Specifications

Graphic Operation Terminal GOT-F900 Creation of Display Screens (FX-PCS-DU/WIN-E) 18
18-48
#
##
#
Important point
1) Controlled bit device:
If "Operation" is set to "Momentary", the controlled bit device becomes OFF when the
display screen is changed over.
If the "Switch" object is registered in the common setting for all screens, it is effective on all
screens.
2) If two or more keys are pressed simultaneously:
If two or more switch functions are registered, and two keys are simultaneously pressed
both functions will be executed.
If three or more keys are pressed simultaneously, only the first two pressed will be effective.
3) If two or more functions are assigned to one touch key or one function key:
Two or more switch functions can be registered to one touch or function key.
4) If screens are overlaid:
If screens are overlaid using control devices, the screen call function or the "Overlay
Screen", the switch functions are effective on all of the base screen and the overlaying
screens. If switches are overlaid, the switch on the top screen is effective. Pay close
attention so that switches do not are not overlaid.
In switch areas A and B on the composed screen realized by overlay, each switch is
effective. However, if the area C is pressed, the switch B located on the top is effective.
5) Caution on connecting the SYSMAC C Series manufactured by OMRON
Using a forced set/reset by peripheral equipment in the SYSMAC C Series PLC locks the
PLC bit devices into their current state. This state cannot be changed by the PLC program.
In the above described situation, using the switch function in USER SCREEN MODE or
forced ON/OFF function in HPP MODE in the GOT will have the following consequences.
a) If a bit device is turned ON/OFF in the GOT, all the bit devices are released to change
state by the PLC program. (GOT uses the KC command)
F930GOT or F933GOT: prior to Version 4.40; F940GOT or F943GOT: prior to Version
6.40; F940WGOT: prior to Version 1.40
b) Only the device turned ON/OFF in the GOT is released to change state by the PLC
program. (GOT uses the FK command)
F930GOT-K: First version, F930GOT or F933GOT: Version 4.40 or later;
F940GOT or F943GOT: Version 6.40 or later; F940WGOT: Version 1.40 or later
A
BB
A
Base screen Overla
y
in
g
screen Overla
y
in
g
screen
C
Example