Specifications

12 13
Quiet, Lightweight and Compact
With the FDU71, the noise level is
only 25dB (low), weight is only 34kg
and height is only 280mm.
In addition 600mm Drain Pump is
mounted in FDU71/100/125/140.
The indoor unit is completely
hidden in the ceiling, so this is
suitable for spaces with classy
interior decoration.
Dimensions (Unit:mm)
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
External static pressure is 35Pa(71), 60Pa (100/125/140).
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level
become 5dB(A) higher at external static pressure of 200Pa.
*
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
R410A
FDU 71/100/125/140
FDU
DUCT CONNECTED
-High Static pressure-
Model FDU71VF1 Models FDU100VF1,125VF,140VF
Models FDU200,250VF
(Micro inverter only, refer to P21)
RC-E5RC-EX1A
Wired
RCH-E3
SPECIFICATIONS
RCN-KIT3-E
Wireless
600mm
[ INDOOR UNIT ]
Remote control (Option)
Enhanced installation workability
Powerful-Hi can be selected. Sound level: 71VNXVF1 38dB, 100VN(S)XVF1 44dB, 125VN(S)XVF 45dB, 140VN(S)XVF 47dB
Air flow: 71VNXVF1 24m
3
/min, 100VN(S)XVF1 36m
3
/min, 125VN(S)XVF 39m
3
/min, 140VN(S)XVF 48m
3
/min
Set model name
FDU100VSXVF1 FDU125VSXVF FDU140VSXVF
Indoor unit FDU100VF1 FDU125VF FDU140VF
Outdoor unit FDC100VSX FDC125VSX FDC140VSX
Power source 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )
Power consumption Cooling/Heating kW 2.68 / 3.02 3.49 / 3.77 4.28 / 4.42
EER/COP Cooling/Heating 3.73 / 3.71 3.58 / 3.71 3.27 / 3.62
Inrush current 220/230/240 V
A
5 5 5
Max. running current 16 18 19
Sound power
level*
1
Indoor Cooling/Heating
dB(A)
65 / 65 67 / 67 70 / 70
Outdoor
Cooling/Heating 70 / 70 70 / 70 72 / 72
Sound
pressure
level*
1
Indoor
Cooling (Hi/Me/Lo)
38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Heating (Hi/Me/Lo)
38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Outdoor
Cooling/Heating 48 / 50 48 / 50 49 / 52
Air flow
Indoor
Cooling (Hi/Me/Lo)
m
3
/min
28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Heating (Hi/Me/Lo)
28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Outdoor
Cooling/Heating 100 / 100 100 / 100 100 / 100
External static pressure*
2
Pa Standard:60 Max:200
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
280 x 1,370 x 740
Outdoor
1,300 x 970 x 370
Net weight
Indoor
kg
54
Outdoor
105
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
3
Heating -20~20
Air filter Procure locally
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
Set model name
FDU71VNXVF1 FDU100VNXVF1 FDU125VNXVF FDU140VNXVF
Indoor unit FDU71VF1 FDU100VF1 FDU125VF FDU140VF
Outdoor unit FDC71VNX FDC100VNX FDC125VNX FDC140VNX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 )
Power consumption Cooling/Heating kW 2.05 / 2.01 2.68 / 3.02 3.49 / 3.77 4.28 / 4.42
EER/COP Cooling/Heating 3.46 / 3.98 3.73 / 3.71 3.58 / 3.71 3.27 / 3.62
Inrush current 220/230/240 V
A
5 5 5 5
Max. running current 17 25 29 30
Sound power
level*
1
Indoor Cooling/Heating
dB(A)
65 / 65 65 / 65 67 / 67 70 / 70
Outdoor
Cooling/Heating 66 / 66 70 / 70 70 / 70 72 / 72
Sound
pressure
level*
1
Indoor
Cooling (Hi/Me/Lo)
33 / 29 / 25 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Heating (Hi/Me/Lo)
33 / 29 / 25 38 / 36 / 30 40 / 34 / 29 40 / 35 / 30
Outdoor
Cooling/Heating 51 / 48 48 / 50 48 / 50 49 / 52
Air flow
Indoor
Cooling (Hi/Me/Lo)
m
3
/min
19 / 15 / 10 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Heating (Hi/Me/Lo)
19 / 15 / 10 28 / 25 / 19 32 / 26 / 20 35 / 28 / 22
Outdoor
Cooling/Heating 60 / 50 100 / 100 100 / 100 100 / 100
External static pressure*
2
Pa Standard:35 Max:200 Standard:60 Max:200
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
280 x 950 x 635 280 x 1,370 x 740
Outdoor
750 x 880(+88) x 340 1,300 x 970 x 370
Net weight
Indoor
kg
34 54
Outdoor
60 105
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50 Max.100
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
3
Heating -20~20
Air filter Procure locally
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E