Specifications

1110
FDTC
R410A
CEILING CASSETTE
-4way Compact (600 X 600mm)-
Point
3
“CLEARER”Air Flow
Point
4
Installation Workability
SPECIFICATIONS
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
RCN-TC-24W-ER
New shape & angled louver redirects the air
current away from the ceiling, to reduce
ceiling stains
For wireless control simply insert the
infrared receiver kit on a corner of the
panel
wireless
remote control
Point
5
Compact and Convenient
Fits into standard
600 x 600 ceiling
Point
1
Taking OA (Outside Air) into inside
Point
2
Quiet operation
(Sound Pressure level in the Lo mode)
Previous
(Cooling/Heating)
New
(Cooling)
New
(Heating)
36
35
34
33
32
31
30
29
28
27
26
25
(dB)
35dB
30dB
32dB
5dB
Down
3dB
Down
Dimensions (Unit:mm)
Powerful-Hi can be selected. Sound level: 40/50/60ZMXVF 47dB Air flow: 40/50/60ZMXVF 13.5m
3
/min
[ INDOOR UNIT ]
600mm Drain Pump
Drain can be discharged upward by 600 mm from the ceiling
surface close to the indoor unit.
It allows a piping layout with a high degree of freedom
depending on the installation location.
600 x 600 ceiling
Indoor unit size (W:570 x D:570) brings easy installation for
600 x 600 ceiling and Panel size (700 x 700) is suitable for
600 x 600 ceiling. Height is the industry's lowest height level
248mm and weight is 15kg only.
Flexible hose
248mm
600mm
FDTC 40/50/60
RCN-TC-24W-ERRC-E5RC-EX1A
Wireless
Wired
RCH-E3
Remote control
(Option)
OA Spacer TC-OAS-E (option)
Joint Duct TC-OAD-E (option)
Utilizing OA spacer which comes as optional equipment, outside air
can be taken inside.
OA
OA
Panel
300mm
Ceiling
surface
Indoor Unit FDTC
OA Spacer
Joint Duct
Using 1 joint duct:
OA up to 1.3m
3
/min.
Using 2 joint ducts:
OA from 1.3 to 2.6m
3
/min.
Set model name
FDTC40ZMXVF FDTC50ZMXVF FDTC60ZMXVF
Indoor unit FDTC40VF FDTC50VF FDTC60VF
Outdoor unit SRC40ZMX-S SRC50ZMX-S SRC60ZMX-S
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 4.0 ( 1.1 ~ 4.7 ) 5.0 ( 1.1 ~ 5.6 ) 5.6 ( 1.1 ~ 6.3 )
Nominal heating capacity (Min~Max) kW 4.5 ( 0.6 ~ 5.4 ) 5.4 ( 0.6 ~ 6.3 ) 6.7 ( 0.6 ~ 6.7 )
Power consumption Cooling/Heating kW 1.04 / 1.10 1.56 / 1.45 1.99 / 2.07
EER/COP Cooling/Heating 3.85 / 4.09 3.21 / 3.72 2.81 / 3.24
Inrush current 220/230/240 V
A
5 5 5
Max. running current 12 15 15
Sound power
level*
1
Indoor Cooling/Heating
dB(A)
60 / 60 60 / 60 60 / 60
Outdoor
Cooling/Heating 63 / 63 63 / 63 64 / 64
Sound
pressure
level*
1
Indoor
Cooling (Hi/Me/Lo)
42 / 36 / 30 42 / 36 / 30 46 / 39 / 30
Heating (Hi/Me/Lo)
42 / 36 / 32 42 / 36 / 32 46 / 39 / 32
Outdoor
Cooling/Heating 50 / 50 54 / 50 54 / 54
Air flow
Indoor
Cooling (Hi/Me/Lo)
m
3
/min
11.5 / 9 / 7 11.5 / 9 / 7 13.5 / 10 / 7
Heating (Hi/Me/Lo)
11.5 / 9 / 8 11.5 / 9 / 8 13.5 / 10 / 8
Outdoor
Cooling/Heating 36 / 33 40 / 33 41.5 / 39
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
Unit: 248 x 570 x 570 Panel: 35 x 700 x 700
Outdoor
640 x 800(+71) x 290
Net weight
Indoor
kg
18.5(Unit:15 Panel:3.5)
Outdoor
45
Ref.piping size
Liquid/Gas ømm 6.35(1/4") / 12.7(1/2")
Refrigerant line (one way) length m Max.30
Vertical height differences
Outdoor is higher/lower
m Max.20 / Max.20
Outdoor operating
temperature range
Cooling
°C
-15~43*
2
Heating -15~20
Panel TC-PSA-25W-E
Air filter, Q'ty Pocket plastic net x 1(Washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-TC-24W-ER