heating (Hi/Me/Lo)
46 / 44 / 43 46 / 44 / 43 44 / 41 / 39 46 / 44 / 43 46 / 44 / 43
Outdoor
Cooling/Heating 48 / 50 49 / 52 48 / 50 48 / 50 49 / 52
Air flow
Indoor
Cooling (Hi/Me/Lo)
m
3
/min
29 / 26 / 23 29 / 26 / 23 26 / 23 / 21 29 / 26 / 23 29 / 26 / 23
Heating (Hi/Me/Lo)
29 / 26 / 23 29 / 26 / 23 26 / 23 / 21 29 / 26 / 23 29 / 26 / 23
Outdoor
Cooling/Heating 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
250 x 1,620 x 690
Outdoor
1,300 x 970 x 370
Net weight
Indoor
kg
49
Outdoor
105
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
2
Heating -20~20
Air filter, Q'ty Pocket Plastic net x2(Washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E1R