Specifications
Graphic Operation Terminal GOT-F900 Creation of Display Screens (FX-PCS-DU/WIN-E) 18
18-49
18.6.4 Send Data Bank (recipe function)
The GOT can store up to 4,000 16-bit data corresponding to data registers in the PLC. By
giving a command via a touch or function key, data can be read from/written to the PLC. For
data files, refer to "17.9 Data file".
*
**
*
Contents of setting
1) Bank No.
Enter a file No created using the screen creation software (when selecting "Direct").
Or file number can be specified using a control device "D0+6" (when selecting "Indirect").
2) Function
Specify the data file transfer direction.
GOT
(
PLC: Writes data stored in a data file in the GOT to a data register in the PLC.
PLC
(
GOT: Writes data stored in a data register in the PLC to a data file in the GOT.
#
##
#
Important point
• Data file transfer condition
"
✔
" indicates that transfer is enabled.
Do not set two or more "Send Data Bank" functions to one touch or one function key.
Even if the above attempt is made, the function registered last overwrites the previous one
because the data register number to read from/write to the PLC is fixed for the send data bank
function.
Attribute Contents of setting
Control Input Enter a key which actuates data transfer.
Bank No.
Enter a data file number to be transferred.
Select "Direct" or "Indirect".
Function Select "GOT
(
PLC" or "PLC
(
GOT".
PLC FX Series A Series
PLC memory type
$
:RAM
%
:EPROM *1
$
:RAM
$
:EPROM
%
:EEPROM
*1 When the read/write destination
is a data register, data can be
transferred without regard to the
memory type.
PLC operation status
$
:RUN
$
:STOP
$
:RUN
$
:STOP
GOT memory type
$
:Flash memory
$
:Flash memory
PLC entry code
%
: While entry
code is
registered
(while write is
forbidden)
$
:While entry
code is
unlocked or is
not registered
%
: While entry
code is
registered
(while write is
inhibited)
$
:While entry
code is
unlocked or is
not registered