Specifications
Graphic Operation Terminal GOT-F900 Creation of Display Screen (GT Designer) 20
20-13
20.5 Data display function
The ON/OFF status of bit devices in the PLC and the current value of word devices in the PLC
can be displayed.
20.5.1 Display of numerics
The "Numerical Display" object displays the data of word devices in the PLC in the form of
numeric.
*
**
*
Contents of setting
1) Number of digits
• Maximum allowable number of digits: 12 (Minus sign (-) and decimal point are counted
as digits.)
Number of digits after decimal point (Decimal Point)
• Enter the number of digits after a decimal point for a case where a decimal point is
displayed.
Example: When the displayed numeric is "2000"
2000: Number of digits after decimal point = 0
200.0: Number of digits after decimal point = 1
20.00: Number of digits after decimal point = 2
2.000: Number of digits after decimal point = 3
2) Format
• Select one style from decimal with sign, decimal without sign, hexadecimal, octal, binary
and real (Binary float value).
• Zero suppression
When the zero suppression function is not used, "0" is displayed in each digit position to
the left of the data. The number of "0"s will depend on the specified total number of
digits.
Example:
When the total number of digits is set to 7 and the number of digits after decimal point is
set to 2
• A numeric is displayed horizontally.
Hi
g
h-speed counter
-2147483648
C235
(
32 bits
)
11 di
g
its 10 di
g
its
If data whose number of di
g
its exceeds the maximum allowable
number of di
g
its is specified to be displa
y
ed, "?" is displa
y
ed.
to
2147483648
0012.34
"0" is displa
y
ed.